Download  Print this page

Remote Condenser Assembly Models - HP A0554832 User Manual

2–40 hp portable chillers
Hide thumbs

Advertisement

Remote Condenser Assembly Models

To convert inches to cm, multiply dimension by 2.54.
Fan(s)
Each
HP Dia.
Motor
Amps
in.
hp
5
26
3/4 hp 1 ø
7.5
26
1 /3 hp 3 ø
10
26
1 /3 hp 3 ø
15
26
1 /3 hp 3 ø
20
30 1 1/2 hp 3 ø
25
30 1 1/2 hp 3 ø
30
30 1 1/2 hp 3 ø
35
30 1 1/2 hp 3 ø
40
30 1 1/2 hp 3 ø
ø represents electrical phase; all motors are 1,140 rpm. Multiply hp by 0.746 to convert to kW.
All first fan motors (Header Side) are ¾ hp (0.56 kW) single phase variable speed.
Multiply 460V amperages by 2.0 for 208-230V amperages.
Multiply 460 V amperages by 0.8 for 575 V amperages.
Refrigeration charge is for remote condenser only!
To convert cfm to cmh, multiply by 1.699. To convert lbs. to Kg, multiply by 0.454.
See drawing above.
2-40 HP Portable Chillers
Totals
Air
Net
flow
wt.
460V Fans cfm
lbs.
2.4
1
6,450 260
3.7
2
12,400 470
3.7
2
13,700 510
5.0
3
20,500 550
5.9
2
23,000 840
5.9
2
21,900 860
9.4
3
34,800 1,280
9.4
3
32,900 1,300
12.9
4
46,400 1,690
Chapter 7: Appendix
Remote Condenser
Overall Dimensions
Length Width Height
'A'(in.) 'B'(in) 'C'(in.) 'D'(in)
49.8
43.0
40.5
69.8
43.0
40.5
89.8
43.0
40.5
129.8
43.0
40.5
125.0
45.5
50.0
125.0
45.5
50.0
180.0
45.5
50.0
180.0
45.5
50.0
235.0
45.5
50.0
Refrigeration
Connections
Mtg.
Discharge
Liquid
ODS(in.) ODS(in.) lbs.
40.0
1 1 /8
7 /8
60.0
1 1 /8
7 /8
80.0
1 3 /8
1 1 /8
120.0
1 5 /8
1 1 /8
108.0
1 5 /8
1 5 /8
108.0
1 5 /8
1 5 /8
2 1 /8
2 1 /8
2 1 /8
2 1 /8
2 1 /8
2 1 /8
57 of 78
Charge
R-22
3.6
3.6
4.6
6.4
10.0
16.0
24.0
24.0
29.0

Advertisement