Mitsubishi Electric MIFH1 Installation Manual page 7

Controller kit
Hide thumbs

Advertisement

Installer setup tables
Setup function
134
Central Controller
(AG-150 or similar)
Present
136
Residential/Commercial
138
Permanent Hold Lock
(Non-programmable)
139
Fahrenheit/Celsius
Display
140
Commercial Override
Duration
142
System Type
144
System Changeover
145
System Changeover
Deadband Value
146
Drying Mode
148
Schedule Format
150
Optimal Start
152
Scheduled Off
154
Power Off Timer
("Sleep Timer")
160
Full Lockout
162
Lockout On/Off
164
Lockout System Mode
(Heat, Cool, Auto,
Drying)
165
Lockout Fan Mode
166
Lockout Setpoint
168
Lockout Set Clock/Day/
Schedule
170
Max Heat Setpoint
172
Min Cool Setpoint
173
Sensing Location
174
Indoor Temperature
Display Offset
Settings & options
0
Not Installed
1
Installed
1
Commercial
0
Residential
0
OFF (Programmable)
1
ON (Non-programmable)
0
Fahrenheit
1
Celsius
3
3 Hours
0
OFF
1–12
1–12 Hours
0
Heat & Cool (Heat Pump)
1
Cool Only
1
System Changeover (Auto, Heat, Off, Cool)
0
Manual Changeover (Heat, Off, Cool)
2
System Changeover Only (Auto Only)
3
System Changeover Single Setpoint - only with AG-150 or
similar (Auto, Heat, Off, Cool)
3
3 °F (2 °C)
2–8
2–8 °F (1.5–4.5 °C)
0
OFF
1
ON
0
5-2
1
5-1-1
1
ON
0
OFF
0
Not Shown
1
Shown
0
Not Shown
1
Resume operation at next scheduled period
2
Permanently Off until user changes System mode
0
No
1
Yes
0
No
1
Yes
0
No
1
Yes
0
No
1
Yes
0
No
1
Yes
0
No
1
Yes
90
90 °F (32 °C)
40–89
40 to 89 °F (4.5 to 31.5 °C)
50
50 °F (10 °C)
51–99
51 to 99 °F (10.5 to 37 °C)
1
Sense at Remote Controller
0
Sense at Indoor Unit
0
0 °F (0 °C)
-3 to 3 °F (-1.5 to 1.5 °C)
7
(factory default in bold)
* See page 9 for feature information