Toshiba TOSVERT VF-AS1 Instruction Manual

Toshiba TOSVERT VF-AS1 Instruction Manual

High-performance inverter
Hide thumbs Also See for TOSVERT VF-AS1:
Table of Contents

Advertisement

Instruction Manual

The new
high-performance inverter
TOSVERT
200V class
400V class 0.75 500kW
1.Make sure that this instruction manual is delivered to the end user of
the inverter unit.
2.Read this manual before installing or operating the inverter unit, and
store it in a safe place for reference.
©Toshiba Schneider Inverter Corporation 2006
All rights reserved.
AS1
VF-
TM
0.4 75kW
NOTICE
E6581445
I
Safety
precautions
II II
Introduction
Contents
1
Read first
2
Connection
equipment
3
Operations
4
Searching and
setting parameters
5
Basic
parameters
6
Extended
parameters
7
Operation with
external signal
8
Monitoring the
operation status
9
Taking measures
to satisfy the
CE/UL/CSA standards
10 10
Selection of
peripheral
devices
11 11
Table of
parameters
12 12
Specifications
13 13
Before making a
service call
14 14
Inspection and
maintenance
15 15
Warranty
16 16
Disposal of
the inverter

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba TOSVERT VF-AS1

  • Page 1: Instruction Manual

    2.Read this manual before installing or operating the inverter unit, and 15 15 store it in a safe place for reference. Warranty 16 16 Disposal of the inverter ©Toshiba Schneider Inverter Corporation 2006 All rights reserved.
  • Page 2 Precautions of using 4-20mA input signal VFAS1/PS1 have adopted the semiconductor switch as the change function of 4-20mA current input and the voltage input of 0-10V. When the power supply is turned off, 4-20mA input circuit will be in open state, then it will be in high impedance condition.
  • Page 3: Motor Thermal Protection

    This additional sheet is additional descriptions of Section 9.2 “Measures to be taken to satisfy the UL/CSA standards”. The VF-AS1 models, that conform to the UL Standard and CSA Standard have the UL/CSA mark on the nameplate. 1.Compliance with Installation The VF-AS1 inverter must be installed in a panel, and used within the ambient temperature specification.
  • Page 4 この追加取説は、9.2 章“UL 規格/CSA 規格への対応について”の補足事項を記載していま す。 VF-AS1ではUL/CSA規格を取得しており、取得したインバータについては、定格銘板にUL/CSAマークが貼付 けてあります。 1 据付けについての注意 本インバータは盤内に収納することを前提にUL規格を取得しています。 このため、 盤内に収納し、 インバータの周囲温度 (収 納盤内部の温度)を仕様温度範囲内となるようにしてください。 詳細は、本体添付の取扱説明書 1.4.4 節をご参照ください。 2 配線についての注意 インバータの入力端子(R/L1,S/L2,T/L3)および出力端子(U/T1,V/T2,W/T3)に接続する配線 にはUL認定(導体最高許容温度75℃以上の銅電線)の電線に丸形圧着端子を取付けて使用してください。推奨電線サイズ については、本体取説9.2節の表をご参照ください。 National Electrical Code 及び現地の規格に従って実施して アメリカ合衆国内に設置する場合は分岐線の保護は、 ください。 Canadian Electrical Code 及び現地の規格に従って実施してくだ カナダ国内に設置する場合は分岐線の保護は、 さい。 3 周辺機器についての注意 インバータの入力側にヒューズを設置してください。ヒューズはUL認定品を使用してください。 また、本インバータは電源しゃ断電流(電源短絡が発生した場合に流れる電流)条件にてUL試験を実施しています。機種に より電源しゃ断電流、ヒューズ電流値が異なります。ヒューズ電流値については、本体取説9.2節の表をご参照ください。 入力電圧クラス...
  • Page 5: Safety Precautions

    E6581445 I. Safety precautions The items described in these instructions and on the inverter itself are very important so that you can use the inverter safely prevent injury to yourself and other people around you as well as prevent damage to property in the area. Thoroughly familiarize yourself with the symbols and indications shown below and then continue to read the manual.
  • Page 6: General Operation

    E6581445 General Operation Danger Reference • Never disassemble, modify or repair. This can result in electric shock, fire and injury. For repairs, call your sales agency. Disassembly prohibited • Never remove the front cover when power is on or open door if enclosed in a cabinet. The unit contains many high voltage parts and contact with them will result in electric shock.
  • Page 7 1.4.4 Operation cannot be stopped immediately by the inverter alone, thus risking an accident or injury. • All options used must be those specified by Toshiba. The use of any other option may result in an accident. 1.4.4 Caution Reference •...
  • Page 8 E6581445 Wiring Danger Reference • Do not connect input power to the output (motor side) terminals (U/T1,V/T2,W/T3). That will destroy the inverter and may result in fire. • Do not connect resistors to the DC terminals (between PA/+ and PC/-, or between PO and PC/-).
  • Page 9 E6581445 Operations Danger Reference • Do not touch inverter terminals when electrical power is applied to the inverter even if the motor is stopped. Touching the inverter terminals while power is connected to it may result in electric shock. • Do not touch switches when thands are wet and do not try to clean the inverter with a damp cloth.
  • Page 10: Maintenance And Inspection

    E6581445 Maintenance and inspection Danger Reference • Never replace any part by yourself. 14.2 This could be a cause of electric shock, fire and bodily injury. To replace parts, call the local sales agency. Prohibited • The equipment must be inspected every day. If the equipment is not inspected and maintained, errors and malfunctions may not be discovered which could lead to accidents.
  • Page 11 E6581445 II. Introduction Thank you for your purchase of the Toshiba “TOSVERT VF-AS1” industrial inverter. This instruction manual is intended for inverters with CPU version 130 or later. The CPU version will be frequently upgraded.
  • Page 12: Table Of Contents

    2.3.2 Control circuit terminal block B-11 2.3.3 Serial RS485 communication connector B-16 Operations Setting/monitor modes Simplified operation of the VF-AS1 3.2.1 Terminal board operation 3.2.2 Panel operation Searching and setting parameters How to set parameters 4.1.1 Setting parameters in the selected quick mode 4.1.2...
  • Page 13 E6581445 5.17 PWM carrier frequency E-31 5.18 Trip-less intensification E-32 5.18.1 Auto-restart (Restart during coasting) E-32 5.18.2 Regenerative power ride-through control/Deceleration stop during power failure/ Synchronized acceleration/deceleration E-34 5.19 Dynamic (regenerative) braking - For abrupt motor stop E-36 5.20 Standard default setting E-42 5.21 Searching for all reset parameters and changing their settings...
  • Page 14 E6581445 6.24 Torque control F-43 6.24.1 Torque command F-43 6.24.2 Speed limits in torque control mode F-43 6.24.3 Torque bias and load sharing gain F-43 6.25 Torque limit F-45 6.25.1 Torque limit switching F-45 6.25.2 Torque limit mode selection at acceleration/deceleration F-47 6.26 Stall prevention function...
  • Page 15 E6581445 6.38 Integrating wattmeter F-79 6.39 Communication function F-80 6.39.1 2-wire RS485/4-wire RS485 F-80 6.39.2 Open network option F-86 6.40 My function F-86 6.41 Traverse function F-87 6.42 Instruction manuals for optionally available devices and special functions F-87 Operation with external signal External operation Applied operation with input and output signals (operation by terminal board) 7.2.1...
  • Page 16 E6581445 Before making a service call- Trip information and remedies 13.1 Trip causes/warnings and remedies 13.2 Method of resetting causes of trip 13.3 If the motor does not run while no trip message is displayed. 13.4 How to check other troubles Inspection and maintenance 14.1 Regular inspection...
  • Page 17: Read First

    Additional functions II specification code L: Built-in EMC filter TOSVERT 2: 200V~240V 004: 0.4kW 450: 45kW P: Provided Y: Others : Special VF-AS1 series 007: 0.75kW 550: 55kW (non-standard) 4: 380V~480V basic filter 015: 1.5kW 750: 75kW specification code VFZ1: M: Built-in basic filter 022: 2.2kW...
  • Page 18: Structure Of The Main Body

    E6581445 1. 3 Structure of the main body 1.3.1 Names and functions 1) Outside view Control circuit Operation panel terminal cover Be sure to close the cover before starting the operation to prevent persons from touching the terminal in error. Main circuit terminal cover Inverter type and...
  • Page 19 E6581445 Operation panel Up key RUN lamp EASY key [Note 1] EASY key lamp % lamp Lights when an ON Lights when the unit Press this key to control Lights when the EASY command is issued but no is %. the function assigned key is enabled.
  • Page 20 E6581445 2) Main circuit terminal VFAS1-2004PL~2015PL VFAS1-4007PL~4022PL Shorting-bar M4 screw Grounding capacitor switching switch Grounding terminal (M5 screw) Screw hole for EMC plate VFAS1-2022PL, 2037PL VFAS1-4037 PL Shorting-bar M4 screw Grounding capacitor switching switch Grounding terminal (M5 screw) Screw hole for EMC plate VFAS1-2055PL VFAS1-4055PL, 4075PL Shorting-bar...
  • Page 21 E6581445 VFAS1-2075PL VFAS1-4110PL Shorting-bar M5 screw Grounding capacitor switching switch Grounding terminal (M5 screw) Screw hole for EMC plate VFAS1-2110PM, 2150PM VFAS1-4150PL, 4185PL Grounding capacitor switching switch Shorting-bar M6 screw Grounding terminal (M5 screw) Screw hole for EMC plate VFAS1-2185PM, 2220PM VFAS1-4220PL M8 screw Shorting-bar...
  • Page 22 E6581445 VFAS1-4300PL, 4370PL Grounding capacitor switching switch M8 screw Shorting-bar Each main circuit terminal has the structure shown in the figure below. Connect a cable to part A. Do not use part B, because it is to connect a bare wire of a different size. Grounding terminal (M8 screw) Hole...
  • Page 23 E6581445 VFAS1-2750P VFAS1-4110KPC M12 screw M10 screw Grounding capacitor switching bar M4 screw M8 screw Grounding terminal(M10 screw) VFAS1-4132KPC Grounding capacitor M12 screw switching screw M10 screw M10 screw M4 screw Grounding terminal(M10 screw) VFAS1-4160KPC Grounding capacitor switching screw M12 screw M12 screw M10 screw M4 screw...
  • Page 24 E6581445 VFAS1-4200KPC~4280KPC M12 screw Grounding capacitor switching screw M12 screw Grounding terminal M4 screw (M12 screw) VFAS1-4355KPC, 4400KPC Grounding M12 screw capacitor switching screw M12 screw M4 screw Grounding terminal (M12 screw) VFAS1-4500KPC Grounding capacitor M12 screw switching screw M4 screw M12 screw Grounding terminal (M12 screw)
  • Page 25: Detaching The Cover

    E6581445 3) Control circuit terminal block The control circuit terminal block is common to all equipment. Serial 4-wire RS485 ST-CC Shorting bar connector Control circuit terminal block screw size: M3 ⇒ For details on all terminal functions, refer to Section 2.3.2. 1.3.2 Detaching the cover Main circuit terminal cover To wire the main circuit terminal for models 200V-15kW or smaller and 400V-18.5kW or smaller, remove the main...
  • Page 26 E6581445 For 200V/0.4kW to 200V/15kW models and 400V/0.75kW to 400V/18.5kW models, cut off the tabs (part A in the figure below) on the main circuit terminal cover if necessary for connecting the cables from the power supply. 200V-0.4kW~3.7kW 200V-5.5kW~15kW 400V-0.75kW~3.7kW 400V-5.5kW~18.5kW Front cover To wire the main circuit terminal for models 200V-18.5kW or more and 400V-22kW or more, remove the front cover.
  • Page 27 E6581445 Charge lamp This lamp is lit when a high voltage remains in the inverter. When removing the main circuit terminal cover or opening the front cover, be sure to check that this lamp is off and follow the instructions about wiring on page 4. The mounting position of the charge lamp varies from model to model.
  • Page 28: Grounding Capacitor Switching Method

    E6581445 1.3.3 Grounding capacitor switching method The inverter is grounded through a capacitor. The leakage current from the inverter can be reduced using the selector switch, switching bar or switching screw (depending on the model) on the main circuit terminal board. This switching device is used to detach the capacitor from the grounding circuit or to reduce its capacitance.
  • Page 29 E6581445 200V/55kW models and larger 400V/90kW, 110kW models: Grounding capacitor switching bar Large To change the capacitance from Small to Large, secure the upper end of the grounding capacitor switching bar to the inverter Small chassis, with a screw. To change the capacitance from Large Large to Small, remove the screw that fixes the upper end of the...
  • Page 30 E6581445 «200kW~280kW» To change the capacitance from Large Small Small to Large, fix to part A shown in the figure on the left with the grounding capacitor switching screw. To change the capacitance from Large to Small, fix to part B shown Large Small in the figure on the left with the grounding capacitor switching...
  • Page 31: Installing The Dc Reactor

    E6581445 1.3.4 Installing the DC reactor When purchasing and installing a DC reactor (DCL1, packaged with the inverter for 400V-355kW to 500kW models), refer to the table below. Applicable DC reactor types Inverter DC reactor type VFAS1-2550P DCL1-2550 VFAS1-2750P DCL1-2750 VFAS1-4900PC DCL1-4900 VFAS1-4110KPC...
  • Page 32: Notes On The Application

    Comparisons with commercial power operation The VF-AS1 Inverter employs the sinusoidal PWM system to supply the motor. This is why compared to operation with a commercial power there will be a slight increase in motor temperature, noise and vibration. The main supply voltage and current will also be distorted due to harmonic distortion while increase the line current.
  • Page 33 E6581445 High-speed operation at and above 60Hz (rated frequency) Operating at frequencies greater than 60Hz will increase noise and vibration. There is also a possibility that such operation will exceed the motor's mechanical strength under these conditions and the bearing limits. You should verify with the motor's manufacturer operating.
  • Page 34: Inverters

    E6581445 In circuit configuration 1, the brake is turned on and off through MC2 and MC3. If the circuit is configured in some other way, the overcurrent trip may be activated because of the locked rotor current when the brake goes into operation.
  • Page 35: What To Do About The Leak Current

    E6581445 There is no fuse in the inverter's main circuit. Thus, as the diagram above shows, when more than one inverter is used on the same power line, you must select interrupting characteristics so that only the MCCB2 will trip and the MCCB1 will not trip when a short occurs in the inverter (INV1).
  • Page 36 E6581445 (2) Affects of leakage current across supply lines Thermal relay inverter Power supply Leakage current path across wires (1) Thermal relays The high frequency component of current leaking into electrostatic capacity between inverter output wires will increase the effective current values and make externally connected thermal relays operate improperly. If the motor cables are more than 50m long, external thermal relay may operate improperly with models having motors of low rated current, especially the 400V class low capacity (3.7kW or less) models, because the leakage current will be high in proportion to the motor rating.
  • Page 37: Installation

    E6581445 1.4.4 Installation Installation environment The VF-AS1 Inverter is an electronic control instrument. Take full consideration to installing it in the proper operating environment. Danger • Do not place any inflammable substances near the VF-AS1 Inverter. If an accident occurs in which flames are emitted, this could lead to fire.
  • Page 38 Please consult with your supplier about these measures. • If the VF-AS1 Inverter is installed near any of the equipment listed below, provide measures to insure against errors in operation. Solenoids: Attach surge suppressor on coil. Brakes: Attach surge suppressor on coil.
  • Page 39 E6581445 Install the inverter in a well-ventilated indoor place and mount it on a flat metal plate in portrait orientation. If you are installing more than one inverter, the separation between inverters should be at least 5cm, and they should be arranged in horizontal rows.
  • Page 40 E6581445 200V 18.5~45kW (See lines shown in - - - for 22kW) 400V 22~75kW Ambient temperature 40°C *1 100% 50°C 60°C 2.5kHz 4kHz 8kHz 12kHz 16kHz Carrier frequency () 200V 55kW or more Ambient temperature 40°C *1 100% 50°C 60°C 2.5kHz 3kHz 4kHz 5kHz 6kHz...
  • Page 41 E6581445 Calorific values of the inverter and the required ventilation The energy loss when the inverter converts power from AC to DC and then back to AC is about 5%. In order to suppress the rise in temperature inside the cabinet when this loss becomes heat loss, the interior of the cabinet must be ventilated and cooled.
  • Page 42 E6581445 Panel designing taking into consideration the effects of noise The inverter generates high frequency noise. When designing the control panel setup, consideration must be given to that noise. Examples of measures are given below. • Wire so that the main circuit wires and the control circuit wires are separated. Do not place them in the same conduit, do not run them parallel, and do not bundle them.
  • Page 43: Connection Equipment

    E6581445 2. Connection equipment Danger • Never disassemble, modify or repair. This can result in electric shock, fire and injury. For repairs, call your sales agency. Disassembly prohibited • Don't stick your fingers into openings such as cable wiring hole and cooling fan covers. This can result in electric shock or other injury.
  • Page 44 Control and main power supply The control power supply and the main circuit power supply for the VF-AS1 are the same. If a malfunction or trip causes the main circuit to be shut off, control power will also be shut off.
  • Page 45: Standard Connections

    E6581445 Standard connections Danger • Do not connect input power to the output (motor side) terminals (U/T1, V/T2, W/T3). Connecting input power to the output could destroy the inverter or cause a fire. • Do not connect a regenerative braking resistor to any DC terminal (between PA/+ and PC/-, or between PO and PC/-).
  • Page 46 E6581445 [Standard connection diagram – sink logic] The figure below shows an example of typical wiring in the main circuit 200V 0.4-45kW/400V 0.75-75kW inverter. *1: The inverter is shipped with the terminals PO and PA/+ shorted with a bar (200V-45kW or smaller, 400V-75kW or smaller). Remove this shorting bar when installing a DC reactor (DCL).
  • Page 47 E6581445 [Standard connection diagram - sink logic] The figure below shows an example of typical wiring in the main circuit 200V 55, 75kW/400V 90-280kW inverter. *1: Be sure to connect the DC reactor. *2: To supply a DC power, connect the cables to the PA/+ and PC/- terminals. *3: If you want to use a DC power supply to operate the inverter, be sure to contact your supplier customer support center, because an inrush current limiting circuit is required in such a case.
  • Page 48 E6581445 [Standard connection diagram - sink logic] The figure below shows an example of typical wiring in the main circuit 400V 355-500kW inverter. *1: Be sure to connect the DC reactor. *2: To supply a DC power, connect the cables to the PA/+ and PC/- terminals. *3: If you want to use a DC power supply to operate the inverter, be sure to contact your supplier customer support center, because an inrush current limiting circuit is required in such a case.
  • Page 49 E6581445 [Standard connection diagram - source logic] The figure below shows an example of typical wiring in the main circuit 200V 0.4-45kW/400V 0.75-75kW inverter. *1: The inverter is shipped with the terminals PO and PA/+ shorted with a bar (200V-45kW or smaller, 400V-75kW or smaller). Remove this shorting bar when installing a DC reactor (DCL).
  • Page 50 E6581445 [Standard connection diagram - source logic] The figure below shows an example of typical wiring in the main circuit 200V 55, 75kW/400V 90-280kW inverter. *1: Be sure to connect the DC reactor. *2: To supply a DC power, connect the cables to the PA/+ and PC/- terminals. *3: If you want to use a DC power supply to operate the inverter, be sure to contact your supplier customer support center, because an inrush current limiting circuit is required in such a case.
  • Page 51 E6581445 [Standard connection diagram - source logic] The figure below shows an example of typical wiring in the main circuit 400V 355-500kW inverter. *1: Be sure to connect the DC reactor. *2: To supply a DC power, connect the cables to the PA/+ and PC/- terminals. *3: If you want to use a DC power supply to operate the inverter, be sure to contact your supplier customer support center, because an inrush current limiting circuit is required in such a case.
  • Page 52: Description Of Terminals

    Description of terminals 2.3.1 Main circuit terminals This diagram shows an example of wiring of the main circuit. Use options if necessary. Power supply and motor connections VF-AS1 Connect the power Connect the motor Power supply cables to RL1, S/L2, cables to U/T1, V/T2 and T/L3.
  • Page 53: Control Circuit Terminal Block

    E6581445 2.3.2 Control circuit terminal block The control circuit terminal block is common to all equipment. Shorting bar between ST-CC ⇒ How to set input terminal function, refer to section 7. Terminal Input/ Electrical Function Inverter internal circuits symbol output specifications Shorting across F-CC causes forward Voltage free contact...
  • Page 54 E6581445 Terminal Input/ Electrical Function Inverter internal circuits symbol output specifications Constant 10Vdc voltage circuit Output Analog input setting power output (Permissible load current:10mAdc) SW3: Multifunction programmable analog input 2.2k 12.7k terminal when SW3 is in the RR position. 10Vdc RR/S4 Input Standard default setting:0~10Vdc input and...
  • Page 55 E6581445 Terminal Input/ Electrical Function Inverter internal circuits symbol output specifications Relay contact output. Contact rating 250Vac-2A Used to detect the activation of the inverter's 30Vdc-1A Output protective function. Contact across FLA-FLC is :at resistance load closed and FLB-FLC is opened during 250Vac-1A protection function operation.
  • Page 56 E6581445 Sink logic/source logic (When inverter's internal power supply is used) Current flowing out turns control input terminals on. These are called sink logic terminals. The method generally used in Europe is source logic in which current flowing into the input terminal turns it on. Sink logic terminals and source logic terminals are sometimes referred to as negative logic terminals and positive logic terminals, respectively.
  • Page 57 E6581445 Sink logic/source logic (When an external power supply is used) The P24/PLC terminal is used to connect to an external power supply or to insulate a terminal from other input or output terminals. Use the slide switch SW1 to switch between sink logic and source logic configurations. <Examples of connections when an external power supply is used>...
  • Page 58: Serial Rs485 Communication Connector

    When connecting a communications device via the two-wire connector, carefully read the precautions for use in the operating manual for the communications device. * When connecting the VF-AS1 to other inverters, you do not need to connect the master receive lines (pins 4 and 5) or the slave send lines (pins 3 and 6).
  • Page 59: Operations

    E6581445 3. Operations This section explains the basics of operation of the inverter. Check the following again before starting operation. 1) Are all wires and cables connected correctly? 2) Does the supply voltage agree with the rated input voltage? Danger •...
  • Page 60: Monitoring The

    E6581445 Setting/monitor modes The VF-AS1 has the following three setting/monitor modes. Standard monitor mode The standard inverter mode. This mode is enabled when inverter power goes on. This mode is for monitoring the output frequency and setting the frequency reference value. If also displays information about status alarms during running and trips.
  • Page 61: Simplified Operation Of The Vf-As1

    E6581445 Simplified operation of the VF-AS1 On of three operation modes can be selected: terminal board operation, operation panel and combination of both. ⇒ For other operation modes, refer to Section 5.5. Terminal board mode :Operation by means of external signals...
  • Page 62 E6581445 Frequency setting 1) Setting the frequency using potentiometer Potentiometer The operation frequency by potentiometer (1~10kΩ- 1/4W ) for setting ⇒ Refer to Section 7.3 for details of adjustment. :Frequency settings RR/S4 60Hz With potentiometer Frequency [Parameter setting] Set the “basic parameter frequency setting mode selection 1” parameter  to  . (There is no need to set this parameter before the first use after purchase.) 2) Setting the frequency using input voltage (0~10V) Voltage signal...
  • Page 63 E6581445 4) Setting the frequency using input voltage (0~10Vdc) Voltage signal Voltage signal (0~10V) for setting the operation frequency ⇒ Refer to Section 7.3 for details of adjustment. VI/II :Voltage signal 0-10Vdc 60Hz Frequency 10Vdc 0Vdc [Parameter setting] Set the “extended parameter analog input VI/II voltage/current switching” parameter ...
  • Page 64 E6581445 Key operated LED display Operation Press either the key or the key to change to the parameter  group .  Press the ENTER key to display the first extended parameter .  Press the key to change to . Pressing the ENTER key allows the reading of parameter setting.
  • Page 65: Panel Operation

    E6581445 3.2.2 Panel operation This section describes how to start/stop the motor, and set the operation frequency with the operating panel. :Set frequency Example of basic connection MCCB :Motor starts Motor R/L1 U/T1 Power S/L2 V/T2 :Stop the motor supply STOP T/L3 W/T3...
  • Page 66 E6581445 Example of operation panel control Key operated LED display Operation The running frequency is displayed. (When standard monitor display  selection = [Output frequency])  Set the operation frequency. Press the ENTER key to save the operation frequency. and the ⇔...
  • Page 67: Searching And Setting Parameters

    E6581445 4. Searching and setting parameters There are two types of setting mode quick mode and standard setting mode. Quick mode : EASY key: ON Eight frequently used basic parameters are just displayed (Factory default position). Quick mode (EASY) Title Function ...
  • Page 68: How To Set Parameters

    E6581445 How to set parameters This section explains how to set parameters, while showing how parameters are organized in each setting monitor mode. 4.1.1 Setting parameters in the selected quick mode To place the inverter in this mode, press the key (the LED lights up), and then press the key.
  • Page 69: Setting Parameters In The Standard Setting Mode

    E6581445 4.1.2 Setting parameters in the standard setting mode Press the key to place the inverter in this mode. MODE How to set basic parameters Selects parameter to be changed. (Press the key.) Reads the programmed parameter setting. (Press the key.) Change the parameter value.
  • Page 70: Functions Useful In Searching For A Parameter Or Changing A Parameter Setting

    E6581445 Adjustment range and display of parameters : An attempt has been made to assign a value that is higher than the programmable range. Or, as a result of changing other parameters, the programmed value of the parameter that is now selected exceeds the upper limit....
  • Page 71: Basic Parameters

    E6581445 5. Basic parameters This parameter is a basic parameter for the operation of the inverter. ⇒ Refer to Section 11, Table of parameters. History function : History function  • Function Automatically searches for 5 latest parameters that are programmed with values different from the standard default setting and displays them in the .
  • Page 72: Setting Acceleration/Deceleration Time

    E6581445 Setting acceleration/deceleration time  : Automatic acceleration/deceleration : Acceleration time 1  : Deceleration time 1  • Function 1) For acceleration time 1  programs the time that it takes for the inverter output frequency to go from 0Hz to maximum frequency .
  • Page 73: Manually Setting Acceleration/Deceleration Time

    E6581445 5.2.2 Manually setting acceleration/deceleration time Set acceleration time from 0 (Hz) operation frequency to maximum frequency  and deceleration time as the time when operation frequency goes from maximum frequency  to 0 (Hz). Output frequency [Hz]  = (Manual setting) Time [s] ...
  • Page 74 3) Increasing torque manually (V/f constant control) The VF-AS1 inverter is set to this control mode by factory default. This is the setting of constant torque characteristics that are suited for such things as conveyors. It can also be used to manually increase starting torque.
  • Page 75: Setting Parameters By Operating Method

    E6581445 Setting parameters by operating method  : Automatic function setting • Function Automatically programs all parameters (parameters described below) related to the functions by selecting the inverter's operating method. The major functions can be programmed simply. [Parameter setting] Title Function Adjustment range Default setting...
  • Page 76: Selection Of Operation Mode

    E6581445 Voltage/current switching by means of an external terminal (=) Switching between remote and local (different frequency commands) can be performed by turning on or off the S3 terminal. In that case, apply a voltage via the RR/S4 terminal and a current via the VI/II terminal. S3-CC OFF: The frequency is set according to the voltage applied to the RR/S4 terminal.
  • Page 77 E6581445 <Frequency setting mode selection> [Parameter setting] Title Function Adjustment range Default setting :VI/II (voltage/current input) :RR/S4 (potentiometer/voltage input) :RX (voltage input) :Operation panel input enabled (including LED/LCD option input) :2-wire RS485 communication input Frequency setting mode :4-wire RS485 communication input ...
  • Page 78 E6581445 The functions assigned to the following control input terminals (contact input: ⇒ Refer to Section 7.2) are always activated regardless of the settings of the command mode selection  and frequency setting mode selection 1 . • Reset terminal (default setting: RES, valid only for tripping) •...
  • Page 79 E6581445 2) Setting the run and stop frequencies (forward run, reverse run and coast stop) by means of external signals and setting the operation frequency with the operation panel Title Function Example of setting Run/stop : ON/OFF of terminals F-CC/R-CC (Standby: connection of terminals ...
  • Page 80 E6581445 4) Setting the run, stop and operation frequencies (forward run, reverse run and coast stop) by means of external signals (default setting) Title Function Example of setting Run/stop :ON/OFF of terminals F-CC/R-CC Command mode Speed command :External signal input :(Terminal input) ...
  • Page 81: Selecting Control Mode

    Selecting control mode  : V/f control mode selection • Function With “VF-AS1,” the V/f controls shown below can be selected. 0: Constant torque characteristics 1: Voltage decrease curve 2: Automatic torque boost (*1) 3: Sensorless vector control 1 (*1)
  • Page 82 E6581445 2) Decreasing output voltage Setting of V/f control mode selection = (Voltage decrease curve This is appropriate for load characteristics of such things as fans, pumps and blowers in which the torque in relation to load rotation speed is proportional to its square. Base frequency voltage 1 ...
  • Page 83 Setting of V/f control mode selection =,  (Sensorless vector control 1, 2) Using sensorless vector control with a Toshiba standard motor will provide the highest torque at the lowest speed ranges. The effects obtained through the use of sensorless vector control are described below.
  • Page 84 E6581445 Base frequency V/f 5-point setting voltage 1       [V]/[%]  Output frequency [Hz]       Base frequency 1 Note 1: Restrict the amount of torque to boost () to 3% or so. Boosting the torque too much may impair the linearity between points.
  • Page 85 30m, be sure to perform the auto-tuning (=) mentioned above, even when using a standard motor recommended by Toshiba. 2) The sensorless vector control exerts its characteristics effectively in frequency areas below the base frequency ().
  • Page 86: Manual Torque Boost-Increasing Torque Boost At Low Speeds

    E6581445 Manual torque boost–increasing torque boost at low speeds  : Manual torque boost 1 • Function If torque is inadequate at low speeds, increase torque by raising the torque boost rate with this parameter. Base frequency voltage 1  ...
  • Page 87: Maximum Frequency

    E6581445 Maximum frequency  : Maximum frequency • Function 1) Programs the range of frequencies output by the inverter (maximum output values). 2) This frequency is used as the reference for acceleration/deceleration time. Output frequency [Hz] In case of =80Hz •...
  • Page 88: Setting Frequency Command Characteristics

    E6581445 5.11 Setting frequency command characteristics  ~  ,  : VI/II point setting  ~  ,  : RR/S4 point setting  ~  : RX point setting  ~  :  ~  : It sets up, when using the optional circuit board. ...
  • Page 89 E6581445 Example of preset speed contact input signal : ON –: OFF (Speed commands other than preset speed commands are valid when all are OFF) Preset speed Terminal S1-CC – – – – – – – S2-CC – – – –...
  • Page 90 E6581445 Below is an example of 7-step speed operation. Output  frequency [Hz]       Time ST-CC F-CC S1-CC S2-CC S3-CC Example of 7-step speed operation 4)Setting the operation mode An operation mode can be selected for each preset speed. Operation mode setting Title Function...
  • Page 91: Selecting Forward And Reverse Runs (Operation Panel Only

    E6581445 5.13 Selecting forward and reverse runs (operation panel only)  : Forward/reverse run selection • Function Program the direction of rotation of the motor when the running and stopping are made using the RUN key and STOP key on the operation panel. Valid when ...
  • Page 92: Setting The Electronic Thermal

    E6581445 5.14 Setting the electronic thermal  : Motor electronic thermal protection level 1 : Electronic thermal protection characteristic selection   : OL reduction starting frequency  : Motor 150%-overload time limit  : Temperature detection • Function This parameter allows selection of the appropriate electronic thermal protection characteristics according to the particular rating and characteristics of the motor.
  • Page 93 Note:The motor overload starting level is fixed at 30Hz. If necessary, set  to , ,  or . (See the following section.) Even if the inverter is used with a Toshiba standard motor, the load may need to be reduced at frequencies of 30Hz and more in some cases.
  • Page 94 E6581445 Setting of motor electronic thermal protection level 1  If the capacity of the motor is smaller than the capacity of the inverter, or the rated current of the motor is smaller than the rated current of the inverter, adjust the electronic thermal protection level 1  so that it fits the motor's rated current.
  • Page 95 E6581445 3) Inverter overload characteristics Set to protect the inverter unit. Cannot be turned off by parameter setting. The inverter has two overload detecting functions, which can be switched from one to another using parameter  (temperature detection). [Parameter setting] Title Function Adjustment range...
  • Page 96: Changing The Display Unit % To A (Ampere)/V (Volt

    E6581445 5.15 Changing the display unit % to A (ampere)/V (volt)  : Current/voltage unit selection • Function These parameters are used to change the unit of monitor display. % ⇔A (ampere)/V (volt) Current 100% = Inverter’s rated current 200V-class voltage 100% = 200Vac 400V-class voltage 100% = 400Vac Example of setting During the operation of the VFAS1-2037PL (rated current 16.6A) at the rated load (100% load), units are displayed...
  • Page 97: Meter Setting And Adjustment

    Connect meters as shown below. <Connection to terminal FM> Meter: Frequency meter (default setting) VF-AS1 The reading of the frequency meter fluctuates during calibration. A frequency meter QS60T is optionally available. Output modes of the FM terminal When used with a 0~1mAdc ammeter...
  • Page 98 E6581445 [Terminal FM-related parameters] Adjustment Title Function Adjustment range Default setting level  : Output frequency  : Frequency command value  : Output current  : Input voltage (DC detection)  : Output voltage  : Compensated frequency *2 ...
  • Page 99 MODE (When standard monitor display selection  =  [Output frequency]) For meter connection, the VF-AS1 inverter has two output terminals; FM and AM, which can be used simultaneously. Meter adjustment 1 when the inverter is at rest (adjustment by setting  (  ) to  : Fixed output 1, ...
  • Page 100 E6581445 Meter adjustment Fixed output 1 Fixed output 2 Fixed output 3 Adjustment level  (  )   (  )   (  )   185% 100% 150% 250% 135% 100% Note: The 100% value of input/output power is the product of 3 ×200V (400V) ×...
  • Page 101: Pwm Carrier Frequency

    E6581445 Gradient bias adjustment of analog monitor output Here is an example of the adjustment of output from 0-20mA → 20-0mA, 4-20mA using the FM terminal.  =  ,  =   =  ,  =  (mA) (mA) 100%...
  • Page 102: Trip-Less Intensification

    E6581445 Note 5: If you change the carrier frequency, you may need to reduce the inverter’s continuous output current. ⇒ Refer to Section 1.4.4, “Current reduction curve.” Note 6: If the motor becomes overloaded when  is set to  or  (carrier frequency not decreased automatically), an overload trip occurs.
  • Page 103 E6581445 2) Restarting motor during coasting (Motor speed search function) Motor speed F-CC ST-CC =: This function operates after the ST-CC terminal connection has been opened first and then connected again. Title Function Adjustment range Default setting Example of setting :Disabled :At auto-restart after momentary stop Auto-restart control...
  • Page 104: Regenerative Power Ride-Through Control/Deceleration Stop During Power Failure/Synchronized Acceleration/Deceleration

    E6581445 5.18.2 Regenerative power ride-through control/Deceleration stop during power failure/Synchronized acceleration/deceleration  : Regenerative power ride-through control  : Non-stop control time/Deceleration time during power failure  : Synchronized deceleration time  : Synchronized acceleration time  : Regenerative power ride-through control level •...
  • Page 105 E6581445 An example of setting when = Input voltage Motor speed Time Deceleration stop • Even after the recovery from an input power failure, the motor continues slowing down to a stop. If the voltage in the inverter main circuit falls below a certain level, however, control will be stopped and the motor will coast. •...
  • Page 106: Dynamic (Regenerative) Braking - For Abrupt Motor Stop

    Note 1: The time set using  is the time for which the resistor sustains an overload. (Enter the time elapsed before the inverter trips if a load 10 times as large as the allowable continuous braking resistance specified using  is applied.) There is no need to change resistance settings recommended by Toshiba (except DGP resistance setting).
  • Page 107 E6581445 All 200V VF-AS1 and 400V VF-AS1 with ratings of up to 160kW have built-in dynamic braking transistors as standard equipment. If the rating of your inverter falls within this range, connect the resistor, as shown in Figure a) below or Figure b) on the next page.
  • Page 108 E6581445 b) When a using braking resistor without thermal fuse An external braking resistor (optional) * If no power supply is provided TH - Ry for the control circuit MCCB PA/+ Motor Three-phase R/L1 U/T1 main circuit S/L2 V/T2 power supply T/L3 W/T3 Depression...
  • Page 109 E6581445 c) Capacities of 400V-200kW or more TH - Ry An external braking resistor (optional) * If no power supply is provided Dynamic braking unit (optional) for the control circuit MCCB PA/+ PC/- Motor R/L1 Three-phase U/T1 main circuit S/L2 V/T2 power supply T/L3...
  • Page 110 E6581445 Selection of braking resistor option and braking unit Standard braking resistors are listed in the table below. The usage rate is 3%. (Except for type DGP***) Braking resistor Continuous regenerative Inverter type Model number Rating braking allowable capacity [Note 2] [Note 1] VFAS1-2004PL, PBR-2007...
  • Page 111 E6581445 Minimum resistance of connectable braking resistors The minimum allowable resistance values of the externally connectable braking resistors are listed in the table below. Do not connect braking resistors with smaller resultant resistance than the listed minimum allowable resistance values. (For 200kW or greater models, a dynamic braking resistor drive unit (optional separate unit) is needed.) Inverter 200V Class...
  • Page 112: Standard Default Setting

    E6581445 5.20 Standard default setting  : Factory default setting • Function This parameter is to set two or more parameters at a time for different commands. Using this parameter, all parameters can be also return to their respective default settings by one operation, and save or set specific parameters individually.
  • Page 113: Inverters A

    E6581445 Default setting (=) Setting parameter  to  resets all parameters except the following to their default settings. When this parameter is set to 3,  is displayed for a while, then switches back to the original display (  ...
  • Page 114: Searching For All Reset Parameters And Changing Their Settings

    E6581445 5.21 Searching for all reset parameters and changing their settings  : Automatic edit function • Function Automatically searches for only those parameters that are programmed with values different from the standard default setting and displays them in the user parameter group . Parameter setting can also be changed within this group.
  • Page 115: Easy Key Function

    E6581445 5.22 EASY key function  : Registered parameter  ~  : display selection Quick registration parameter 1~32  : EASY key function selection • Function The following three functions can be assigned to the EASY key for easy operation by means of a single key. •...
  • Page 116 E6581445 [How to select parameters] Select the desired parameters as parameters 1 to 32 (~). Note that parameters should be specified by communication number. For communication numbers, refer to Table of parameters. In the quick mode, only parameters registered as parameters 1 to 32 are displayed in order of registration. By default, parameters are set as shown in the table below.
  • Page 117: Extended Parameters

    E6581445 6. Extended parameters Extended parameters are provided for sophisticated operation, fine adjustment and other special purposes. ⇒ Refer to Section 11, Table of parameters. Input/output parameters 6.1.1 Low-speed signal  : Low-speed signal output frequency • Function When the output frequency exceeds the setting of  an ON signal will be generated. This signal can be used as an electromagnetic brake excitation/release signal.
  • Page 118: Putting Out Signals Of Arbitrary Frequencies

    E6581445 6.1.2 Putting out signals of arbitrary frequencies  : Speed reach setting frequency  : Speed reach detection band • Function When the output frequency becomes equal to the frequency set by  ± , an ON or OFF is generated.
  • Page 119: Input Signal Selection

    E6581445 Input signal selection 6.2.1 Priority when forward/reverse run commands are entered simultaneously  : Priority when forward/reverse run commands are entered simultaneously • Function This parameter allows you to select the direction in which the motor runs when a forward run (F) command and a reverse run (R) command are entered simultaneously.
  • Page 120: Assigning Priority To The Terminal Board In The Operation Panel And Operation Mode

    E6581445 6.2.2 Assigning priority to the terminal board in the operation panel and operation mode  : Input terminal priority selection • Function This parameter is used to give priority to certain external commands entered from the terminal board in operation panel and operation mode.
  • Page 121: Analog Input Signal Switching

    E6581445 Output frequency [Hz] Forward run Set frequency Forward run Panel key STOP STOP STOP ST-CC 3-CC (Jog run) 6.2.3 Analog input signal switching  : Analog input VI/VII voltage/current switching  : Analog input AI2 (optional circuit board) voltage/current switching •...
  • Page 122: Terminal Function Selection

    E6581445 Terminal function selection 6.3.1 Keeping an input terminal function always active (ON)  ,  , : Always ON function selection 1~3   • Function This parameter specifies an input terminal function that is always kept active (ON). (Only one function selectable) [Parameter setting] Title...
  • Page 123 E6581445 Connection method 1) a-contact input Inverter a-contact switch Sink setting Input This function is activated when the input terminal and CC terminal (common) are short-circuited. Use this function to specify forward/reverse run or a preset speed operation. 2) Connection with transistor output Inverter Programmable controller Input...
  • Page 124: Using The Servo Lock Function

    E6581445 6.3.3 Using the servo lock function  : Input terminal function selection 3 (ST)  : Starting frequency setting • Function As with the operation of a server motor, these parameters allow you to operate the motor at 0Hz by simply issuing an operation signal.
  • Page 125: Response Time Of Input/Output Terminals

    E6581445 6.3.5 Response time of input/output terminals  : Input terminal 1 response time selection  : Input terminal 2 response time selection  : Input terminal 3 response time selection  : Input terminal 4 response time selection  : Input terminal 5~12 response time selection ...
  • Page 126 E6581445 Setting of switching terminals The V/f1, V/f2, V/f3 and V/f4 switching function is not yet assigned to any terminal. Therefore, it is necessary to assign them to unused terminals. Ex.) Assigning the V/f switching 1 function to S1 and the V/f switching 2 function to S2. Title Function Adjustment range...
  • Page 127: V/F 5-Point Setting

    E6581445 V/f 5-point setting  : V/f 5-point setting VF1 frequency  : V/f 5-point setting VF4 frequency  : V/f 5-point setting VF1 voltage  : V/f 5-point setting VF4 voltage  : V/f 5-point setting VF2 frequency  : V/f 5-point setting VF5 frequency ...
  • Page 128 E6581445 2) Automatic switching by means of switching frequencies (=) Command selected Operation frequency with  command Command selected with  A: If the frequency set with  is higher than that set with  Priority is given to the command set with .
  • Page 129: Start Frequency/Stop Frequency

    E6581445 Operation frequency 6.7.1 Start frequency/Stop frequency  : Start frequency setting  : Stop frequency setting • Function The frequency set with the parameter  is put out as soon as operation is started. Use the  parameter when a delay in response of starting torque according to the acceleration/deceleration time is probably affecting operation.
  • Page 130: Frequency Setting Signal 0Hz Dead Zone Handling Function

    E6581445 Output frequency [Hz] The inverter begins accelerating after  the frequency command value has reached point B. Deceleration stop begins when the   frequency command value decreases  below point A.  –  100% Operation frequency command value 6.7.3.
  • Page 131: Dc Braking

    E6581445 Note:During DC braking, the DC braking current may be adjusted Output frequency [Hz] automatically to prevent the overload LED display protection function from being activated and causing the inverter to  displayed Set frequency trip. DC braking The DC braking current may be adjusted automatically to prevent tripping.
  • Page 132: Motor Shaft Fixing Control

    E6581445 [Priority to DC braking during forward/reverse operation] (Forward/reverse run DC braking priority control =[Enabled]) Output frequency [Hz] : DC braking = =      Set frequency  Time [s] Reference frequency   Forward run signal (F-CC) Reverse run signal (R-CC) (4) During normal forward/reverse run (=) : Not recognized as a stop command, so that the DC...
  • Page 133: Function Of Issuing A 0Hz Command During A Halt

    E6581445 LED display Output frequency [Hz]  is displayed.  is displayed. Set frequency  DC braking start frequency  Time [s] Output current [A]  Operation signal (F-CC) Operation standby signal (ST-CC) Note 1: If the motor shaft fixing control parameter  is set at  (enabled) when the output frequency is below the DC braking start frequency ...
  • Page 134: Auto-Stop In Case Of Lower-Limit Frequency Continuous Operation (Sleep/Wake-Up Function

    E6581445 Auto-stop in case of lower-limit frequency continuous operation (Sleep/Wake-up function)  : Time limit for lower-limit frequency operation • Function If operation is carried out continuously at a frequency below the lower-limit frequency () for the period time set , theinverter will automatically slow down the motor to a stop. “”...
  • Page 135: Jog Run Mode

    E6581445 6.10 Jog run mode  : Jog run frequency  : Jog run stop pattern  : Operation panel jog run mode • Function Use the jog run parameters to operate the motor in jog mode. Input of a jog run signal generates a jog run frequency output at once, irrespective of the designated acceleration time.
  • Page 136: Setting Frequency Via External Contact Input (Up/Down Frequency Setting

    E6581445 [Setting of jog run setting terminal (S3-CC)] Assign control terminal S3 ([: preset speed 3] in default setting) as the jog run setting terminal. Title Function Adjustment range Example of setting Input terminal function selection 7 (S3)  (Jog run setting terminal) ...
  • Page 137 E6581445 Adjustment with continuous signals (Parameter setting example 1) Set parameters as follows to adjust the output frequency up or down in proportion to the frequency adjustment signal input time: Panel frequency incremental gradient = / setting time Panel frequency decremental gradient = / setting time Set parameters as follows to adjust the output frequency up or down almost in synchronization with the adjustment by the panel frequency command: ...
  • Page 138: Jump Frequency - Jumping Resonant Frequencies

    E6581445 If two signals are input simultaneously • If a clear single and an up or down signal are input simultaneously, priority will be given to the clear signal. • If up and down signals are input simultaneously, the frequency will be increased or reduced by the difference between the settings of ...
  • Page 139: Preset Speed Operation Frequencies

    E6581445 [Parameter setting] Title Function Adjustment range Default setting  Jump frequency 1 ~ Hz   Jumping width 1 ~ Hz   Jump frequency 2 ~ Hz   Jumping width 2 ~ Hz   Jump frequency 3 ~...
  • Page 140: Trip-Less Intensification

    E6581445 6.14 Trip-less intensification 6.14.1 Retry function  : Retry selection (selecting the no. of times) Warning • Stand clear of motors and equipment. The motor and equipment stop when the alarm is given, selection of the retry function will restart them suddenly after the specified time has elapsed.
  • Page 141: Avoiding Overvoltage Tripping

    E6581445 Even when trip retention selection parameter () is set to , the retry function is enabled by  setting. During retry the blinking display will alternate between  and the monitor display specified by parameter monitor display selection parameter . The number of retries will be cleared if the inverter is not tripped for the specified period of time after a successful retry.
  • Page 142 E6581445 [Parameter setting] Title Function Adjustment range Default setting 200V models: Base frequency voltage 1 V class:~ V  (output voltage  V class:~ V 400V models: adjustment)  Base frequency voltage :Without voltage compensation (limitless output voltage) selection : With voltage compensation (limitless output voltage) ...
  • Page 143: Reverse Run Prohibition

    E6581445 6.14.4 Reverse run prohibition  : Reverse run prohibition selection • Function This function prevents the motor from running in the forward or reverse direction when it receives the wrong operation signal. [Parameter setting] Title Function Adjustment range Default setting :Permit all, :Prohibit reverse run Reverse-run prohibition selection ...
  • Page 144: Light-Load High-Speed Operation Function

    E6581445 • The error in drooping insensitive torque increases in the frequency range above the base frequency, and it is therefore recommended that these functions be used at frequencies below the base frequency. • During drooping control, the output frequency is not restricted by the maximum frequency (). The change in frequency at the time of drooping can be calculated, as described below: a) Gain by internal torque reference (Gain1) If internal torque reference (%)
  • Page 145: Braking Function

    E6581445 6. 17 Braking function  : Braking mode selection  : Brake release time  : Load portion torque input  : Creeping frequency selection  : Creeping time  : Hoisting torque bias input  : Braking time learning function ...
  • Page 146 Note2: For the braking functions, the pre-excitation time is automatically determined by the inverter from motor- related constants. When the VFAS1-2037PL is used in combination with a Toshiba 4P-3.7kW-60Hz-200V standard motor, the preliminary excitation time is approximately 0.1 to 0.2 seconds.
  • Page 147: Acceleration/Deceleration Suspend Function

    E6581445 6.18 Acceleration/deceleration suspend function  : Acceleration/deceleration  : Deceleration suspend frequency suspend function  : Deceleration suspend time  : Acceleration suspend frequency  : Acceleration suspend time • Function Using these parameters, acceleration or deceleration can be suspended to let the motor run at a constant speed.
  • Page 148: Commercial Power/Inverter Switching

    E6581445 If the stall control function is activated during constant-speed rotation The frequency drops momentarily as a result of stall control, but the time for which the frequency drops is included in the suspend time. Output frequency [Hz]   Time [s] ...
  • Page 149 E6581445 [Timing chart (example)] Commercial power switching frequency holding time  Detection time Commercial power/inverter switching frequency  Set frequency Inverter-side switching waiting time  MC output for inverter operation Commercial power/inverter switching output 1 (P24-OUT1) Commercial power-side switching waiting time ...
  • Page 150: Pid Control

    E6581445 6.20 PID control  : PID control switching  : Process upper limit  : PID control feedback control signal selection  : Process lower limit  : Delay filter  : PID control waiting time  : Proportional (P) gain ...
  • Page 151 E6581445 1) External connection Pressure transmitter (1) Process value DC:0~10V RR/S4 VI/II (2) Feedback value DC:4~20mA 2) Types of PID control interface Process value (frequency) and feedback value can be combined as follows for the PID control of the VF-PS1. (1)Process value(frequency setting) (2) Feedback value Frequency setting mode selection ...
  • Page 152 E6581445 3) Setting the PID control In case of controlling the airflow, water flow and pressure, please set the parameter to””(Process type PID control operation) (1)Please set the parameter (Acceleration time),(deceleration time) to the suitable time for the system. (2)Please set the following parameters to place limits to the setting value and the control value. Placing a limit to the process value : The parameter (Process upper limit), ...
  • Page 153 E6581445  Differential (D) gain The differential (D) gain set with f366 is the differential (D) gain obtained by PID control. The differential gain increases the speed of response to rapid changes in deviation. If this gain is set excessively high, a phenomenon in which the output frequency greatly fluctuates may occur.
  • Page 154: Stop Position Control Function

    E6581445 The characteristic of the feedback value can also be reversed by means of a signal from an external device. Example: To use the S3 terminal as a PID normal/reverse characteristic switching signal input terminal Title Function Adjustment range Default setting ...
  • Page 155 Operation in automatic torque boost mode or vector control mode =, , , ,  Is the motor Toshiba standard four-pole motor with the same capacity rating as the inverter? Is the motor cable 30m or less in length? *1 Set the following parameters, as specified on the motor nameplate.
  • Page 156 :Motor constant auto calculation ( after execution) =: Resets  (motor constant 1),  (motor constant 2),  (motor constant 3) and  (motor constant 4) to their factory default settings (constant of a Toshiba standard four-pole motor with the same capacity as the inverter).
  • Page 157: Setting Motor Constants

    E6581445 Examples of setting the motor constants a) Combination with a Toshiba standard motor (4P motor with the same capacity as the inverter) Inverter : VFAS1-2037PL Motor : 3.7kW-4P-60Hz 1) Set the V/f control mode selection  at  (Sensorless vector control).
  • Page 158: Increasing The Motor Output Torque Further In Low Speed Range

    E6581445 6.23 Increasing the motor output torque further in low speed range  : Exciting strengthening coefficient  : Stall prevention factor The output torque of the motor can adjusted using the parameters described in 6.22 in most cases, but if a finer adjustment is required, use these parameters.
  • Page 159: Torque Control

    E6581445 6.24 Torque control ⇒ For details, refer to Instruction Manual (E6581331) specified in Section 6.42. 6.24.1 Torque command : V/f control mode selection   : Torque command selection  : VI/II input point 1 setting  : VI/II input point 1 rate ...
  • Page 160 E6581445 For a crane/hoist, an elevator application, as lifted Reverse run up and down at controlled speeds, the direction of rotation is frequently reversed. In such cases, the Forward run load can be started smoothly, by adding load torque into the torque reference equivalent to the additional torque, when starting acceleration after releasing the brake.
  • Page 161: Torque Limit

    E6581445 6.25 Torque limit 6.25.1 Torque limit switching  : Power running torque limit 1  : Power running torque limit 3 selection level  : Power running torque limit 1  : Regenerative braking torque level limit 3 level ...
  • Page 162 E6581445 [Parameter setting] Title Function Adjustment range Default setting :VI/II (voltage/current input) :RR/S4 (potentiometer/voltage  Power running torque limit 1 selection input)  :RX (voltage input) : Power running torque limit 1 level ~ %  %:Disabled  %  :VI/II (voltage/current input) :RR/S4 (potentiometer/voltage Regenerative braking torque limit 1...
  • Page 163: Torque Limit Mode Selection At Acceleration/Deceleration

    E6581445 RX-CCA RR/S4 -CCA, VI-CCA 100% +100% Torque produced Torque produced by motor by motor -10V +10V II-CCA -100% 100% Torque produced by motor 20mA [Parameter setting] Title Function Adjustment range Default setting :VI/II (voltage/current input) :RR/S4 (potentiometer/voltage Power running torque limit 1 selection input) ...
  • Page 164 E6581445 Operation frequency Frequency [Hz] If the torque limit function is not activated Actual speed Time [s] Torque [N·m] Torque limit level Time [s] Mechanical brake (released) Time [s] (2) =(In sync with min. time) The operation frequency keeps increasing, even if the torque limit function is activated. In this control mode, the actual speed is kept in sync with the operation frequency, while torque is held at a limit level when it decreases as a result of the release of the mechanical brake.
  • Page 165: Stall Prevention Function

    E6581445 6.26 Stall prevention function 6.26.1 Power running stall continuous trip detection time  : Power running stall continuous trip detection time • Function A function for preventing lifting gear from failing accidentally. If the stall prevention function is activated in succession, the inverter judges that the motor has stalled and trips.
  • Page 166: Fine Adjustment Of Frequency Setting Signal

    E6581445 6.28 Fine adjustment of frequency setting signal  : VI/II input bias  : RX input gain  : VI/II input gain  : Optional AI1 input bias  : RR/S4 input bias  : Optional AI1 input gain ...
  • Page 167: Acceleration/Deceleration

    E6581445 6.30 Acceleration/deceleration 2 6.30.1 Setting acceleration/deceleration patterns and switching acceleration/deceleration patterns 1, 2, 3 and 4  : Acceleration time 2  : Deceleration S-pattern upper limit adjustment  : Deceleration time 2  : Acceleration time 3  : Acceleration/deceleration 1 pattern ...
  • Page 168 E6581445 2) Switching by frequencies - Automatically switching acc/dec times at certain frequencies Title Function Adjustment range Default setting  Acceleration/deceleration switching frequency 1 ~ Hz   Acceleration/deceleration switching frequency 2 ~ Hz   Acceleration/deceleration switching frequency 3 ~...
  • Page 169 E6581445 Setting parameters a) Operating method: Terminal input Set the command mode selection  to . b) Use the S2 and S3 terminals for switching. (Instead, other terminals may be used.) S2: Acceleration/deceleration switching signal 1 S3: Acceleration/deceleration switching signal 2 Title Function Adjustment range...
  • Page 170: Pattern Operation

    E6581445 3) S-pattern acceleration/deceleration 2 Select this pattern to obtain slow acceleration in a demagnetizing region with a small motor acceleration torque. This pattern is suitable for high-speed spindle operation. Output frequency [Hz] Output frequency [Hz] Maximum frequency Maximum frequency ...
  • Page 171 E6581445 <Basic operating> Step Setting Parameter Set the pattern operation selection  =  (Disabled) parameter at “Enabled.”  (Pattern operation enabled, setting in seconds)  (Pattern operation enabled, setting in minutes) Set all necessary operation frequencies.  ~  (Preset speed operation frequencies 1~7) In addition, set frequencies for preset ...
  • Page 172: Preset Speed Mode

    E6581445 Pattern operation switching output (output terminal function:  ,  ) If the pattern operation switching output function is selected (activated), a signal is put out on completion of all the predetermined patterns of operation. When there is no operation command left to be entered or the pattern operation selection signal changes, the output terminals are turned off.
  • Page 173: Protection Functions

    E6581445 6.33 Protection functions 6.33.1 Setting of stall prevention level  : Stall prevention level Warning • Do not set the stall prevention level () extremely low. If the stall prevention level parameter () is set at or below the no-load current of the motor, the stall preventive function will be always active and increase the frequency when it judges that regenerative Prohibited braking is taking place.
  • Page 174: Emergency Stop

    E6581445 6.33.3 Emergency stop  : Emergency stop  : Emergency DC braking control time • Function Emergency stop mode can be selected. At emergency stop, a trip message (“”) is displayed. FL relay can be deactivated using the output function selection. 1) Emergency stop by terminal operation Emergency stop can be performed with the a or b-contact.
  • Page 175: Output Phase Failure Detection

    E6581445 6.33.4 Output phase failure detection  : Output phase failure detection mode selection • Function This parameter detects inverter output phase failure. If the inverter detects an open phase failure, the tripping function and the FL relay will be activated. At the same time, the trip information  will also be displayed.
  • Page 176: Control Mode For Low Current

    E6581445 6.33.8 Control mode for low current  : Low current detection hysteresis width  : Low current trip selection  : Low current detection current  : Low current detection time • Function If the current is lower than  level and passes for a time longer than , the inverter trips. Trip information is displayed as “.”...
  • Page 177: Detection Of Output Short Circuit

    E6581445 6.33.9 Detection of output short circuit  : Selection of short circuit detection at starting • Function Detects a short-circuit on the output side of the inverter. Title Function Adjustment range Default setting :Each time (standard pulse) :Only one time after power is turned on :Each time (short pulse) Selection of short circuit ...
  • Page 178: Cooling Fan Control Selection

    E6581445 Overtorque signal output less than     -  Torque [%] Time [sec] When = (tripping), the inverter will trip if overtorque lasts for the period of time set with . In such a case, the overtorque signal remains ON. 6.33.11 Cooling fan control selection ...
  • Page 179: Abnormal Speed Detection

    E6581445 6.33.13 Abnormal speed detection  : Abnormal speed detection time  : Overspeed detection frequency upper band  : Overspeed detection frequency lower band • Function These parameters allow you to set the inverter so that, when it is in sensor speed control mode (=, ), it always monitors the rotational speed of the motor, even when the motor is at rest, and if the speed remains out of the specified limits for the specified length of time, it outputs an error signal.
  • Page 180: Regenerative Power Ride-Through Control Level

    E6581445 6.33.16 Regenerative power ride-through control level  : Regenerative power ride-through control level • Function This parameter is used to set the operation level of the regenerative power ride-through control and the deceleration stop. (Refer to Section 5.18.2.) Title Function Adjustment range Default setting...
  • Page 181: Guide To Time Of Replacement

    E6581445 6.33.19 Guide to time of replacement  : Annual average ambient temperature • Function You can set the inverter so that it will calculate the remaining useful life of the cooling fan, main circuit capacitor and on-board capacitor from the ON time of the inverter, the operating time of the motor, the output current (load factor) and the setting of ...
  • Page 182: Selection Of A Restart Condition For The Motor Stopped With A Mechanical Brake

    E6581445 6.33.23 Selection of a restart condition for the motor stopped with a mechanical brake : Brake-equipped motor restart condition selection  • Function With this function, the motor can be restarted immediately after a stop if it is operated at a frequency of more than 10Hz (20Hz or less) and stopped with a mechanical brake.
  • Page 183 E6581445 =: If control power is not backed up with an external backup device: Select this setting if an external backup device is not connected to the inverter’s control terminals +SU and CC. =: If control power is backed up with an external backup device (alarm signal output): Be sure to select this setting if an external backup device is connected to the inverter’s control terminals +SU and CC, and if the main power supply is turned on and off endlessly for reasons of sequence, as shown below, in the event the external power backup device fails.
  • Page 184: Override

    E6581445 6.34 Override  : Override addition input selection  : Override multiplication input selection • Function These parameters are used to adjust reference frequencies by means of external input. Title Function Adjustment range Default setting :Disabled :VI/II (voltage/current input) :RR/S4 (potentiometer/voltage input) :RX (voltage input) :Operation panel input enabled (including...
  • Page 185 E6581445 Ex.1: = (VI/II input), = (disabled) Output frequency = Reference frequency + Override (VI/II input [Hz]) Ex.2: = (VI/II input), = (disabled) Output frequency = Reference frequency + Override (VI/II input [Hz]) 2) Multiplicative override In this mode, each output frequency is multiplied by an externally override frequency. [Ex.1: RR/S4 (Reference frequency), VI/II (Override input)] [Ex.2: RX (Reference frequency), VI/II (Override input)] Output frequency...
  • Page 186: Adjustment Parameters

    E6581445 6.35 Adjustment parameters 6.35.1 Pulse train output for meters  : Logic output/pulse output selection (OUT1)  : Pulse output function selection  : Selection of number of pulses • Function Pulse trains can be sent out through the OUT1-NO output terminals. To do so, it is necessary to select a pulse output mode and specify the number of pulses.
  • Page 187: Setting Of Optional Meter Outputs

    E6581445 6.35.2 Setting of optional meter outputs  ~  ,  ~  : Meter output settings ⇒ For details, refer to Instruction Manual (E6581341) specified in Section 6.42. 6.35.3 Calibration of analog outputs  : FM voltage/current output switching ...
  • Page 188: Operation Panel Parameter

    E6581445 6.36 Operation panel parameter 6.36.1 Prohibition of key operations and parameter settings  : Parameter write protect selection  : Operation panel frequency setting prohibition selection  : Operation panel emergency stop operation prohibition selection  : Operation panel reset operation prohibition selection ...
  • Page 189: Displaying The Rotational Speed Of The Motor Or The Line Speed

    E6581445 6.36.2 Displaying the rotational speed of the motor or the line speed  : Frequency free unit display magnification  : Frequency free unit conversion selection  : Free unit display gradient characteristic  : Free unit display bias •...
  • Page 190: Changing The Steps In Which The Value Displayed Changes

    E6581445 An example of setting: When  is , and  is  =, = =, = Panel indication Panel indication 1000   80(Hz) 80(Hz) Output frequency Output frequency =, = Panel indication  Output frequency 80 (Hz) 6.36.3 Changing the steps in which the value displayed changes ...
  • Page 191: Changing The Standard Monitor Display

    E6581445 6.36.4 Changing the standard monitor display  : Standard monitor display selection  ~  : Status monitor 1~8 display selection These parameters are used to select the item to be displayed when the power turned on and also to change items displayed in status monitor mode.
  • Page 192: Torque-Related Parameters For Panel Operation

    E6581445 6.36.8 Torque-related parameters for panel operation  : Operation panel tension torque bias  : Operation panel load sharing gain These parameters are used to specify the torque bias and how to share the load. ⇒ For details, refer to Instruction Manual (E6581331) specified in Section 6.42. 6.37 Tracing functions ...
  • Page 193 E6581445 1) To acquire trace data at the occurrence of tripping: = (Examples of current date output) Trip Monitor value of output current Failure FL signal :Trace data Trace data 1 2) To acquire trace data at the time of triggering: = Trigger input Trace data 1 Ex.) When using the RR/S4 terminal as the tracing back trigger signal terminal...
  • Page 194 My function monitor 2   FE62 My function monitor 3  FE63 My function monitor 4 Acquisition of trace data Trace data is acquired through a communication device. The VF-AS1 supports the protocols listed below. • RS485 (Standard protocol) F-78...
  • Page 195: Integrating Wattmeter

    E6581445 Trace data communication number Communication Minimum setting Function Setting/readout range Default setting /readout unit E000 Trace data 1~4 pointer / ~  E100 Data 1 of trace data 1 / ~  Data 2~99 of trace data 1 / ~...
  • Page 196: Communication Function

    E6581445 6.39 Communication function 6.39.1 2-wire RS485/4-wire RS485  : Communication speed (2-wire RS485)  : Parity (common to 2-wire RS485 and 4-wire RS485)  : Inverter number (common)  : Communications time-out time (common to 2-wire RS485 and 4-wire RS485) ...
  • Page 197  (common to 2-wire RS485) master) :Master (sends a frequency command) :Master (sends an output frequency) :Master (sends a torque command) :Master (sends an output torque command)  Protocol selection (2-wire RS485) :TOSHIBA, :MODBUS  F-81...
  • Page 198 E6581445 Title Function Adjustment range Default setting :Disabled :2-wire RS485 Frequency point selection   :4-wire RS485 :Communication add option Point 1 setting ~ %   Point 1 frequency ~ Hz   Point 2 setting ~ %  ...
  • Page 199 E6581445 2) 4-wire RS485 The 4-wire RS485 device included as standard equipment, allows you to connect the inverter to a higher-level system (host) and to set up a network for data communications between inverters. It makes it possible for the inverter to be linked to a computer and to carry out data communications with other inverters.
  • Page 200 E6581445 <Broadcast> When an operation frequency command is broadcasted from the host computer to inverters : Wiring Host computer : Data (host → INV) No.00 No.01 No.02 No.03 No.29 No.30 : Use the terminal board to branch the cable. (1) Data is sent from the host computer. (2) Data from the computer is received at each inverter and the inverter numbers are checked.
  • Page 201 (4-wire RS485) master) :Master (sends a frequency command) :Master (sends an output frequency) :Master (sends a torque command) :Master (sends an output torque command) :TOSHIBA Protocol selection (4-wire RS485)   :MODBUS :Disabled :Command information 1 :Command information 2 Block write data 1 ...
  • Page 202: Open Network Option

    E6581445 Title Function Adjustment range Default setting :Deselect :Status information :Output frequency :Output current :Output voltage :Alarm information :PID feedback value :Input terminal board monitor :Output terminal board monitor :VI/II terminal board monitor  Block read data 1  :RR/S4 terminal board monitor :RX terminal board monitor :Input voltage (DC detection) :Speed feedback frequency...
  • Page 203: My Function

    E6581445 6.41 Traverse function  : Traverse selection  : Traverse step : Traverse acceleration time : Traverse jump step   : Traverse deceleration time  ⇒ For details, refer to Instruction Manual (E6581337) specified in Section 6.42. Instruction manuals for optionally available devices and special functions 6.42 For details, refer to the instruction manual for each optional device or function.
  • Page 204: Operation With External Signal

    E6581445 7. Operation with external signal External operation The inverter can be freely controlled externally. Parameters must be differently set depending on the operation method. Make sure of the operation method before setting parameters, and set parameters properly to the operation mode according to the procedure mentioned below. [Steps in setting parameters] Check of external signal conditions Operation signal:...
  • Page 205: Applied Operation With Input And Output Signals (Operation By Terminal Board

    E6581445 Applied operation with input and output signals (operation by terminal board) 7.2.1 Functions of input terminals (in case of sink logic) Use the above parameters to send signals from an external programmable controller to various control input terminals to operate and/or set the inverter. The desired contact input terminal functions can be selected from 120 types.
  • Page 206 E6581445 3) Connection with transistor output Inverter Programmable controller Input terminal The inverter can be controlled by connecting the input terminal with output (contactless switch) of a programmable controller. Use this function to specify forward/reverse run or a preset speed operation. Use a transistor that operates on 24Vdc, 5mA power.
  • Page 207 E6581445 Table of setting of contact input terminal function Parameter setting Parameter setting Function Function Positive Negative Positive Negative logic logic logic logic No function is assigned Servo lock signal     F: Forward run command Simple positioning (positioning loop) ...
  • Page 208: Functions Of Output Terminals (Incase Of Sink Logic

    E6581445 Sink logic/source logic Switching between sink logic and source logic (input/output terminal logic) is possible. ⇒ For details, refer to the Section 2.3.2. 7.2.2 Functions of output terminals (incase of sink logic) Use the above parameters to send various signals from the inverter to external equipment. By setting parameters for the OUT1, OUT2 and FL (FLA, FLB and FLC) terminals on the terminal board, you can use 0~255 functions and functions obtained by combining them.
  • Page 209 E6581445 Output terminal function (open collector, relay outputs) setting and detection levels For the open connector output terminals (OUT1, OUT2) and the relay output terminals (FLA, FLB and FLC), functions can be selected from 0 to 255 functions. The selectable functions and detection levels are listed in the table below.
  • Page 210 E6581445 Parameter setting Function Operation output specifications (in case of positive logic) Positive Negative logic logic ON:The state that torque component is  ,  set   Over-torque detection value or larger continued more than  set value. ON:A certain rate of braking resister overload trip (  ) Braking resistor detection time is over.
  • Page 211 E6581445 Parameter setting Function Operation output specifications (in case of positive logic) Positive Negative logic logic Specified data output   Specified data output   Specified data output   Specified data output Output of the designated data in 7-bit. ...
  • Page 212: Setup Of Input Terminal Operation Time

    E6581445 7.2.3 Setup of input terminal operation time •Function The input/output terminal operation time setup function is used to extend response time if there is something malfunctioning because of noise or chattering of input relay. Setup of response time Title Function Adjustment range Default setting...
  • Page 213: Setup Of External Speed Command (Analog Signal

    E6581445 Setup of external speed command (analog signal) Function of analog input terminals can be selected from four functions (external potentiometer, 0 to 10Vdc, 4 (0) to 20mAdc, -10 to +10Vdc). The selective function of analog input terminals gives system design flexibility. ⇒...
  • Page 214: Setup By Analog Input Signals (Rr/S4 Terminal

     Run/stop setup To control switching between forward run CHARGE MCCB Motor (F) and reverse run (R), and stop by U/T1 R/L1 VF-AS1 Power external commands. V/T2 S/L2 supply Setup of frequency setting signal and W/T3 T/L3 running frequency characteristic...
  • Page 215: Setup By Analog Input Signals (Vi/Ii Terminal

     (Max. filter) Run/stop setup To control switching between forward run CHARGE MCCB Motor (F) and reverse run (R), run and stop by U/T1 VF-AS1 R/L1 Power external commands. V/T2 S/L2 supply Setup of frequency setting signal and W/T3 T/L3...
  • Page 216: Setup By Analog Input Signals (Rx Terminal

     ~  Hz   Run/stop setup CHARGE Run/stop operation by means of external MCCB Motor commands. U/T1 VF-AS1 R/L1 Power Setup of frequency setting signal and V/T2 S/L2 supply W/T3 T/L3 running frequency characteristic To set up frequency setting signal to be input to the external signal (RX terminal) and characteristic of running frequency.
  • Page 217: Monitoring The Operation Status

    E6581445 8. Monitoring the operation status Screen composition in the status monitor mode The status monitor mode is used to monitor the operation status of the inverter. ⇒ For modes available and instructions about how to switch them, refer to section 3.1. Here is the screen composition in the status monitor mode.
  • Page 218: Monitoring The Status

    E6581445 Monitoring the status 8.2.1 Status monitor under normal conditions In this mode, you can monitor the operation status of the inverter. twice To monitor the inverter when it is normally running, press the MODE and the current status is indicated on the LED display.
  • Page 219 E6581445 (Continued) Commun ication Item displayed Description operated display [Note 5] FE10 Past trip 1 Past trip 1 (displayed alternately at 0.5-sec. intervals) ⇔ [Note 5]  ⇔ FE11 Past trip 2 Past trip 2 (displayed alternately at 0.5-sec. intervals) [Note 5] FE12 Past trip 3...
  • Page 220 E6581445 Input terminal information Data bit of communication No. F E 06 Input terminal 1 (F) :  : 0 Input terminal 2 (R) :  : 1 When there is signal input Input terminal 3 (ST) :  : 2 Input terminal 4 (RES) : ...
  • Page 221: Display Of Detailed Information On A Past Trip

    E6581445 8.2.2 Display of detailed information on a past trip Details on a past trip (of trips 1 to 4) can be displayed, as shown in the table below, by pressing the key when the trip record is selected in the status monitor mode. Unlike the "...
  • Page 222: Changing Status Monitor Function

    E6581445 Changing status monitor function Changing the display format while power is on The item displayed in the standard monitor mode (*1 on the left side of table on page H-2), for example, operation frequency which is displayed by default in this way: “=” when power is on or “” when power is off, can be changed to any item shown on page H-7.
  • Page 223 E6581445 [Setup values of monitor indication parameters (~)] Communication Default Unit Item displayed Marking Unit (Panel) setting (Communication) FD00 Output frequency Depends on  0.01Hz   FE02 Frequency command value Depends on  0.01Hz   FE03  Output current ...
  • Page 224: Display Of Trip Information

    E6581445 Display of trip information 8.4.1 Trip code display If the inverter trips, an error code is displayed to suggest the cause. In the status monitor mode, the status when the inverter trip is held. Display of trip information Communication/Error code Error code Description Communication No.:FC90...
  • Page 225 E6581445 (Continued) Communication/Error code Error code Description Communication No.:FC90 Speed error (Over speed)  Terminal input error  Abnormal CPU2 communication  V/f control error  CPU1 fault   Abnormal logic input voltage Option 1 error   Option 2 error Stop position retaining error ...
  • Page 226: Monitor Display At Tripping

    E6581445 8.4.2 Monitor display at tripping At the occurrence of a trip, the same information as that displayed in the mode described in 8.2.1, “Status monitor under normal conditions,” can be displayed, as shown in the table below, if the inverter is not turned off or reset. To display trip information after turning off or resetting the inverter, follow the steps described in 8.2.2, “Display of detailed information a past trip.”...
  • Page 227 E6581445 (Continued) Commun ication Item displayed Description operated display  ⇔  FE10 Past trip 1 Past trip 1 (displayed alternately at 0.5-sec. intervals) [Note 7]  ⇔  Past trip 2 (displayed alternately at 0.5-sec. intervals) FE11 Past trip 2 [Note 7] ...
  • Page 228: Display Of Alarm, Pre-Alarm, Etc

    E6581445 Display of alarm, pre-alarm, etc. When the inverter alarm, pre-alarm, etc. occurred, the contents are displayed. (Some are not displayed.) Listed below ones can be monitored via communication (FC91). Refer to 13.1 for the other alarms. Description Panel indication Overcurrent pre-alarm ...
  • Page 229: Taking Measures To Satisfy The Ce/Ul/Csa Standards

    Inverters themselves are not subject to approval for CE marking. The CE mark must be put on every final product that includes an inverter(s) and a motor(s). The VF-AS1 series of inverters complies with the EMC directive if an EMC filter recommended by Toshiba is connected to it and wiring is carried out correctly.
  • Page 230: Measures To Satisfy The Emc Directive

    E6581445 9.1.2 Measures to satisfy the EMC directive Concrete measures for EMC directive of CE markings are shown below. Models with a built-in EMC filter (1) 200V class: VFAS1-2004PL~2075PL 400V class: VFAS1-4007PL~4500KPC The above mentioned models install EMC noise filter inside. So the conducted and radiated noise can be reduced, optional EMC noise filters are not needed.
  • Page 231 E6581445 (2) Use shielded power cables and control signal cables for the input and output lines of the inverter. Route the cables and wires so as to minimize their lengths. Keep a distance between the power cable and the control cable and between the input and output wires of the power cable.
  • Page 232 E6581445 When an external EMC filter is added (1) Additional external EMC filters have the further effect of suppressing conduction and radiation noises. Use the recommended EMC noise filter specified in Table 3. This combination of inverter and filter was used when examining the inverter for compliance with the EMC directive.
  • Page 233 E6581445 (Continued) Requirements Conducted noise Conducted noise PWM carrier Length of motor IEC61800-3 category C2 IEC61800-3 category C1 Inverter type frequency  connecting cable (EN55011 classA Group1) (EN55011 classB Group1) (kHz) Applicable filters Applicable filters VW3A4406 VW3A4406 3.5~4 VW3A4406 VFAS1-4220PL VW3A4406 VW3A4406 4.1~12...
  • Page 234 E6581445 [Ex. Countermeasure - inverter wiring] Strip and earth the shielded cable, following the example shown in Fig. Peel off the outer sheath of the cable and fix the shielded part with a metal saddle. EMC plate (Refer to Table 2.) PG feedback signal line (Shielded cabless) Control wiring (Shielded cabless) Relay contact output FLA, FLB, FLC...
  • Page 235: Low-Voltage Directive

    Type : NF series 9.1.3 Low-voltage directive The low-voltage directive provides for the safety of machines and systems. All Toshiba inverters are CE-marked in accordance with the standard IEC61800-5-1 specified by the low-voltage directive, and can therefore be installed in machines or systems and imported without a problem to European countries.
  • Page 236: Measures To Be Taken To Satisfy The Ul/Csa Standards

    Fig. 4 Measures to be taken to satisfy the UL/CSA standards All VF-AS1 series inverters are certified by UL and CSA, and have nameplates with UL and CSA markings. 9.2.1 Caution in installing the inverter A UL certificate was granted on the assumption that the inverter would be installed in a cabinet. Therefore, install the inverter in a cabinet and if necessary, take measures to maintain the ambient temperature (temperature in the cabinet) within the specified temperature range.
  • Page 237: Caution As To The Protection Of Motors From Overload

    E6581445 Table 5 AIC, Fuse and Wire sizes Applicable AIC (A) Fuse class Input wire sizes of Output wire sizes of Voltage Earth motor Inverter model output current (Interrupting and current power circuit power circuit class [kW] (A) *1, *2 capacity) VFAS1-2004PL 2.5 (=)
  • Page 238: Selection Of Peripheral Devices

    E6581445 10. Selection of peripheral devices Danger • When using the inverter without the front cover, be sure to place the inverter unit inside a cabinet. If they are used outside the cabinet, it may cause electric shock. Mandatory • Be sure to ground every unit. If not, it may cause electric shock or fire on the occasion of failure, short-circuit or electric leak.
  • Page 239 LC1F780J (*1): Type forms of TOSHIBA INDUSTRIAL PRODUCTS SALES CORPORATION. (*2): Selections for use of the Toshiba 4-pole standard motor with power supply voltage of 200V/400V-50Hz. (*3): Choose the MCCB according to the power supply capacity. For comply with UL and CSA standard, use the fuse certified by UL and CSA.
  • Page 240: Installation Of A Magnetic Contactor

    When operating multiple motors at a time, be sure to install an overload relay for each individual motor. When using the VF-AS1 inverter to operate a constant-torque motor, such as the Toshiba VF motor, adjust the protection characteristic of the electronic thermal protection unit () to the VF motor use.
  • Page 241: Application And Functions Of Options

    E6581445 10.4 Application and functions of options Separate type options shown below are prepared for the inverter VF-AS1 (6) Braking unit (2) DC reactor (200kW models and larger) (3) High attention radio (DCL) noise filter (4) Zero-phase reactor ferrite core type radio...
  • Page 242 Note) Set the carrier frequency to 4.0~8.0kHz or larger when sine wave filter is used. Control power supply The VF-AS1 supplies control power from the main circuit power supply in it. The optional backup option backup unit is designed to supply control power in the event the main circuit power supply shuts down.
  • Page 243 E6581445 Selection table of separate-type options (1/2) Input filter Dynamic Control Applicable High brake drive Voltage Inverter DC reactor power motor circuit EMC filter attenuation Zero-phase Capacitive class model (DCL) supply [kW] (*1) radio noise core filter (GTR7) backup (*2) filter VFAS1-2004PL Built-in...
  • Page 244 E6581445 Selection table of separate-type options (2/2) EMC Diredctive Motor end compliant noise reduction Appli Motor Control Input AC DC reactor surge voltage filter Voltage -cable Inverter Braking resistor noise power reactor (DCL) suppression class motor model (*2) reduction supply High Core (ACL)
  • Page 245: Optional Internal Devices

    E6581445 Optional internal devices 10.5 Here are the internal devices optionally available. There are two types of optional devices: Add-on type and Plug-in type. Table of optional devices Type of Option name Function, purpose Model installation (1) Expansion I/O card1 option ETB003Z Add-on (Logic input/output + PTC input)
  • Page 246 E6581445 (2) Expansion I/O card2 option (Function of optional card 1 + Analogue input/output + Pulse input) Function Description Multifunction programmable contact No-voltage contact input (24Vdc-5mA or less) input (4 points) Sink logic input (at a common voltage of 24V) Source logic input ON: Less than 10Vdc ON: 11Vdc or more...
  • Page 247 E6581445 How to install Add-on type devices and insertion type devices are installed in different ways. Install them correctly, as shown in the figures below. Add-on type Plug-in type Up to two Add-on type devices and one Plug-in type device can be installed at the same time. Note, however, that two identical optional devices and two identical optional communication devices cannot be connected and used.
  • Page 248: Connection Of A Dc Power Supply And Other Electric Units

    E6581445 10.6 Connection of a DC power supply and other electric units Besides a three-phase commercial power supply, a single-phase 200V power supply (5.5kW or less) and a DC power supply can be connected to the VFAS1 inverter. When connecting each of these units, keep in mind the points described in the following sections. 10.6.1 Connection of a single-phase 200V power supply The table below shows which model to select when operating a three-phase induction motor, using a single-phase 200V power supply (200-240V, 50/60Hz).
  • Page 249: Table Of Parameters

    11. Table of parameters 1. Basic parameter [1/4] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Reference Speed Torque setting running control (Panel/Communi control control cation) History function ●/●...
  • Page 250 1. Basic parameter [2/4] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque Reference (Panel/Communi setting running control control control cation) 0:Constant torque characteristics ● 1:Voltage decrease curve ●...
  • Page 251 1. Basic parameter [3/4] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque Reference (Panel/Communi setting running control control control cation) Motor electronic thermal  0600 10~100% Enabled ●/●...
  • Page 252 1. Basic parameter [4/4] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque Reference (Panel/Communi setting running control control control cation) 0: - 1:50 Hz default setting 2:60 Hz default setting 3:Factory default setting 4:Trip clear...
  • Page 253 2. Extended parameters [1] Frequency signal Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque Reference (Panel/Communi setting running control control control cation) Low-speed signal output  0100 0.0~...
  • Page 254 [3] Terminal function selection Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque Reference (Panel/Communi setting running control control control cation)  0110 Always ON function selection 1 0~135 *1 Disabled ●/●...
  • Page 255 [4] Terminal response time setup Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque Reference (Panel/Communi setting running control control control cation) Input terminal 1 response time ...
  • Page 256 [5] V/f 5-point setting Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque Reference (Panel/Communi setting running control control control cation) V/f 5-point setting VF1 0190 0.0~ Hz 0.1/0.01 Disabled ●...
  • Page 257 [6] Speed/torque reference gain/bias setup [2/2] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Reference Speed Torque (Panel/Communi setting running control control control cation)  0212 RR/S4 input point 2 setting 0~100% Enabled ●/●...
  • Page 258 [7] Operation frequency Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque Reference (Panel/Communi setting running control control control cation)  0240 Starting frequency setting 0.0~10.0Hz 0.1/0.01 Enabled ●/●...
  • Page 259 [10] Jump frequency Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque Reference (Panel/Communi setting running control control control cation)  0270 Jump frequency 1 0.0~ Hz 0.1/0.01 Enabled ●/●...
  • Page 260 [12] Tripless intensification setup [2/2] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque Reference (Panel/Communi setting running control control control cation) 0:Disabled 0304 Dynamic braking selection 1:Enabled (braking resistance overload detect) Disabled ●/●...
  • Page 261 [14] Functions for lift [1/2] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque Reference (Panel/Communi setting running control control control cation) 0324 Drooping output filter 0.1~200.0 rad/s (Enabled if =3, 4, 7 or 8) 0.1/0.1 100.0 Enabled...
  • Page 262 [14] Functions for lift [2/2] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque Reference (Panel/Communi setting running control control control cation) Acceleration/deceleration  0349 0:Disabled, 1:Parameter setting, 2:Terminal input Disabled ●/●...
  • Page 263 [16] PID control [2/2] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque Reference (Panel/Communi setting running control control control cation)  0363 Integral (I) gain 0.01~100.0 0.01/0.01 0.10 Enabled...
  • Page 264 [18] Motor constant [2/2] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation)  0401 Slip frequency gain 0~150% Enabled ●/-...
  • Page 265 [19] Torque control [2/2] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) 0:Disabled 1:VI/II (voltage/current input) Forward speed limit input 0425 2:RR/S4 (potentiometer/voltage input)
  • Page 266 [20] Torque limit [2/2] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) Regenerative braking torque 0443 0.0~249.9%, 250.0:Disabled 0.1/0.01 250.0...
  • Page 267 [21] Adjustment parameters [2/2] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation)  0475 RX input gain 0~255 Enabled ●/●...
  • Page 268 [22] Acceleration/deceleration 2 [2/2] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation)  0514 Acceleration time 4 0.1~6000 sec.
  • Page 269 [23] Pattern operation [2/3] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) 0.1~6000 (The unit depends on the setting of ...
  • Page 270 [23] Pattern operation [3/3] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) Preset speed operation frequency 0570 Ditto Disabled...
  • Page 271 [24] Protection functions [2/3] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) 0:Each time (standard pulse) 1:Only one time after power is turned on 2:Each time (short pulse) Selection of short circuit...
  • Page 272 [24] Protection functions [3/3] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) 0:Deselect 0637 PTC1 thermal selection Disabled ●/●...
  • Page 273 [26] Meter output Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range V/f Constant Reference Speed Torque (Panel/Communi setting running control control control cation)  0671 AM terminal meter adjustment Enabled ●/●...
  • Page 274 [27] Operation panel parameters [1/3] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) Parameter write protect 0:Permit 0700 Enabled...
  • Page 275 [27] Operation panel parameters [2/3] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) Operation panel emergency stop 0:Permit ...
  • Page 276 [27] Operation panel parameters [3/3] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) 0757 Quick registration parameter 7 0~999 *1 Enabled ●/●...
  • Page 277 6. 39. 1 goes wrong with the master) wire RS485) 3:Master (sends a frequency command) 4:Master (sends an output frequency) 5.Master (sends a torque command) 6.Master (sends an output torque command) Protocol selection (2-wire 0:TOSHIBA  0807 Enabled ●/● ●/● ● ●...
  • Page 278 RS485) 3:Master (sends a frequency command) 4:Master (sends an output frequency) 5:Master (sends a torque command) 6:Master (sends an output torque command) Protocol selection (4-wire 0:TOSHIBA 0829 Enabled ●/● ●/● ● ● 6. 39. 1 ...
  • Page 279 [28] Communication function [3/4] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) Communication option (DeviceNet/  0845 0000~...
  • Page 280 [28] Communication function [4/4] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) 0:Deselect 1:Status information 2:Output frequency 3:Output current 4:Output voltage 5:Alarm information...
  • Page 281 [29] My function [1/5] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) Input terminal function number 0:Deselect 1:F terminal 2:R terminal...
  • Page 282 [29] My function [2/5] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) 0:NOP (not operation) 1:ST (move) 2:STN 3:AND (logical product) 4:ANDN...
  • Page 283 [29] My function [3/5] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi Default Write during setting unit Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation)  0915 Input function command 33 Same as ...
  • Page 284 [29] My function [4/5] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation)  0948 Input function command 62 Same as ...
  • Page 285 [29] My function [5/5] Sensorless vector/vector with sensor (●:Effective, -:Ineffective) Minimum Vector control Communi setting unit Default Write during Title cation Function Adjustment range Speed Torque V/f Constant Reference (Panel/Communi setting running control control control cation) 0:Disabled 1:VI/II 2:RR/S4 0962 Analog input function target 21 Enabled ●/●...
  • Page 286 [Contents of monitor displays] Sensorless vector/vector with sensor (●: valid, -: invalid) Unit Meter Communi Monitor output Trip Speed Torque Function (Commun output PM control Reference cation No. selection retention control control ication) selection  Standard monitor FE00 Trip frequency monitor 0.01Hz when tripped when tripped...
  • Page 287 [Monitor FM/AM/pulse output function selection (1/2)] Sensorless vector/vector with sensor ●: valid, -: invalid) FM/AM/pulse output Monitor output Unit Speed Torque Function (Communicat Trip retention PM control Reference Communicati Communicati control control Option No. Option No. ion) on No. on No. FD00 FE00 Output frequency...
  • Page 288 [Monitor FM/AM/pulse output function selection (2/2)] Sensorless vector/vector with sensor (●: valid, -: invalid) FM/AM/pulse output Monitor output Unit Function (Communicat Trip retention Speed control Torque control PM control Reference Communicati Communicati Option No. Option No. ion) on No. on No. FE67 Attached to expansion I/O card 2 CPU version ×...
  • Page 289 [Input terminal function setting (1/2)] Sensorless vector/vector with sensor (●: valid, -: invalid) Positive Negative Speed Torque Function PM control = = Reference logic logic control control No function is assigned ●/● ●/● ● ● F: Forward run command ●/● ●/●...
  • Page 290 [Input terminal function setting (2/2)] Sensorless vector/vector with sensor (●: valid, -: invalid) Positive Negative Speed Torque Function PM control Reference = = logic logic control control Servo lock signal ●/● ● ● ● Simple positioning (positioning loop) ●/● ● ●...
  • Page 291 [Output terminal function setting (1/3)] Sensorless vector/vector with sensor (●: valid, -: invalid) Positive Negative Function Speed control Torque control PM control Reference logic logic ●/● ●/● ● ● ●/● ●/● ● ● ●/● ●/● ● ● ●/● Acceleration/deceleration completion ●...
  • Page 292 [Output terminal function setting (2/3)] Sensorless vector/vector with sensor (●: valid, -: invalid) Positive Negative Function Speed control Torque control PM control Reference logic logic ●/● ●/● Inverter healthy output ● ● RS485 communication error ●/● ●/● ● ● Error code output 1 (6-bit output) ●/●...
  • Page 293 [Output terminal function setting 3/3] Sensorless vector/vector with sensor (●: valid, -: invalid) Positive Negative Function Speed control Torque control PM control Reference logic logic ●/● ●/● My function output 10 ● ● My function output 11 ●/● ●/● ● ●...
  • Page 294 Standard default settings classified by inverter model (capacity) Torque Base Acc/dec boost frequency Allowable Motor Motor Motor Display unit time Dynamic Inverter side Motor rated Motor  voltage PWM Carrier continuous Motor rated Motor rated constant 1 constant 2 constant 3 selection for /...
  • Page 295: Specifications

    E6581445 12. Specifications 12.1 Models and their standard specifications 1) Standard specifications (small/medium capacity types) Item Specification Voltage class 200V class Applicable motor (kW) 0.75 18.5 Applicable motor (HP) Type VFAS1- Form 2004PL 2007PL 2015PL 2022PL 2037PL 2055PL 2075PL 2110PM 2150PM 2185PM 2220PM 2300PM 2370PM 2450PM Output capacity (kVA) [Note 1] Output current...
  • Page 296 E6581445 2) Standard specifications (large capacity types) [Note 1] Item Specification Voltage class 200V class Applicable motor (kW) Applicable motor (HP) Type VFAS1- Form 2550P 2750P Output capacity (kVA) [Note 2] Output current Output voltage Three-phase 200V~240V (The maximum output voltage is equal to the input supply voltage.) Overload 150%-1 minute, 165%-2 sec.
  • Page 297 E6581445 3) Common specification Item Specification Control system Sinusoidal PWM control Output voltage adjustment Main circuit voltage feedback control. (Switchable between automatic adjustment/fix/control off) Setting between 0.01 to 500Hz. Default max. frequency is set to 0.01 to 60Hz. Output frequency range Maximum frequency adjustment (30 to 500Hz) Minimum setting steps of 0.01Hz: operation panel input (60Hz base),...
  • Page 298 E6581445 (Continued) Item Specification Stall prevention during operation, overload limit, overload, undervoltage on power source side, DC circuit Alarms undervoltage, setting error, in retry, upper limit, lower limit. Overcurrent, overvoltage, fin overheat, short circuit on the load side, ground fault on the load side, inverter overload, arm overcurrent at starting, overcurrent on the load side at starting, EEPROM error, RAM error, Causes of ROM error, transmission error, (dynamic braking resistor overcurrent/overload), (emergency stop),...
  • Page 299: Outside Dimensions And Weight

    E6581445 12.2 Outside dimensions and weight Outside dimensions and weight Applicable Applicable Dimensions (mm) Approx. Voltage motor motor Inverter type Drawing weight class (kW) (HP) (kg) VFAS1-2004PL 0.75 VFAS1-2007PL VFAS1-2015PL VFAS1-2022PL VFAS1-2037PL VFAS1-2055PL VFAS1-2075PL VFAS1-2110PM VFAS1-2150PM 200V 18.5 VFAS1-2185PM VFAS1-2220PM VFAS1-2300PM VFAS1-2370PM VFAS1-2450PM...
  • Page 300: Outline Drawing

    E6581445 Outline drawing (Instal l ation di m ension) (Installation dimension) Fig. A Fig. B (Installation dimension) (Installation dimension) Fig. C Fig.D (Installation dimension) (Installation dimension) Fig. E Fig. F...
  • Page 301 E6581445 (Installation dimension) (Installation dimension) Fig. G Fig. H (Installation dimension) (Instal l ation di m ension) Fig. I Fig. J...
  • Page 302 E6581445 (Installation dimension) (Installation dimension) Fig. K Fig. L (Installation dimension) (Installation dimension) Fig. M Fig. N...
  • Page 303 E6581445 Braking unit (optional) (Installation dimension) (Installation dimension) Fig. O Braking unit (optional) (Installation dimension) (Installation dimension) Fig. P...
  • Page 304: Trip Causes/Warnings And Remedies

    E6581445 13. Before making a service call - Trip information and remedies 13.1 Trip causes/warnings and remedies When a problem arises, diagnose it in accordance with the following table. If it is found that replacement of parts is required or the problem cannot be solved by any remedy described in the table, contact your supplier.
  • Page 305 E6581445 (Continued) Error Description Possible causes Remedies code •Rapid acceleration is operated. •Increase the acceleration time . •The DC braking amount is too •Reduce the DC braking amount  and the large. DC braking time . Inverter •The V/f setting is improper. •Check the V/f parameter setting.
  • Page 306 E6581445 (Continued) Error Description Possible causes Remedies code •Inverter is stopped by panel •Reset the inverter. operation during automatic or remote operation. Emergency stop  •A stop command (input terminal function:  or ) is issued by an external control device. •A data writing error occurs.
  • Page 307 E6581445 (Continued) Error Description Possible causes Remedies code Some items indicated on the motor •Make sure that all items on the motor nameplate nameplate are not entered correctly. are entered correctly. •Base frequency  Motor constant •Base frequency voltage 1  ...
  • Page 308 E6581445 [Alarm] The following are messages only. No trip is developed. Error Problem Possible causes Remedies code ST signal OFF •ST terminal is in open-circuit. •Close ST-CC circuit.  •The control voltage between +SU •Check whether the voltage between +SU and CC and CC terminals is too low.
  • Page 309 E6581445 (Continued) Error Problem Possible causes Remedies code •Braking operation is not performed •Brake signal output (, ) is not assigned to normally. the control output terminal. Brake sequence •The load is too heavy. •The brake function mode selection parameter ...
  • Page 310: Method Of Resetting Causes Of Trip

    E6581445 13.2 Method of resetting causes of trip Do not reset the inverter when tripped because of a failure or error before eliminating the cause. Resetting the tripped inverter before eliminating the problem causes it to trip again. For recovering inverter from trip status, (1) By turning off the power (Keep the inverter off until the LED turns off.) ⇒...
  • Page 311: If The Motor Does Not Run While No Trip Message Is Displayed

    E6581445 13.3 If the motor does not run while no trip message is displayed... If the motor does not run while no trip message is displayed, follow these steps to track down the cause. YES : The motor does not run. NO : Is power being Supply the power...
  • Page 312: How To Check Other Troubles

    E6581445 13.4 How to check other troubles The following table provides a listing of other troubles, their possible causes and remedies. Troubles Causes and remedies The motor runs in the wrong •Invert the phases of the output terminals U, V and W. direction.
  • Page 313: Inspection And Maintenance

    E6581445 14. Inspection and maintenance Danger • The equipment must be inspected every day. If the equipment is not inspected and maintained, errors and malfunctions may not be discovered which could lead to accidents. Mandatory • Before inspection, perform the following steps. (1) Shut off all input power to the inverter.
  • Page 314: Periodical Inspection

    E6581445 14.2 Periodical inspection Make a periodical inspection at intervals of 3 or 6 months depending on the operating conditions. Danger • Before inspection, perform the following steps. (1) Shut off all input power to the inverter. (2) Wait at least 15 minutes and check to make sure that the charge lamp is no longer lit. Mandatory (3) Use a tester that can measure DC voltages (800VDC or more), and check that the voltage to the DC main circuits (between PA/+ and PC/-) does not exceed 45V.
  • Page 315 E6581445 Replacement of expendable parts The inverter is composed of a large number of electronic parts including semiconductor devices. The following parts deteriorate with the passage of time because of their composition or physical properties. The use of aged or deteriorated parts leads to degradation in the performance or a breakdown of the inverter.
  • Page 316: Making A Call For Servicing

    14.3 Making a call for servicing For the Toshiba service network, refer to the back cover of this instruction manual. If defective conditions are encountered, please contact the Toshiba service section in charge via your Toshiba dealer. When making a call for servicing, please inform us of the contents of the rating label on the right panel of the inverter, the presence or absence of optional devices, etc., in addition to the details of the failure.
  • Page 317: Warranty

    • Failure or damage caused by the use of the inverter for any purpose or application other than the intended one 4. All expenses incurred by Toshiba for on-site services shall be charged to the customer, unless a service contract is signed beforehand between the customer and Toshiba, in which case the service contract has priority over this warranty.
  • Page 318: Disposal Of The Inverter

    E6581445 16. Disposal of the inverter Warning • For safety's sake, do not dispose of the disused inverter yourself but ask an industrial waste disposal agent (*). If the collection, transport and disposal of industrial waste is done by someone who is not Mandatory licensed for that job, it is a punishable violation of the law.
  • Page 319 The data given in this manual are subject to change without notice. 2006-10...

Table of Contents