Hot Water Reset - T775R - Honeywell T775 Series Application Manual And Cross Reference

2000 electronic stand-alone controllers
Table of Contents

Advertisement

T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
Hot Water Reset – T775R
Application Description
The T775R is controlling the boiler water temperature with two
stages (relays), based on outside temperature using a reset
curve and an offset for relay 2.
Sensor Designation
This device application requires two sensors.
• Sensor A is sensing hot water discharge temperature of
the boiler.
• Sensor B is sensing outside air temperature
Operation
In this example, when the outside temperature reaches
70° F (21° C), the desired water temperature of the boiler is
160° F (71° C). Likewise, when the outside temperature drops
to 20° F (-7° C), the hot water temperature needs to be
210° F (99° C). See Fig. 10.
°F
220
SP MAX A1
210
(BOILER MAX)
S
200
E
N
190
S
O
180
R
A
170
160
SP MIN A2
(BOILER MIN)
150
140
10
RESET B1
(OUTSD MIN)
Fig. 10. Hot Water Reset Curve.
Programming Example
Program in Setup:
Press and hold the MENU button for 5 seconds to enter
Setup mode. Select the Outputs menu, and then select:
=
— MOD 1
Reset
— # Relays = 2
— Relay 1
Reset = YES-BOILER
— Relay 2
Reset = YES-BOILER
Relay 1: Control to the discharge water temperature
Program for: (Refer to the reset curve in Fig. 10.)
— Boiler Max = 210° F (99° C)
— Outside Min = 20° F (-7° C)
— Boiler Min = 160° F (71° C)
— Outside Max = 70° F (21° C)
— Differential = 20° F (-7° C)
— Sensor A
— Heat
Relay 2: Control to the discharge water temperature
Program for:
— Setpoint Offset = -10° F (-12° C) (See Fig. 11)
— Sensor A
— Heat
63-7147—3
RELAY 1
SETPOINT
RELAY 2
SETPOINT
OFFSET -10°F
20
70
30
40
50
60
80
°F
RESET B2
(OUTSD MAX)
SENSOR B
YES-BOILER
PROGRAM
RELAY 2
Fig. 11. Program Mode - Relay 2 Offset.
IMPORTANT
After the desired value is selected, be sure to press
the # or $ or HOME button in order to save that
value in the controller's memory.
IMPORTANT
By programming the boiler setpoint at 210° F (99° C)
the T775 has established 210° F (99° C) as the
highest operating point that will be allowed when the
outside temperature falls below 20° F (-7° C). As the
outside temperature increases above 20° F (-7° C),
the boiler will be reset downward per the reset ratio
until it reaches the minimum setpoint, 160° F.
Assuming an outside temperature of 20° F (-7° C), Fig. 12
describes the actions of relays 1 and 2 to control the boiler
temperature. As the boiler temperature falls below 210° F
(99° C), relay 1 activates (relay 1 Differential is 20° F (-7° C),
so relay closes at 190° F (88° C). If relay 1 cannot raise the
boiler temperature and the boiler temperature continues to fall
to 180° F °, relay 2 activates (relay 2 Differential is 20° F
(-7° C) 180° to 200° F (82° to 93° C) When the boiler is able to
M24871
reach 200° F (93° C), then relay 2 deactivates and relay 1
remains active until the temperature reaches 210° F (99° C).
DIFFERENTIAL
NOTE: The Hot Water Reset application continues on the
next page.
14
MENU
PROGRAM
RELAY 2
OFFSET
DIFFRNTL
HEAT/COOL
SETBACK
EXIT
BOILER DISCHARGE
TEMPERATURE
210°
RELAY 1
200°
RANGE
190°
RELAY 2
DIFFERENTIAL
RANGE
180°
Fig. 12. Relay Actions.
MENU
PROGRAM
RELAY 2
OFFSET
-10
o
F
ENTER
SETPOINT
OFFSET
FOR
RELAY 2
M24321
RELAY 1 OFF
RELAY 2 OFF
RELAY 1 ON
RELAY 2 ON
M24877