DATA

4-1. CORRECTING COOLING AND HEATING CAPACITY

4-1-1. Correcting Changes in Air Conditions
(1) The performance curve charts (Figure 4-1, 4-2, 4-3, 4-4) show the change ratio of capacity and input (power consumption)
according to the indoor and outdoor temperature condition when define the rated capacity (total capacity) and rated input
under the standard condition in standard piping length (5 m) as "1.0".
• Standard conditions:
• Use the rated capacity and rated power values given in the characteristics table for each indoor unit.
• The capacity is the single value on the side of the outdoor unit;
The capacity on the sides of each indoor unit must be added to obtain the total capacity.
(2) The capacity of each indoor unit may be obtained by multiplying the total capacity obtained in (1) by the ratio between the
individual capacity at the rated time and the total capacity at the rated time.
Individual capacity under stated conditions =Total capacity under the stated conditions o
(3) Capacity correction factor curve
Fig. 4-1
Cooling capacity
1.4
1.2
1
0.8
Indoor intake air wet-bulb temperature <:W.B.>
0.6
-5
0
5
10
Outdoor intake air dry-bulb temperature < D.B. >
Fig. 4-3
Heating capacity
Indoor intake air dry-bulb temperature <:D.B.>
Outdoor intake air wet-bulb temperature <:W.B.>
Note : These diagrams show the case where the operation frequency of a compressor is fixed.
OCH480A
Rated cooling capacity
Rated heating capacity
15
20
25
30
35
Indoor
D.B. 27 °C / W.B. 19 °C
Outdoor D.B. 35 °C
Indoor
D.B. 20 °C
Outdoor D.B. 7 °C / W.B. 6 °C
Fig. 4-2
Cooling input
1.2
1.0
0.8
22
20
18
0.6
16
0.4
-5
0
40
46
Outdoor intake air dry-bulb temperature < D.B. >
Fig. 4-4
Heating input
Outdoor intake air wet-bulb temperature <:W.B.>
13
Individual capacity at the rated time
Total capacity at the rated time
Indoor intake air wet-bulb temperature <:W.B.>
5
10
15
20
25
30
Indoor intake air dry-bulb temperature <:D.B.>
22
20
18
16
35
40
46