5 SETTINGS
ENERVISTA MII SETUP
Thermal Image group 2
49 Function (group 2)
Permission to Trip
Trip Enable 49
49 Pickup
Pickup 49
Overload Percent Alarm
Alarm Level 49
Heating Time Constant τ1
Heat Time 49
Cooling Time Constant τ2
Cool Time 49
USER CURVE
ENERVISTA MII SETUP
Parameters
User Curve
A
A Parameter
B
B Parameter
P
P Parameter
Q
Q Parameter
K
K Parameter
GEK-106237P
5.3.3 THERMAL IMAGE SETTINGS (49) (GROUP 2)
HMI
THERMAL MODEL 49
Trip Enable 49
Pickup 49
Alarm Level 49
Heat Time 49
Cool Time 49
HMI
DEFAULT
User Curve
A Parameter
0.0500
B Parameter
0.0000
P Parameter
0.0400
Q Parameter
1.0000
K Parameter
0.000
MIFII Digital Feeder Relay
5.3 ADVANCED SETTINGS
DEFAULT
RANGE
No
Yes/No
1 In (Phase)
0.10 – 2.40 In (Ph)
80 %
70% – 100% ITH
6
3 – 600 min.
1– 6 times τ1
1
RANGE
0.0000-125.0000
0.0000-3.0000
0.0000-3.0000
0.0000-2.0000
0.000-1.999
STEP
NA
0.01 In (Ph)
1 min.
1
STEP
0.0001
0.0001
0.0001
0.0001
0.001
5
5-9