Chapter 5 System Settings and Display
5.3 System Settings > set power-synchronization
-shutdown-time
-preset
-power-fail-signal
-low-battery-signal
-ups-shutdown-signal
-ups-shutdown
Optional. This parameter specifies the time in minutes between when a power outage signal is
received and when a system shutdown begins. If omitted, the existing setting is not changed.
Any value between 0 and 15 can be specified.
shutdown_time
Time in minutes between when a power outage signal is received and when a
system shutdown begins (0 – 15)
Optional. This parameter specifies the preset values for the power synchronization interface. If
this parameter is specified, the following "-power-fail-signal" and "-low-battery-signal"
parameters cannot be specified. If omitted, the existing setting is not changed. The initial
value is set to "pman".
power-sync Power synchronized unit. If this operand is specified, "-power-fail-signal" is
assigned as positive and "-low-battery-signal" is assigned as negative.
pman
PMAN (Default). If this operand is specified, "-power-fail-signal" is assigned as
positive and "-low-battery-signal" is assigned as positive.
manual
Manual setting. For this setting, "-power-fail-signal" and "-low-battery-signal"
must be specified at the same time.
Optional. This parameter specifies the signal polarity of the power outage signal, which
indicates that the power supply has failed. If omitted, the existing setting is not changed. The
initial value is set to "positive". This can be set when "-preset manual" is specified.
positive
Positive is set. (Default)
negative
Negative is set.
Optional. This parameter specifies the signal polarity of the low battery voltage signal, which
indicates that battery power is nearly exhausted. If omitted, the existing setting is not
changed. The initial value is set to "positive". This can be set when "-preset manual" is
specified.
positive
Positive is set. (Default)
negative
Negative is set.
Optional. This parameter specifies the signal polarity of the UPS stop signal when completing
shutdown. If omitted, the existing setting is not changed. The initial value is set to "negative".
positive
Positive is set.
negative
Negative is set. (Default)
Optional. This parameter specifies whether the UPS stop signal output is issued after
completing shutdown. If omitted, the existing setting is not changed. The initial value is set to
"disable".
enable
Enabled.
disable
Disabled. (Default)
ETERNUS CLI User's Guide
Copyright 2014 FUJITSU LIMITED
621
P2X0-1210-05ENZ0