2 8 | Bosch Geothermal Heat Pumps
As the installation location is to be Minneapolis,
Minnesota, a colder climate, the designer should examine
the heating ability of the unit more closely.
Examining the corresponding full load heating data (Table
12) for the Bosch four (4) ton geothermal heat pump
(compressor operating at 100% full load ability), we
nd that at 50°F EFT (the typical shallow groundwater
temperature for the location is 47°F per Bosch Geo
Solutions software) and 70°F entering air temperature
(return air temperature), we determine the total capacity
for heating is 45,810 Btu/h. Our calculated heat loss
at design conditions is 65,000 Btu/h at -11°F outdoor
temperature. We will be able to meet approximately 70%
of the structure heat loss with the Bosch four (4) ton
geothermal heat pump capacity at design conditions.
Examining the actual bin hours for Minneapolis, MN using
the Bosch four (4) ton geothermal heat pump (see Table
13), we nd that the heat pump providing compressor
heating will operate until the structure balance point of
approximately 10°F outdoor temperature without auxiliary
heating typically being required.
Bosch Geo Solutions Software Data
Bin
Bin
Bldg Load
(ÝF)
Hrs
(Btuh)
97
8
48000
92
50
39111
87
136
30222
82
285
21333
77
442
12444
72
613
3556
67
701
0
62
704
0
57
614
2407
52
552
6420
47
478
10432
42
487
14444
37
552
18457
32
653
22469
27
591
26481
22
475
30494
17
379
34506
12
313
38519
7
242
42531
2
190
46543
-3
131
50556
-8
81
54568
-13
45
58580
-18
16
62593
Tab. 13
Data subject to change
EWT
HPCap
Run
(ÝF)
(Btuh)
Time
57
48000
100%
56
43370
90%
55
43516
69%
54
43662
49%
53
43809
28%
52
43955
8%
52
0
51
0
50
33957
7%
49
33571
19%
47
33185
31%
46
32799
44%
45
32413
57%
44
32027
70%
43
31641
84%
42
31255
98%
40
34506
100%
39
38519
100%
38
40133
100%
37
39662
100%
36
39192
100%
35
38722
100%
33
38251
100%
32
37781
100%
Capacity Data - Full Load Heating
Entering
Entering
Fluid Temp.
Air Temp.
(ÝF)
(ÝF)
50
60
60
70
80
50
60
70
70
80
50
60
80
70
80
Tab. 12
(EFT Range (Standard) 25ÝF to 80ÝF)
Pwr
Auxillary
HP
(kW)
(kWh)
(kWh)
2.01
8
1.56
70
1.54
146
1.52
212
1.50
188
1.48
73
0
0
3.26
0.00
96
3.25
0.00
233
3.24
0.00
330
3.23
0.00
470
3.22
0.00
688
3.21
0.00
1000
3.20
0.00
1077
3.19
0.00
1007
3.18
0.00
1069
3.17
0.00
742
3.16
173.94
764
3.14
391.86
598
3.13
446.19
410
3.12
384.73
253
3.11
274.20
140
3.10
118.99
50
Applications Manual
Total
Power
Heat of
Capacity
Input
Abs.
(MBtuH)
(kW)
(MBtuH)
48.44
2.96
38.32
52.79
3.05
42.38
57.15
3.14
46.43
61.50
3.23
50.48
45.81
3.02
35.52
49.92
3.11
39.32
54.04
3.20
43.13
58.15
3.29
46.94
42.72
3.08
32.21
46.55
3.17
35.73
50.39
3.26
39.25
54.22
3.36
42.76
Geo HW
Aux HW
(Btuh/yr)
(Btuh/yr)
17,746
0
110,910
0
301,677
0
445,674
186,516
393,182
587,266
151,859
1,207,900
1,554,960
1,561,620
295,558
1,066,420
710,570
513,882
1,002,765
57,540
1,080,268
0
1,224,452
0
1,448,491
0
1,310,962
0
1,053,650
0
840,701
0
694,300
0
536,807
0
421,460
0
290,585
0
179,675
0
99,819
0
35,491
0
Bosch Thermotechnology Corp.
COP
4.8
5.1
5.3
5.6
4.5
4.7
5.0
5.2
4.1
4.3
4.5
4.7
Aux HW
(kWh
0.00
0.00
0.00
66.79
210.30
432.56
556.85
559.23
381.89
184.03
20.61
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents