Preparing the Site
• Full redundancy (n+1 and grid redundancy)—Add enough power supplies (reserve power supplies) to at least equal
the output of the active power supplies (number of power supplies calculated in Step 2). For power supply (n+1)
redundancy, ensure that you have at least one extra power supply. For input-source (grid) redundancy, you will
probably double the number of power supplies. You must plan for a second power source with at least the same
amount of input power for the reserve power supplies. For example, if you calculate that you need two 3-kW power
supplies for 6 kW of active power, then you need another two 3-kW power supplies for 6 kW of reserve power
(for a total of four 3-kW power supplies used for active and reserve power). Either one of the reserve power supplies
can replace any of the active power supplies.
Step 4
Be sure that the power source circuits are dedicated to the switch and not to other electrical equipment.
For combined power mode (no power redundancy) or power supply (n+1) redundancy, you need only one dedicated
circuit. The requirements for each circuit are listed in the following table.
Table 2: Circuit Requirements for 3-kW Power Supplies
Power Supply
AC Power Supplies
3-kW power supply
DC Power Supplies
3-kW power supply
Step 5
Plan the placement of the input power receptacles within reach of the power cables used for each power supply (see the
following table for the maximum distances).
Typically, power receptacles are placed on the rack with the switch. If the DC power source is further than allowed by
the DC power cables, you can install a power interface unit (PIU) in the rack with the switch and connect that to the
power source with other cabling.
Power Supply
All AC power supplies
DC 3-kW power supplies

Rack and Cabinet Requirements

You can install the following types of racks or cabinets for your switch:
• Standard perforated cabinets
OL-31330-01
Number of
Circuits
(N77-AC-3.0KW)
1
(N77-DC-3.0KW)
1
Maximum Distance Between Receptacle and Power Supply
12 feet (3.5 m)
Determined by the length of the power cord that you supply.
Rack and Cabinet Requirements
Requirement for Each Circuit
20 A at 110 VAC or 220 VAC
20A
Cisco Nexus 7706 Hardware Installation Guide
9