Technical Data

Technical Considerations

The Enphase M215 Microinverters are electrically compatible with most 60-cell PV modules. Be sure to verify
the voltage and current specifications of your PV module match those of the microinverter. For more
information, refer to our list of compatible PV modules at http://www.enphase.com/support/downloads.
WARNING: You must match the DC operating voltage range of the PV module with the
allowable input voltage range of the Enphase Microinverter.
WARNING: The maximum open circuit voltage of the PV module must not exceed the
specified maximum input voltage of the Enphase Microinverter.
The output voltage and current of the PV module depends on the quantity, size and temperature of the PV cells,
as well as the insolation on each cell. The highest PV module output voltage occurs when the temperature of the
cells is the lowest and the PV module is at open circuit (not operating). The maximum short circuit current rating
of the PV module must be equal to or less than the maximum input DC short circuit current rating of the
microinverter.
24
Copyright © 2012 Enphase Energy
M215 Installation and Operation
141-00021 Rev 01