SECTION 6
Calibrating the Thermostat Sensors
Calibrating the Thermostat Sensors
Under normal circumstances it will not be necessary to adjust the
calibration of the temperature and humidity sensors. If calibration is
required, please contact a trained HVAC technician to correctly
perform the following procedure.
6
Place the thermostat in the
MODE
OFF mode.
Press and hold the MODE
MODE
button. While holding the
MODE button, press and hold
the FAN button for 5 seconds.
All icons will appear on the
FAN
display.
PRESS
THERMOSTAT SENSOR
Press the UP and DOWN buttons
at the same time twice. The
thermostat temperature will be
displayed and may be calibrated
using the UP or DOWN buttons.
TWICE
After calibration is complete, press the MODE button once to return to
normal operation.
I2:00
72
Pm
Su
OFF
I8:88
I88
Program On
Am
Pm
StartStop
Service Filter
AUTO
OFFON
Morning
DayNight
Evening
FanOn
Page 6.1
TOTALINE
88
Setup
C
OOL
Outside
A
88
H
UX
EAT
CALIBRATE