6. INSTALLATION WORK

6.1A. Installation dimensions
(Ceiling concealed type)
Provide a service access for inspection purposes.
Do not place any wiring or illumination in the service space,
as they will impede service.
Installation Dimensions
Strong and durable ceiling
Indoor unit
Left
side
100 (3-15/16)
or more
20 (25/32) or more
20 (25/32) or more
Service access
Adjust the wind direction in the room depending on the
shape of blow out opening.
Unit
Service space
unit: mm (in.)
Right
side
300 (11-13/16)
or more
300 (11-13/16) or more
Ceiling
Floor
Service access
Control
box
300 (11-13/16)
or more
6.1B. Installation dimensions (Wall mounted
type/Floor standing concealed type)
The wall mounted type/floor standing concealed type
requires a temperature correction setting. Perform this in
"10.3. Function setting".
10 (13/32)
10 (13/32)
or less
or less
Left side
150 (5-29/32)
or more
Strong and
100 (3-15/16)
durable floor
or more
Left side
150 (5-29/32)
or more
Strong and
100 (3-15/16)
durable floor
or more
6.2A. Installation the unit
(Ceiling concealed type)
WARNING
Install the air conditioner in a location which can withstand a
load do at least 5 times the weight of the main unit and which
will not amplify sound or vibration. If the installation location is
not strong enough, the indoor unit may fall and cause injuries.
If the job is done with the panel frame only, there is a risk that
the unit will come loose. Please take care.
6.2A.1. UNIT INSTALLATION EXAMPLE (CEILING
CONCEALED TYPE)
Connect the locally purchased duct.
(1) Inlet side
• Connect the duct to the locally purchased inlet flange.
• Connect the flange to the body with the locally purchased
tapping screws.
• Wind the inlet flange connecting to the duct with the
aluminum tape etc. to avoid the air discharge.
CAUTION
When the duct is connected to inlet side, remove contained
filter and surely attach locally purchased filter at inlet opening.
(2) Outlet side
• Connect the duct with adjusting inside of outlet flange.
• Wind the outlet flange connecting to the duct with the
aluminum tape etc. to avoid the air discharge.
• Insulate the duct to avoid the dew condensation.
unit: mm (in.)
Right side
(PIPE side)
Grill
Inlet air
Strong and
durable floor
300 (11-13/16)
20 (25/32)
20 (25/32)
or more
or more
or more
Right side
(PIPE side)
Grill
Inlet air
Strong and
durable floor
300 (11-13/16)
20 (25/32)
20 (25/32)
or more
or more
or more
150 (5-29/32)
or more
Duct
150 (5-29/32)
or more
En-7