Troubleshooting (continued)
DR90/120 Technician Function Test
CONNECT A SHORT
WIRE BETWEEN "DEHU"
AND "R" AT WIRING
TERMINAL BLOCK
DO BOTH FAN AND
COMPRESSOR
COME ON?
YES
DOES THE FAN
SOUND NORMAL?
YES
REMOVE THE FILTER
AND FEEL THE
EVAPORATOR COIL
IS THE EVAPORATOR
COLD? (LIKE HOLDING
A COLD DRINK)
YES
TrueDry DR90/DR120 Dehumidification System 69-2690EFS—04
PLUG DEHUMIDIFIER
INTO OUTLET THAT
HAS POWER
JUMP THE FLOAT
NO
TERMINALS TOGETHER
ONLY FAN COMES ON
ONLY COMPRESSOR COMES ON
NO
INLET AIR
INLET AIR
TEMPERATURE
HUMIDITY
80 F (26.7 C)
60% RH
70 F (21.1 C)
60% RH
60 F (15.6 C)
60% RH
CONDUCT A PERFORMANCE TEST:
LEAVE THE DEHUMIDISTAT ON
DR90/120 IN THE "ALWAYS ON"
POSITION AND COLLECT DRAIN
NO
WATER FOR 24 HOURS. COMPARE
AMOUNT OF WATER COLLECTED
TO EXPECTED RANGE ABOVE.
DOES THE OUTLET
NO
HAVE POWER?
VERIFY POWER
AT OUTLET
NO
DO BOTH FAN AND
COMPRESSOR
COME ON?
DR90: GALLONS
DR120:GALLONS
COLLECTED IN
COLLECTED IN
24 HOURS
24 HOURS
10 TO 12.5
13.5 TO 16.5
8.5 TO 10.5
10.25 TO 12.5
5 TO 6.5
7.25 TO 9
IS THE AMOUNT OF
WATER COLLECTED
IN THE RANGE
EXPECTED?
YES
SEE DR90/120
SERVICE DIAGNOSTIC
YES
TREE
CLEAN DRAIN
LINES AND CHECK
FLOAT SWITCH
YES
CHECK THE FOLLOWING:
FAILED COMPRESSOR
OVERLOAD, FAILED
COMPRESSOR, WIRING,
DEFROST PROBE, LOW
PRESSURE SWITCH
CHECK THE FOLLOWING:
SWITCH, FAN, CAPACITOR,
RELAY, WIRING
CHECK THE FOLLOWING:
MECHANICAL ISSUE
WITH IMPELLER, MOUNT
OR SHROUD
SEE DR90/120
SERVICE DIAGNOSTIC
TREE
NO
NORMAL OPERATION.
TURN DEHUMIDISTAT
BACK TO SETTING OR
"OFF" POSITION.
M33756
15