Circulating Supply Air And Return Air - Goodman GMN SERIES Installation & Operating Instructions Manual

Gas furnaces
Table of Contents

Advertisement

Check both manifold pressure (using the 1/8" NPT tap located on the gas valve) and service pressure (using the 1/8" NPT
tap as shown in the drawing above).
Capacity of gas pipe of different diameters and length in cu. ft. per hr. with pressure drop of 0.3 in. and specific gravity of
0.60 (natural gas). NOTE : COPPER TUBING MUST NOT BE USED FOR NATURAL GAS INSTALLATIONS.
Nominal Iron
Pipe Size, Inches
1/2
3/4
1
1 1/4
1 1/2
After the length of pipe has been determined, select the pipe size which will provide the minimum cubic feet per hour required
for the gas input rating of the furnace using the formula :
Cu. Ft.Per Hr. Required =
The gas input of the furnace is marked on the furnace rating plate. The heating calorific value of the gas (BTU/Ft
determined by consulting the local natural gas utility or the L.P. gas supplier.
If your local utility/ building codes permit the use of a flexible gas line ALWAYS USE A NEW LINE. DO NOT USE FLEXIBLE
GAS LINES WHICH HAVE PREVIOUSLY SERVICED ANOTHER APPLIANCE.
The circulating air return may be taken from:
(1) outside the building (2) return ducts from several rooms (3) central return (4) any combination of the above.
Note: When outside air is utilized, the system should be designed and adjusted such that the temperature of the air supply
to the furnace will not drop to below 50°F during the heating season.
When a combination of indoor and outside air is used (in conjunction with a mixing or diverting damper) the volume of air
must not be reduced.
Plenum chambers and air ducts must be installed in accordance with Standard for the Installation of Air Conditioning and
Ventilating Systems, NFPA No. 90A, or the Standard for the Installation of Warm Air Heating and Air Conditioning Systems,
NFPA No. 90B.
When the ducts are installed so that the supply ducts carry air circulated by the furnace to area outside the space containing
the furnace, the return air shall be handled by a duct or ducts sealed to the furnace casing and terminated outside the space
containing the furnace. If there is no complete return air duct system, the return air connection must be sealed to the furnace
casing and run full size to a location outside the utility room or space housing the furnace. The furnace must be installed
in a level and plumb position.
If installed in parallel with a cooling unit, the damper or other means used to control the flow of air must be adequate to prevent
GAS PIPE CAPACITY TABLE (CU. FT./HR)
10
20
132
92
278
190
520
350
1050
730
1600
1100
Gas Input of Furnace(BTU/HR)
Heating Value of Gas (BTU/HR)

CIRCULATING SUPPLY AIR AND RETURN AIR.

Length of Pipe, Feet
30
40
50
73
63
56
152
130
115
285
245
215
590
500
440
890
760
670
14
60
70
80
50
46
43
105
96
90
195
180
170
400
370
350
610
560
530
3
) may be

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents