I Gnition C Ontrol - Amana GUI Installation Instructions Manual

Gas-fired warm air furnace
Table of Contents

Advertisement

Timing Chart for Integrated Ignition Control Normal Heating Operation
Circulator
Blower
OFF
OPEN
Gas Valve
CLOSED
Igniter
OFF
CLOSED
Pressure Switch
OPEN
Contacts
Induced Draft
OFF
Blower
Thermostat
OFF
SECONDS
NOTE: CUSTOM CONTROLS, INC. INTEGRATED CONTROL MODULE HAS A FIXED
STANDARD SEVEN-SECOND IGNITER WARM UP PERIOD
(MINI IGNITER).
WHITE-RODGERS 50A65 INTEGRATED CONTROL MODULE HAS A
20-SECOND IGNITER WARM UP PERIOD (SILICON NITRIDE).
Timing Chart for Integrated Ignition Control Normal Cooling Operation
Indoor Fan
Outdoor Fan
and
Compressor
Thermostat
Seconds
ON
ON
ON
ON
t
0
ign
IGNITER
WARM UP PERIOD
(see note)
WHITE-RODGERS 50A55 or 50T55 INTEGRATED CONTROL MODULE HAS A
VARIABLE STANDARD IGNITER WARM UP PERIOD BETWEEN
A 17-SECOND MAXIMUM AND A FIVE-SECOND MINIMUM.
ON
OFF
ON
OFF
ON
OFF
0
5
27
t
circ
FIXED HEAT
ON DELAY:
30 SECONDS
0
60,90,
0
15
120 or
180
45