ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information
pack upon completion of work.
These instructions do not cover all variations in
systems nor provide for every possible contingency to
be met in connection with installation. All phases of
this installation must comply with NATIONAL, STATE
AND LOCAL CODES. Should further information be
desired or should particular problems arise which are not
covered sufficiently for the purchaser's purposes, the matter
should be referred to your installing dealer or local distributor.
A. GENERAL
The following instructions cover 2TWR1 and 2TWR2 Heat
Pump Units.
NOTE:
These outdoor units may be used with indoor units
equipped with Thermostatic Expansion Valve or Accutron™
Flow Control Check Valve (F.C.C.V.) assembly for refrigerant
flow control only.
Check for transportation damage after unit is uncrated.
Report promptly, to the carrier, any damage found to the unit.
To determine the electrical power requirements of the unit,
refer to the nameplate of the unit. The electrical power
available must agree with that listed on the nameplate.
®
The Weathertron
Heat Pump has been designed and
manufactured to withstand and operate in severe winter
conditions. However, there are precautionary steps which
should be taken at the time of installation which will help
assure the efficient operation of the unit. It is recom-
mended that these precautions be taken for units
being installed in areas where snow accumulation and
prolonged below freezing temperatures occur.
1. Units should be elevated 3 to 12 inches above the pad or
rooftop, depending on local weather. This additional
height will allow better drainage of snow and ice (melted
during defrost cycle) prior to its refreezing. This should
prevent a build-up of ice around the unit which occurs
when unit is not elevated. Insure that drain holes in
unit base pan are not obstructed preventing
draining of defrost water.
2. If possible, avoid locations that are likely to accumulate
snow drifts. If not possible, a snow drift barrier should be
installed around the unit to prevent a build-up of snow
on the sides of the unit and should be of sufficient
distance from the unit to prevent restriction of airflow to
and from the unit. Also allow for proper maintenance
space. The barrier should be constructed of materials
which will blend in with the building design.
Installer's Guide
Heat Pumps
2TWR1 & 2TWR2
1
3. Avoid locating the unit where condensation and freezing
of defrost vapor may annoy the customer. For instance,
installing the unit under a bedroom, kitchen, or picture
window may be annoying to the customer since conden-
sate and fog will occur during the defrost cycle.
4. Avoid locating the unit under the eaves or other over-
head structures as sizeable icicles may form and the unit
may be damaged by these falling icicles.
B. LOCATION AND PREPARATION
OF THE UNIT
1. When removing unit from the pallet, notice the tabs on
the basepan. Remove tabs by cutting with a sharp tool as
shown on page 2, Figure 2, and slide unit off of pallet.
2. The unit should be set on a level support pad at least as
large as the unit base pan, such as a concrete slab. If this
is not the application used please refer to application
bulletin "Trane APB2001-02".
3. The support pad must NOT be in direct contact with any
structure. Unit must be positioned a minimum of 12"
from any wall or surrounding shrubbery to insure
adequate airflow. Clearance must be provided in front of
control box (access panels) and any other side requiring
service access to meet National Electrical Code. Also, the
unit location must be far enough away from any struc-
2TWR2-IN-1B
18-BC51D2-3
5 FT. ABOVE UNIT-UNRESTRICTED

Advertisement

Table of Contents
loading

Summary of Contents for Trane 2TWR1

  • Page 1 A. GENERAL The following instructions cover 2TWR1 and 2TWR2 Heat Pump Units. NOTE: These outdoor units may be used with indoor units equipped with Thermostatic Expansion Valve or Accutron™...
  • Page 2: Installing Refrigerant Lines

    Installer’s Guide D. INSTALLING REFRIGERANT LINES BASEPAN TAB REMOVAL ▲ CAUTION If using existing refrigerant lines make certain that all joints are brazed, not soldered. Condensing units have provisions for braze connections. Pressure taps are provided on the service valves of outdoor unit for compressor suction and liquid pressures.
  • Page 3 Installer’s Guide GAS LINE SERVICE VALVE GAS LINE BALL SERVICE VALVE 1/4 TURN ONLY COUNTERCLOCKWISE FOR FULL OPEN POSITION VALVE STEM UNIT SIDE OF VALVE PRESSURE TAP PORT GAS LINE CONNECTION 6. Precautions should be taken to avoid heat damage to the pressure tap valve core during brazing.
  • Page 4: Electrical Connections

    Installer’s Guide 3. Attach center hose of manifold gauges to vacuum pump. 5. Provide flexible electrical conduit whenever vibration transmission may create a noise problem within the 4. Evacuate until the micron gauge reads no higher than structure. 350 microns. 6.
  • Page 5 Installer’s Guide I. OPERATIONAL AND CHECKOUT 3. FRC_DFT = Forced Defrost (Short TEST_COMMON to PROCEDURES this pin for two (2) seconds to initiate a forced defrost. Remove the short after defrost initiates.) Final phases of this installation are the unit Operational and Checkout Procedures which are found in this instruction on DEFROST CONTROL CHECKOUT page 8.
  • Page 6 Installer’s Guide 2TWR1 & 2TWR2 OUTLINE DRAWING Note: All dimensions are in MM (Inches). MODELS BASE FIG. 2TWR1018A 651 (25-5/8) 724 (28-1/2) 651 (25-5/8) 127 (5) 57 (2-1/4) 180 (7-1/8) 44 (1-3/4) 457 (18) 2TWR1024A 651 (25-5/8) 724 (28-1/2) 651 (25-5/8)
  • Page 7: Mounting Hole Location

    Installer’s Guide MOUNTING HOLE LOCATION Note: All dimensions are in MM (Inches). NOTE: For model base size, see table on page 6. From Dwg. 21D152637 Rev. 1 18-BC51D2-3...
  • Page 8: Checkout Procedure

    SV-UN-S/SP-2TWR2-IN-1B Supersedes 2TWR2-IN-1A Stocking Location PI Louisville & Webb/Mason-Houston Trane A business of Trane has a policy of continuous product and product data improvement and it reserves the right to change American Standard Companies www.trane.com design and specifications without notice.

This manual is also suitable for:

2twr22twa02twa2

Table of Contents