External Device Settings
Use the MODE key, SET key, up key, and down key in the operation panel of the CPU unit for External Device
communication settings.
Refer to your External Device manual for details.
1
Press MODE key to select the parameter setting mode.
2
Press SET key.
3
Press up key or down key to display the most significant digit of the parameter number.
4
Press SET key.
5
Press up key or down key to display the middle digit of the parameter number.
6
Press SET key.
7
Press up key or down key to display the least significant digit of the parameter number.
8
Press SET key to display the current setting value.
9
Press up key or down key to set the setting value.
10
Press SET key for 1.5 seconds to write the setting value.
Setting Parameter Number
331
332
333
334
335
336
337
341
• Always restart the Eternal Device after changing parameters.
GP-Pro EX Device/PLC Connection Manual
Setting Value
0
Inverter station number
192
Communication speed
1
Stop bit length
2
Parity check yes/no
1
Communication retry count
Any Except 0
Communication check time interval
9999
Waiting time setting
1
CR/LF yes/no selection
37
FREQROL Inverter Driver
Setup Description