Carrier 58MVP Installation, Start-Up, And Operating Instructions
Carrier 58MVP Installation, Start-Up, And Operating Instructions

Carrier 58MVP Installation, Start-Up, And Operating Instructions

Builder’s non-programmable thermostat

Advertisement

Visit www.carrier.com
Installation, Start-Up, and Operating Instructions
NOTE: Read the entire instruction manual before starting the
installation.
SAFETY CONSIDERATIONS
Read and follow manufacturer instructions carefully. Follow all
local electrical codes during installation. All wiring must conform
to local and national electrical codes. Improper wiring or installa-
tion may damage thermostat.
Recognize safety information. This is the safety-alert symbol
When you see this symbol on the equipment and in the instruction
manual, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAU-
TION. These words are used with the safety-alert symbol. DAN-
GER identifies the most serious hazards which will result in severe
personal injury or death. WARNING signifies a hazard which
could result in personal injury or death. CAUTION is used to
identify unsafe practices which would result in minor personal
injury or product and property damage.
INTRODUCTION
The Builder's Model thermostat is an electronic 24-vac, non-
programmable, manual changeover wall mount thermostat. This
thermostat uses a single set point to maintain and control room
temperature in both the heating and air conditioning modes. The
thermostat is designed to maintain +/- 2°F accuracy. No batteries
are required; temperature, fan, mode, and installer configuration
settings are preserved with power off.
INSTALLATION CONSIDERATIONS
AIR CONDITIONER MODEL
TSTATCCBAC01-B, the Builder's Model air conditioner thermo-
stat, may be wired with or without connecting a common wire
between the indoor equipment and the thermostat. However, it is
recommended to use a common wire whenever possible. Without
a common wire this thermostat becomes "power stealing." This
means it will need to steal a small amount of power from the
equipment to which it is connected. When "power stealing"
method is used, the supplied 270 ohm load resistor must be
connected at the indoor unit. (See Fig. 2, 3, 5, and notes.)
NOTE: Not all HVAC equipment is compatible with power
stealing type thermostats. For all non-Carrier equipment, consult
the system equipment Installation Instructions before applying this
thermostat in a power stealing manner.
HEAT PUMP MODEL
TSTATCCBHP01-B, the Builder's Model heat pump thermostat,
is compatible with all Carrier heat pump systems. It is NOT power
stealing and MUST have both the R and C terminals connected to
operate properly. This thermostat uses a green LED to indicate
auxiliary heat and emergency heat operation.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1
4
PC 101
Tab misc. misc.
Builder's Non-Programmable Thermostat
Catalog No. 03TS-TA16
Printed in U.S.A.
.
Fig. 1—Builder's Non-Programmable Thermostat
The following Carrier equipment is not compatible with the
AC version (TSTATCCBAC01-B) of this thermostat.
58MVP
58DFA, 58GFA
58PAP, 58RAP
58CLA, 58CMA
58EFB
TSTATXXCNV10
Step 1—Thermostat Location
Thermostat should be mounted:
• Approximately 5 ft (1.5m) from floor.
• Close to or in a frequently used room, preferably on an inside
partitioning wall.
• On a section of wall without pipes or duct work.
Thermostat should NOT be mounted:
• Close to a window, on an outside wall, or next to a door leading
to the outside.
• Exposed to direct light and heat from a lamp, sun, fireplace, or
other heat-radiating object which may cause a false reading.
• Close to or in direct airflow from supply registers and return-air
grilles.
• In areas with poor air circulation, such as behind a door or in
an alcove.
Form TSTAT-22SI
90% Variable Speed Furnace
78% Standing Pilot Furnace
Oil Furnaces
Gas Furnace
Thermostat Conversion Kit
INSTALLATION
Pg 1
8-99
Replaces: TSTAT-21SI
A98192

Advertisement

loading

Summary of Contents for Carrier 58MVP

  • Page 1 TSTATCCBHP01-B, the Builder’s Model heat pump thermostat, • Close to or in direct airflow from supply registers and return-air is compatible with all Carrier heat pump systems. It is NOT power grilles. stealing and MUST have both the R and C terminals connected to operate properly.
  • Page 2 Step 2—Install Thermostat TO ENTER THE CONFIGURATION MODE: Press and hold FAN button for approximately 10 sec until room temperature disappears and the display reads "01". You are now in configuration mode. Before installing thermostat, turn off all power to unit. There NOTE: If FAN button is pressed again, or if no button is pressed may be more than 1 disconnect.
  • Page 3 The numbers can range between -5 and +5. Factory default is 0. However, if the heating demand is greater than 5°, there will be AVAILABLE SELECTION: only a 3-minute delay before bringing on W. Use UP and DOWN buttons to now move between -5 and +5 in ERROR MESSAGES steps of 1.
  • Page 4 2. Power stealing method may not be used with the Two-Zone system. In addition, the supplied 270 ohm load resistor MUST always be connected between Y1 and C at Two-Zone input as shown. Copyright 1999 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231 tstt22si Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.