5. INSPECTION AND MAINTENANCE
Contents (BIN)
Error
Register D9008
"END NOT
EXECUTE"
"WDT ERROR"
"UNIT VERIFY
ERR."
"FUSE BREAK OFF"
"CONTROL-BUS
ERR."
"SP. UNIT DOWN"
Table 5.9 Table of Error Codes (cont.)
CPU
of Special
Status
24
STOP
25
STOP
STOP
31
(RUN)
STOP
32
(RUN)
40
STOP
41
STOP
Error Description and Cause
(1) During execution, the END code
was read as a different instruction
code due to noise, or some other
cause.
(2) The END instruction changed to
another instruction code for some
reason.
A sequence program run by a CJ
instruction is stuck in a loop and the
END instruction cannot be executed.
Problem with I/O module at power on.
(1) During operation, the I/O module
(induding the special function
module) is loose or has come out
of its slot, or the wrong module is
mounted.
(1) A fuse is blown in an output
module.
(2) The external power supply for the
output load is turned off or not
connected.
FROM and TO instructions could not
be executed.
(1) Control bus error with a special-
function module.
When a FROM or TO instruction was
executed, no reply was received that
the special-function module was
accessed.
(1) The accessed special-function
module is defective.
5 − 22
Corrective Action
(1) Reset the CPU and run again.
If the same error is displayed
again, a problem exists in the
CPU hardware.
Contact your nearest Mitsubishi
representative with details.
Check if a program contains an
infinite loop and modify, as required.
(1) The bit corresponding the
module causing the verification
error is set to "1" in special
register D9116. Monitor the
contents of this special register
from the peripheral device.
Check the module where the
error occurred and replace, if
necessary.
(2) If the module position is correct,
reset with the RUN/STOP key
switch.
(1) Check the ERR indicator on
each output module and replace
the module with the indicator lit.
(2) The module with a blown fuse
can also be identified from a
peripheral device. The bit
corresponding the module with
the blown fuse is set to 1 in
special register D9100. Monitor
the contents of this special
register to identify the module.
(3) Ensure that the external power
supply for the output load is
turned on.
(1) A hardware error exists in a
special-function module, CPU
module, or the main base unit.
Replace the module or unit and
check the defective module or
unit for defects.
Contact your nearest Mitsubishi
representative with details.
A hardware error exists in the
accessed special-function module.
Contact your nearest Mitsubishi
representative with details.