Specifications

1. Specification
Type
Model
Cooling Capacity
Heating Capacity
power input
Cooling
heating
Casing
Dimensions
Body
(W x D x H)
Coil
Rows x Columns x FPI
Fan
Type
Motor Output x Number
Running Current
Air Flow Rate(H/M/L)
(High Mode-factory set)
External Static Pressure mmAq(Pa)
Air Flow Rate(H/M/L)
(Standard Mode)
External Static Pressure mmAq(Pa)
Drive
Motor type
Temperature Control
Sound Absorbing Material Control
Air Filter
Safety Device
Pipe
Liquid Side
Connections
Gas Side
Drain(OD/ID)
Net Weight
Noise Level(SoundPress, 1.5m, H/M/L) dBA±3
Power Supply
Refrigerant Control
Power cable
Transmission cable
Notes:-
1. Capacities are based on the following conditions:
Cooling
• Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB
• Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
Heating
• Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB
• Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. EEV : Electronic Expansion Valve
5. To be added for more available Models
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Unit
ARNU07GBHA1
kW
2.2
kcal/h
1,900
7,500
Btu/h
2.5
kW
kcal/h
2,200
Btu/h
8,500
kW
0.118
kW
0.118
Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate
882x450x260
mm
34.7x17.7x10.2
inch
2x10x21
Sirocco Fan
W
118
A
0.92
cmm
7/6.5/6
247/230/212
cfm
8(80)
cmm
8.5/8/7.5
cfm
300/282/265
6(60)
Direct
BLDC
Microprocessor, Thermostat for cooling and heating
Foamed polystrene Foamed polystrene Foamed polystrene Foamed polystrene
-
Fuse
mm(inch)
Ø6.35(1/4)
mm(inch)
Ø12.7(1/2)
mm
26(57.3)
kg(lbs)
Ø / V / Hz
1, 220 ~ 240, 50
1, 220, 60
EEV
mm
CV1.5 x 3C
2
CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C CVV-SB 1.25 x 2C
mm
2
- 116 -
Ceiling Concealed Duct(High Static)
ARNU09GBHA1
ARNU12GBHA1
2.8
3.6
2,400
3,100
9,600
12,300
3.2
4.0
2,800
3,400
10,900
13,600
0.118
0.118
0.118
0.118
882x450x260
882x450x260
34.7x17.7x10.2
34.7x17.7x10.2
2x10x21
2x10x21
Sirocco Fan
Sirocco Fan
118
118
0.92
0.92
9/8/7
12/10/9
318/282/247
424/353/318
8(80)
8(80)
8.5/8/7.5
11/8.5/8
300/282/265
388/300/282
6(60)
6(60)
Direct
Direct
BLDC
BLDC
-
-
Fuse
Fuse
Ø6.35(1/4)
Ø6.35(1/4)
Ø12.7(1/2)
Ø12.7(1/2)
26(57.3)
26(57.3)
1, 220 ~ 240, 50
1, 220 ~ 240, 50
1, 220, 60
1, 220, 60
EEV
EEV
CV1.5 x 3C
CV1.5 x 3C
ARNU15GBHA1
4.5
3900
15400
5
4300
17100
0.118
0.118
882x450x260
34.7x17.7x10.2
2x10x21
Sirocco Fan
118
0.92
14/12/10
494/424/353
8(80)
13.5/12/11
477/424/388
6(60)
Direct
BLDC
-
Fuse
Ø6.35(1/4)
Ø12.7(1/2)
26(57.3)
1, 220 ~ 240, 50
1, 220, 60
EEV
CV1.5 x 3C
LGE Internal Use Only