12.6. OFF Timer Control

OFF timer can be set using remote control, the unit with timer set will stop operate at set time.

12.7. Auto Restart Control

1. When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within three to four
minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be selected randomly) after
power supply resumes.
2. This type of control is not applicable during ON/OFF Timer setting.

12.8. Indication Panel

LED
POWER
Color
Green
Light ON
Operation ON
Light OFF
Operation OFF
Note:
• If POWER LED is blinking, the possible operation of the unit are Hot Start, during Deice operation, operation mode judgment, or
ON timer sampling.
• If Timer LED is blinking, there is an abnormality operation occurs.
• If e-ion LED is blinking, there is an abnormality of e-ion occurs.
• If PATROL LED is blinking, there is a gas sensor error detection.

12.9. Patrol Operation

A. Purpose
To monitor air dirtiness level by using gas sensor and activates e-ion operation whenever air is dirty.
B. Control Condition
a. Patrol operation start condition
• When the unit operation is started with "OFF/ON" button.
• When the unit stops, "Patrol" button is pressed, Patrol individual operation will start.
• During cooling only operation, "Patrol" button is pressed.
TIMER
QUIET
Orange
Orange
Quiet Setting ON
Quiet Mode ON
Quiet Setting OFF
Quiet Mode OFF
POWERFUL
Orange
Powerful Mode ON
Powerful Mode OFF
36
e-ion
PATROL SENSOR
Blue
Blue
e-ion ON
PATROL ON
e-ion OFF
PATROL OFF