A zone may reside in any combination of partitions. A zone that resides in more than one partition
becomes a common zone and is reported to its lowest partition number. A common zone is armed
only when all the partitions that it belongs to are armed. It is immediately disarmed when one of the
partitions it belongs to is disarmed.
The control panel can have a maximum of two on-board hardwired inputs, and a total of 48 zones
(wired and wireless together).
There are 30 pre-defined zone types. All zone types can be edited by changing their characteristics.
Table 11. Default zone types
Zone Type
Day Zone
24 Hour Audible
Entry/Exit 1
Follower
Interior Follower
with Auto-Bypass
Instant
24 Hour Silent
Fire
Entry/Exit 2
24 Hour Audible
Supervised
Keyswitch
Momentary
Interior Follower
with Cross Zone
Instant Entry Guard
Entry/Exit 1 with
Group Bypass
Interior Follower
with Group Bypass
Instant with Group
Bypass
Keyswitch
Maintained
Description of default configuration
Instant when system is armed; trouble zone when system is disarmed. It is permanently active
24 hours a day unless bypassed by forced arming.
Creates an instant yelping siren alarm regardless of the arming state of the control panel. This
zone type is not abortable, but it can be bypassed.
A trip will start entry delay 1. Absence of a trip during the exit delay will enable the Automatic
Bypass or Instant mode, if so programmed.
This zone will be instant when the system is armed and no entry or exit delays are being timed. It
is delayed during entry and exit delay times. This zone will not bypass automatically, even if the
Group Bypass command is active.
This zone will be instant when the system is armed and no entry or exit delay is being timed. It is
delayed during entry and exit delay times. This zone will bypass automatically, if enabled by the
Group Bypass command.
This zone creates an instant alarm whenever it is tripped and the system is armed.
Creates an instant silent alarm regardless of the arming state of the control panel. It will not
display on the keypad. This zone is not abortable, but it can be bypassed.
Indicates a fire zone. This zone cannot be bypassed. The system will rapidly flash the Fire symbol
on the keypad and sound the steady siren each time the zone is shorted. To acknowledge the fire
alarm a user must enter the user code. After the alarm has been cancelled the Fire symbol still
displays on the keypad until a user selects the Detector Reset menu option from the Quick User
(or User) menu.
A trip will start entry delay 2. Absence of a trip during the exit delay will enable the automatic
bypass or instant mode, if so programmed.
Creates an instant audible alarm, regardless of the arming state of the control panel. It will
display on the keypad. This zone is not abortable and cannot be bypassed.
This zone type will arm and disarm the partition or partitions of the control panel where it is
resident, every time the zone is shorted. Keyswitch arming will report as User 99 in logs and
reports. This zone type can only belong to one partition.
This zone will be instant when the system is armed and no entry or exit delay is being timed. It is
delayed during entry and exit delay times. If a "Cross Zone" is not being timed, it will start a "Cross
Zone" timer. If a "Cross Zone" is being timed, it will create an instant alarm. This zone will bypass
automatically, if enabled by the Group Bypass command.
This zone creates an instant alarm whenever it is tripped and the zone is timed. It will start an
entry delay time 2 if it is tripped, provided that the system is armed and the stay/instant mode is
on.
A trip will start entry delay 1. This zone will bypass when the "Group Bypass" command is entered
at the keypad. Absence of a trip during exit delay will enable the automatic bypass or instant
mode, if so programmed.
This zone will be instant when the system is armed and no entry or exit delays are being timed. It
is delayed during entry/exit delay times. This zone will bypass when the "Group Bypass"
command is entered at the keypad. This zone will bypass automatically, if enabled by the Group
Bypass command.
This zone creates an instant alarm whenever it is tripped and the system is armed. This zone will
bypass when the "Group Bypass" command is entered at the keypad
This zone type will arm the partition or partitions of the control panel where it is resident, as long
as the zone is shorted. This zone type will disarm the partition or partitions of the control where it
NX-10 Installers manual
49