Section 3. Installation
CONNECTION OF FIREMAN'S SWITCH OR REMOTE CONTACT
If, while there is line voltage connected to the heater, you touch either line voltage terminal with any 24VAC wire that
is connected to the control board (including the Fireman's Switch jumper), you will immediately destroy the control
board and void the warranty.
REMOTE CONTROL CONNECTIONS
1. Switch off power to heater at main circuit breaker panel.
2. Unbolt and remove the access door panels.
3. Open control box cover (see
4a. To connect a 2-Wire Control (such as Pentair's IntelliTouch or EasyTouch) or a
timer:
- Remove the factory installed jumper from the Fireman's Switch terminals.
- Connect wires between the Fireman's Switch terminals on the heater and the
relay. Connect wires from the controller or timer to the Fireman's Switch.
Controller, timer or relay should be sized to handle 24VAC at 0.5 Amp (because
it will be completing the 24VAC control board circuit on the heater as shown in
Figure
22). DO NOT apply line voltage to the Fireman's Switch terminals. Use
18 gauge wire with a minimum 3/64" (1.2mm) thick insulation rated for a
temperature rise of at least 105°C.
- Knock-outs are provided to route the wires through
the bottom of the control box and past the junction
box.
4b. To connect a 3-Wire Control:
- Connect wires between the control board terminals
on the heater and the external relays, as shown in
Figure
23. Use at least 2 relays per heater, to allow
for an "OFF setting" on each heater mode. Select
relays that can handle logic level switching. DO NOT
apply line voltage to control board terminals.
- Move jumper (as shown on
external control and to disable the heater membrane
pad's "Pool ON" and "Spa ON" buttons (the "OFF"
key on the membrane pad remains functional).
- Knock-outs are provided to route the wires through
the bottom and the top of the control box and past
the junction box.
5. Close control box cover.
6. Re-install the access door panels.
To control heaters that are operated in parallel, connect wiring
at same locations on heater as 2-Wire or 3-Wire Control. It
is imperative that each control circuit is isolated from the
other control circuits, to avoid that current will flow from
one heater to another through the control circuits.
NOTICE: The fuse for the Fireman's Switch is a 1.25 Amp
1¼ x ¼" fast blow fuse, which is commonly available.
Rev. B 3-7-07
CAUTION
Figure
21).
Figure
23) to enable
Figure 22.
TRANS
OPERATING CONTROL
BK
O
MEMBRANE PAD
CONNECTION
ENABLE TOGGLE
DISABLE TOGGLE
TERMINAL BOARD
L1
F1
L1
GND
24VAC
2 9
Figure 21.
BK
O
Y
Y
Y Y
24 VAC
J6
W
W
TRAN S
F
S
I
R
W
W
I
E
L2
FL
M
T
A
C
H
N
R
S
BM
R
L2
Time Clock or Remote
(Purchase Separately –
Supplies Power to
Circulator Pump)
Fireman's Switch
Completes the heater
24 Volt AC Control
Board Circuit.
DO NOT connect this
circuit to Line Voltage!
P/N 472592