Download Print this page

Honeywell 5800COA Installation And Setup Manual page 2

Carbon monoxide alarm with built-in wireless transmitter

Advertisement

BATTERY INSTALLATION AND REPLACEMENT
To replace the battery:
1. Remove the 5800COA from its mounting base by twisting the
unit counterclockwise. Remove the battery and dispose of
properly.
2. To ensure proper power-down sequence, wait a minimum of 20
seconds before installing new battery.
3. Install a new 3-volt CR123A Lithium battery in the battery
compartment. Follow the polarity diagram inside the
compartment.
4. Reinstall the unit onto the mounting base by turning it clockwise.
5. Test the 5800COA as described in the TESTING SIGNAL
STRENGTH section of this manual. The green LED should blink
about once every 10 seconds to indicate normal operation. If the
battery is not installed correctly, the unit will not operate and the
battery may be damaged. If the unit does not appear to be sending
a signal during any of the tests, check for correct battery
installation and for a fully charged battery.
TEST BUTTON
GREEN LED
RED LED
5800COA-001-V0
Figure 1. 5800COA Wireless Carbon Monoxide Alarm
PROGRAMMING
The 5800COA must be enrolled in the control panel before it can
operate in the system. Alarms and trouble conditions are reported to
the control on one protection zone, which is programmed as carbon
monoxide zone type (zone type 14 for Honeywell residential controls).
Events reported include the following:
Event
Alpha Keypad
CS Report
alarms
CO Alarm
CO alarm (CID 162)
test
CO Alarm
CO alarm (CID 162)
low battery
Lo Bat
RF low-battery (CID 384)
supervision
CO Trouble
RF sensor supervision
(CID 381)
end-of-life
CO Trouble
sensor trouble - end-of-life
trouble
(CID 380)
tamper
CO Trouble
RF sensor tamper
(CID 383)
1. Enter the control’s Zone Programming mode.
2. Enter the alarm zone number to be programmed.
3. Enter the applicable zone type when prompted. Use zone type 14
for Honeywell residential controls.
4. When prompted, enter Input Type 03 (3 on some controls) –
Supervised RF Transmitter.
5. When prompted for the serial number, do the following:
a. Remove the unit from its base (rotate the unit counter-
clockwise on the base until it snaps open) and remove the
battery tab (if not already removed).
NOTE: Unit must be removed from the base to enroll.
b. Press the Test button twice (for each press, hold the button
down several seconds).
c. Reinstall the unit on its base (twist clockwise until it snaps
into place).
d. Check that the 5800COA is enrolled as loop 1.
6.
Exit Programming mode when programming is complete, and
test the system. Refer to the Testing Section.
See the control unit’s installation instructions for more details.
– 2 –
MOUNTING THE 5800COA
First, determine the best location, one that provides proper carbon
monoxide detection (see Figure 4 for suggested detection locations)
and a strong wireless transmission path.
Proper Carbon Monoxide Detection Location
In a wall location, the 5800COA should be at least as high as a light
switch, and at least six inches from the ceiling. In a ceiling location,
it should be at least 30cm from any wall.
Where to install, ideally:
• Within 2 meters of all sleeping areas
• Inside the bedroom if it contains a fuel burning appliance
• On every floor of the building
• Ideally, install in any room that contains a fuel burning appliance
• If the appliance in the room is not normally used, such as the
boiler room, the 5800COA should be placed just outside the room
so the alarm can be heard more easily
Where NOT to install, ideally:
• 5800COA operates best if not installed within 2 meters of any
cooking appliance
• Directly above a sink, cooker, stove or oven
• Next to a door or window that would be affected by drafts i.e.
extractor fan or air vent
• Outdoors
• Do not install in any environment that does not comply with the
environmental specifications on the last page
• In or below a cupboard
• Where air flow would be obstructed by curtains or furniture
• Where dirt or dust could collect and block the sensor
• Where it could be knocked, damaged, or inadvertently removed
Good Transmission Path
A GOOD TRANSMISSION PATH MUST BE ESTABLISHED FROM
THE PROPOSED MOUNTING LOCATION BEFORE
PERMANENTLY INSTALLING THE 5800COA. To check, perform
the test described in the TESTING SIGNAL STRENGTH section.
Prior to mounting the unit to the mounting base, you must “enroll”
its serial number into the system (see the PROGRAMMING section).
Mounting Procedure
Once a suitable location is found, mount the 5800COA as follows:
1. Refer to the diagram below and install the mounting base on the
ceiling or on the wall (if local ordinances permit) using screw
locations “A” or “B” as required. Use the two screws and anchors
provided. Maneuver the base so the screws are at the elbow of the
screw slots and secure.
2. Fit the unit inside the base by aligning it over the base as shown
(unit’s alignment notch should be slightly offset from mounting
base tamper release tab), then turn the unit in a clockwise
direction until it clicks into place.
3. Test the 5800COA after completing the installation (as described
in the TESTING THE 5800COA section of this manual) and
refer to the control system’s instructions for additional
information concerning the use of wireless devices.
MOUNTING
SCREWS
(INSTALLED)
A
B
TAMPER
RELEASE TAB
B
(CUT OFF
SMALL TAB TO
A
ACTIVATE
TAMPER RESIST
FEATURE)
NOTE
USE SCREW LOCATIONS
OR
A
B
AS REQUIRED, THEN ROTATE BASE
AND SECURE SCREWS AT EACH
MOUNTING SLOT'S ELBOW.
ENGAGE NOTCH WITH
TAMPER RELEASE TAB
ON BASE AND TURN
CLOCKWISE TO LOCK
5800COA-006-V0
Figure 2. Mounting the 5800COA

Advertisement

loading