6 F 2 S 0 7 1 5
Enter the number corresponding to the timer to be observed. For the timers and related numbers,
refer to the "Timer List" attached to the relay instruction manual.
Click the [Test on] button to operate the timer. The timer is initiated and the input and output
signals of the timer can be observed at monitoring jacks A and B respectively.
Be sure to click the [Test off] button when the relay resumes service. If not, the relay may not
operate correctly. For safety, the "TESTING" LED lights in red on the front panel of the relay
while both of them are not reset.
Logic circuit test
It is possible to observe the binary signal level on the signals listed in "Signal List" with
monitoring jacks A and B. For the "Signal List", refer to the relay instruction manual.
Click the [Logic circuit] tab to open the screen.
Enter the signal numbers to be observed at monitoring jacks A and B.
Click the [Test on] button and the signals can be observed by the binary logic level at monitoring
jacks A and B or by the LEDs above the jacks.
Mode change
The condition of IEC61850 Test Mode is able to change on the Test screen. Between normal mode
and Test mode is switched by clicking the [IED Mode chg.] button. After completing change to
Test mode, the button is held down and "Test mode" is displayed in the status bar. (This function
is GR∗∗∗∗-∗∗∗D model and G1IF4 only.)