Electric Dryers; Electrical Requirements - Kenmore 796.8128 Series Use & Care Manual

Hide thumbs Also See for 796.8128 Series:
Table of Contents

Advertisement

Available languages

Available languages

INSTALLATION INSTRUCTIONS

ELECTRIC DRYERS

ELECTRICAL REQUIREMENTS

WARNING:
electrical shock, serious injury, or death, the wiring
and grounding must conform to the latest edition of
the National Electrical Code, ANSI/NFPA 70 and all
applicable local regulations. Please contact a qualifi ed
electrician to check your home's wiring and fuses to
ensure that your home has adequate electrical power to
operate the dryer.
Special Electrical Requirements for Mobile
or Manufactured Homes
WARNING:
electric shock, or injury to persons when using this
appliance, follow basic precautions, including the
following:
• Any installation in a manufactured or mobile
home must comply with the Manufactured Home
Construction and Safety Standards Title 24 CFR, Part
3280 or Standard CAN/CSA Z240 MH and local codes
and ordinances.
• A 4-wire connection is required for all mobile and
manufactured home installations, as well as all new
construction after January 1, 1996. Failure to do so
can result in fi re, explosion, or death.
To help prevent fi re,
To reduce the risk of fi re,
Electrical Requirements for Electric Models Only
WARNING:
fi re, electric shock, or injury to persons when using this
appliance, follow basic precautions, including
the following:
• This dryer must be connected to a grounded metal,
permanent wiring system, or an equipment grounding
conductor must be run with the circuit conductors and
connected to the equipment grounding terminal or
lead on the dryer. Failure to do so can result in fi re,
explosion, or death.
• The dryer has its own terminal block that must be
connected to a separate 240 VAC, 60-Hertz, single
phase circuit, fused at 30 amperes (the circuit must be
fused on both sides of the line). ELECTRICAL SERVICE
FOR THE DRYER SHOULD BE OF THE MAXIMUM
RATE VOLTAGE LISTED ON THE NAMEPLATE. DO
NOT CONNECT DRYER TO 110-, 115-, OR 120-VOLT
CIRCUIT. Failure to follow these instructions can result
in fi re, explosion, or death.
• If branch circuit to dryer is 15 ft. (4.5 m) or less in
length, use UL (Underwriters Laboratories) listed No.-
10 AWG wire (copper wire only), or as required by
local codes. If over 15 ft. (4.50 m), use UL-listed No.-8
AWG wire (copper wire only), or as required by local
codes. Allow suffi cient slack in wiring so dryer can
be moved from its normal location when necessary.
Failure to do so can result in fi re, explosion, or death.
• The power cord (pigtail) connection between wall
receptacle and dryer terminal block IS NOT supplied
with the dryer. Type of pigtail and gauge of wire
must conform to local codes and with instructions on
the following pages. Failure to follow these instructions
can result in fi re, explosion, or death
• A 4-wire connection is required for all new
construction after January 1, 1996. A 4-wire
connection must be used where local codes do not
permit grounding through the neutral wire. Failure to
do so can result in fi re, explosion, or death.
12
To reduce the risk of

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

796.9128 series796.8118 series796.9118 series

Table of Contents