Mitsubishi Electric Mr.Slim PAR-30MAA Technical Manual page 78

Ma remote controller
Hide thumbs Also See for Mr.Slim PAR-30MAA:
Table of Contents

Advertisement

When grouping in different refrigerant systems
Standard 1:1
Ref
Outdoor
address = 00
unit
(Main)
Indoor unit
Main remote
controller
* The refrigerant address is set with the outdoor unit's DIP switch. (Refer to the Outdoor Unit Installation Manual for details.)
* All indoor units enclosed in the box are controlled as one group.
(a) Wiring the remote controller and indoor unit
• Connect to the terminal block (TB5) for the indoor unit's remote controller wire. (The terminal block has no polarity.)
• When using the simultaneous multi-type and different indoor unit models exist, always connect the remote controller to the
indoor unit having the most functions (wind speed, vane, louver, etc.).
(b) Wiring to group with different refrigerant systems
• Groups are formed with the remote controller cables. Use crossover wires between the remote controller terminal blocks (TB5)
of the main indoor unit in each refrigerant system to be grouped.
• If there are different indoor unit models in the same group, always use the outdoor unit to which the indoor unit with most
functions (wind speed, vane, louver, etc.) is connected as the main unit (refrigerant address = 00).
If the main unit is a simultaneous multi-type, make sure that the conditions in (a) above are satisfied.
• Up to 16 refrigerant systems can be controlled as one group using the MA remote controller.
(c) Up to two remote controllers can be connected to one group.
• If two remote controllers are connected to one group, always set the main remote controller and sub remote controller.
• If only one remote controller is connected to the group, always set the main remote controller. If two remote controllers are
connected to one group, set each remote controller as the main or sub remote controller. (Refer to the Installation Manual
(Setting Section.)
(d) Overall distance of remote controller cable
• The overall distance is 500m. Use a 0.3m
The overall distance is 200m when two remote controllers are connected.
«Note»
Do not use a crossover wire between the remote controller terminal blocks (TB5) for the indoor units within the
same refrigerant system.
►The system may not operate correctly if a crossover wire is used.
When connecting to the remote controller terminal block (TB5) of the indoor unit, up to two wires having the same
size can be connected to one terminal block.
►Improper connections can result in contact defects or wire disconnection.
Do not use crossover wires between the remote controllers.
►Only one wire can be connected to the remote controller's terminal block.
Twin
Outdoor
Ref address = 00
unit
Indoor unit
Main remote
controller
78
Twin
Ref
Outdoor
address = 01
unit
(Sub)
Indoor unit
Indoor unit
Sub remote
controller
2-core cable for the remote controller cable. (Procure locally.)
2
Standard 1:1
Ref
Outdoor
address
unit
= 00
Indoor unit
Indoor unit
Main remote
controller
Triple
Ref
Outdoor
address = 02
unit
(Sub)
Indoor unit
Indoor unit
Indoor unit
Twin
Ref
Outdoor
address
unit
= 01
Indoor unit
Indoor unit
Standard 1:1
Outdoor
Ref address = 00
unit
Indoor unit
Main remote
Sub remote
controller
controller