External Device Settings
Use the PU/EXT key, MODE key, M dial and SET key in the operation panel of the CPU unit for External Device
communication settings.
Refer to your External Device manual for details.
1
Turn ON the power supply.
2
Press PU/EXT key to select the PU operation mode.
3
Press MODE key to select the parameter setting mode.
4
Display the setting parameter number with M dial.
5
Press SET key to display the current setting value.
6
Set the setting value with M dial.
7
Press SET key to confirm the setting value.
Setting Parameter Number
117
118
119
120
121
122
123
124
549
• Always restart the Eternal Device after changing parameters.
GP-Pro EX Device/PLC Connection Manual
Setting Value
0
PU communication station number
192
PU communication speed
1
PU communication stop bit length
2
PU communication parity check
1
Number of PU communication retries
Any Except 0
PU communication check time interval
9999
PU communication waiting time setting
1
PU communication CR/LF selection
0
Protocol selection
23
FREQROL Inverter Driver
Setup Description