Testing Main Condenser - Maytag AFU1202BW Service

Upright freezers
Hide thumbs

Advertisement

Component Testing
!
WARNING
power to be connected. When removing any wiring from terminals they must be replaced on the same terminals.
Ensure all ground wires are connected before certifying unit as repaired and/or operational.

Testing Main Condenser

Before testing condenser, verify no leaks exist
elsewhere.
Condenser loop must be disconnected from the system
and tested separately. The following illustration shows
the tubing as it is routed and fastened in the freezer
cabinet flange.
NOTE: Verify a leak is not present in any external
tubing or joints before performing the following
test.
Following equipment is required to test.
• An access fitting.
• A drum of oil pumped nitrogen.
• Pressure regulator.
• Two gauges.
• Line valve and tubing.
Access fitting should be prepared as follows:
Gauges
Pressure
regulator
Line
valve
Nitrogen Tank and Fittings
To
Process
condensor
Tube
process
Compressor Cutting or Unsoldering
Points Refrigerated Shelf Models
©2004 Maytag Services
Suction
From
Discharge
condensor
16023585
To avoid risk electrical shock, personal injury, or death,
always disconnect electrical power source to the freezer
before attempting to service, unless test procedures require
To
To
evaporater
condensor
Tube
process
Compressor Cutting or Unsoldering
Points No Defrost Models
Prepare equipment as required and test condenser as
follows:
1. Cut tubing at arrow "to condenser" and "from
condenser" as shown in the previous illustration.
2. Crimp and solder the end "to condenser" that enters
into the cabinet.
3. Silver solder access fitting of test equipment to the
end "from condenser" tube that emerges from the
cabinet.
4. Pressurize the system to 250 pounds with dry
nitrogen. Test all connections for leaks with a soap
solution.
5. Check the pressure gauge. If pressure drops, there is
a leak. However, it may be necessary to allow as
much as 24 hours for test results to verify no leaks
exist. If there are no leaks, reconnect the tubing.
Evacuate and recharge the system.
Condensor
bottom
external
Suction
From
Discharge
condensor
15