Enclosure Installation

Air for combustion and ventilation must not be supplied from
the occupied spaces of the manufactured (mobile) home.
IMPORTANT: The opening that provides outside air to your
water heater must have a minimum free area of 20 square
inches. Also, ensure that your installation complies with all
applicable code requirements.
The following methods may be used to provide sufficient
combustion and ventilation air to the water heater when it is
installed in the enclosure.
Method I (Figure 15)
Provide a single air opening in the exterior door of the
enclosure. The opening must have a minimum free area of
20 square inches. The bottom of the opening must be within
6 inches from the bottom edge of the door. Cover the opening
with 1/4 inch wire mesh screen or louvers.
Method II (Figure 16)
For enclosures with a solid exterior door, provide an air opening
in the floor. The opening must have a minimum diameter of 5
inches (20 square inches minimum free area) and be covered
with 1/4-inch wire mesh screen.
Method I:
Door Opening
ROOF JACK
(NOT INCLUDED)
ROOF
CEILING
MAINTAIN MIN. CEILING
CLEARANCE PER LABEL
ON WATER HEATER
MAINTAIN MIN.
CLEARANCE PER CODE
SECURE TOP
TO WALL WITH
STRAP AND
SCREWS
MAINTAIN MIN.
CLEARANCES
SECURE WATER HEATER
TO FLOOR WITH BRACKETS
AND SHEET METAL
SCREWS (PROVIDED)
FLOOR
* FREE AREA FOR AIR OPENING: 20 SQ. IN. MIN.
FIGURE 15.
Also, if the manufactured home is skirted, an air intake opening
with a minimum free area of 32 square inches must be provided
in the skirt. Other gas fired appliances in the home may require
additional free air openings. Consult the manufacturers for
correct sizing.
IMPORTANT:
When using Method II, ensure that the drain pan does not
cover the air intake opening in the floor.
A discharge line must be installed as described in the
"Temperature and Pressure Relief Valve" section.
Do not obstruct the combustion and ventilation air openings.
Do not use the enclosure as a storage area.
Secure the water heater as described in "Securing Water
Heater to Floor and Wall."
METAL
DRAIN PAN
ONE OPENING
IN DOOR *
PROTECTION:
1/4 IN. WIRE
MESH OR
OUTSIDE
LOUVERS
FRESH
AIR
6 INCHES MAX.
ABOVE BOTTOM
EDGE OF DOOR
20
Method II:
Floor Opening
ROOF JACK
(NOT INCLUDED)
ROOF
CEILING
MAINTAIN MIN. CEILING
CLEARANCE PER LABEL
ON WATER HEATER
MAINTAIN MIN.
CLEARANCE PER CODE
SECURE TOP
TO WALL WITH
STRAP AND
SCREWS
MAINTAIN MIN.
CLEARANCES
SECURE WATER HEATER
TO FLOOR WITH BRACKETS
AND SHEET METAL
SCREWS (PROVIDED)
AIR INTAKE
FLOOR
IMPORTANT: DRAIN PAN MUST
NOT BLOCK OR COVER AIR INTAKE
* FREE AREA FOR AIR OPENING: 20 SQ. IN. MIN.
FIGURE 16.
METAL
DRAIN PAN
FLOOR OPENING (5 IN. MIN. DIA.) *
1/4 IN. WIRE MESH PROTECTION