(3) How to attach and detach the coil of linear expansion valve (A12, 18 )
<Composition>
Linear expansion valve is separable into the main body and the coil as shown in the diagram below.
Lead wire
<How to detach the coil>
Hold the lower part of the main body (shown as A) firmly so that
the main body does not move and detach the coil by pulling it
upward.
Be sure to detach the coil holding main body firmly. Otherwise
pipes can bend due to pressure.
<How to attach the coil>
Hold the lower part of the main body (shown as A) firmly so that
the main body does not move and attach the coil by inserting it
downward into the main body. Then securely attach the coil stop-
per to pipe B. (At this time, be careful that stress is not added to
lead wire and main body is not wound by lead wire.) If the stop-
per is not firmly attached to pipe B, coil may be detached from
the main body and that can cause defective operation of linear
expansion valve.
To prevent piping stress, be sure to attach the coil holding the
main body of linear expansion valve firmly. Otherwise pipe may
break.
Coil
Stopper
60
Main body
A
A
B
Be sure to attach the
stopper to pipe B.

Hide quick links: