Download  Print this page

Installer Setup Tables; Setup Function - Mitsubishi Electric MIFH1 Installation Manual

Controller kit
Hide thumbs

Advertisement

Wireless System Installation Guide

Installer setup tables

Default settings for Setup functions 101-128 are automatically determined by the HVAC
equipment. It may take up to 40 seconds to enter setup, and 30 seconds to exit setup.

Setup function

101
Unit automatically
restarts after power
outage
103
Ventilation Air
104
Power Voltage
105
Auto energy-savings
operation
107
Change Filter Duration
108
Auto Fan (speed setting) 1
109
No. of Air Outlets (PLA
only)
110
High Performance Filter
Installed
111
Airflow Direction
Settings
115
Indoor Unit Coil Frost
Prevention Temperature
117
Defrost Control
123
Airflow Oscillate Mode
124
Heating Mode
Temperature Offset
125
Thermal Off Fan
Operation (Heat Mode)
127
Thermal Off Fan
Operation (Cool Mode)
128
Display System Error
69-2426—01
Settings & options
1
OFF
2
ON
3
Not Supported
1
Not Supported
2
IDU does not intake outdoor air through LOSSNAY
3
IDU does intake outdoor air through LOSSNAY
1
230V
2
208V
3
Not Supported
1
ON
2
OFF
3
Not Supported
1
100 Hours
2
2500 Hours
3
OFF
Quiet
2
Standard
3
High Ceiling
1
4 directions
2
3 directions
3
2 directions
1
NO
2
YES
3
Not Supported
1
No Vanes (or Vane #3 for PLA)
2
Vane #1 Setting (typically kept at the default setting)
3
Vane #2 Setting (typically kept at the default setting)
1
36 °F (2 °C)
2
37 °F (3 °C)
3
Not Supported
1
Standard
2
High Humidity
3
Not Supported
1
Not Available
2
Available
3
Not Supported
1
ON
2
OFF
3
Not Supported
1
Extra Low
2
Stop
3
Selectable Fan Speed
1
Selectable Fan Speed
2
Stop
3
Not Supported
1
ON
2
OFF
3
Not Supported
6
(factory default in bold)

Hide quick links:

Advertisement

loading

  Related Manuals for Mitsubishi Electric MIFH1

This manual is also suitable for:

Mcch1Mrch1Mos1