GE MIFII GEK-106237P Instruction Manual page 209

Digital feeder protection with recloser
Table of Contents

Advertisement

C.4 SYNCHRONIZATION
C.4SYNCHRONIZATION
To synchronize the date and time of a relay we use a command with the following characteristics:
1.
The command is executed in broadcast mode (relay address = 00H)
2.
Date and time are included in the message. The date and time format length is 6 bytes.
3.
No answer is expected from the relay.
C
Example:
To send the date and time of June 15
Intel Synchronization:
ADDRESS
00H
Motorola Synchronization:
ADDRESS
00H
C-6
FIELD
Relay address
Function
Beginning address
Number of registers
Number of bytes
Value of the registers
CRC
th
, 2005 at 00:015:09.000
FUNCTION
BEGINNING
10H
0000H
FUNCTION
BEGINNING
10H
0000H
LENGTH
1 byte (00H – broadcast)
1 byte (10H)
1 word (0000H) (High Byte – low byte)
1 word (0004H) (High Byte – low byte))
1 byte (08H) (High Byte – low byte))
Register 1=>Command code (Low byte –High
byte).
Register 2...4=>Date and time
1 word
#REGS
#BYTES
DATA0
0004H
08H
FE 00H
#REGS
#BYTES
DATA0
0004H
08H
FE 00H
MIFII Digital Feeder Relay
APPENDIX C
DATA1
DATA2
DATA3
C8CAH
7476H
4500H
DATA1
DATA2
DATA3
0045H
7674H
CAC8H
CRC
B950H
CRC
3919H
GEK-106237P

Advertisement

Table of Contents
loading

Table of Contents