Bosch C 1210 ES Installation Manual page 30

Bosch indoor residential and commercial models tankless water heaters temperature modulated with electronic ignition suitable for heating potable water and space heating, natural & liquefied petroleum (lp) gas
Table of Contents

Advertisement

Installation instructions
Connecting the pressure relief valve (PRV)
The listed pressure relief valve must be installed at the
time of installation. No valve is to be placed between
the PRV and the heater. No reducing coupling or
other restriction may be installed in the discharge line.
The discharge line must be a minimum of 4" above a
drain and installed such that it allows complete drainage
of both the PRV and the line. The discharge line must be
placed where it will not cause any damage.
The location of the PRV must be readily accessible for
servicing or replacement, and be mounted as close to
the water heater as possible. See Fig. 34. To install the
PRV, a suitable fitting connected to an extension on a
"T" fitting can be sweated to the hot water line.
Support all piping.
Pressure
relief
valve
Fig. 34 Plumbing Connections (with isolation valves)
and Pressure Relief Valve
Warning:
In
applications
temperature can exceed 140°F (60ºC), a
thermostatic or mixing valve must be
installed before the appliance to prevent
water exceeding 140°F (60°C) from
entering the appliance.
30
where
inlet
water
6 720 644 887