10 hp and 15 hp Water-Cooled Portable Chillers

Nominal operating parameters for water-cooled models are 50ºF (10ºC) leaving water temperature at 2.4 gpm per ton
(9.1 lpm per 3.517 kW) with 85ºF (29ºC) tower water. For 50 Hz applications, multiply capacity by 0.83. Nominal 60
Hz capacity flow rate must be maintained.
Nominal cooling
capacity
HP
no
1
pump
pump
10
10.7
10.3
15
15.9
15.5
Based on 50ºF (10ºC) chilled water supply temperature and 85ºF (29ºC) tower water. Optional additional process
pump hp reduces chiller capacity by 0.2 tons per hp (0.703 kW ref. cap. per 0.746 kW pump power).
Based on 2.4 gpm per ton (9.1 lpm per 3.517 kW), nominal 1 pump.
Based on availability of 85ºF (29ºC) tower water at 25 psi (172.4 kPa/1.7 bars) minimum.
Based on availability of 70ºF (21ºC) city water at 25 psi (172.4 kPa/1.7 bars) minimum.
An optional oversized process pump adds to the total rated or running chiller amperage. To find the new total
chiller amperage, subtract the standard process pump amperage from the optional pump amperage (see Figure 1
on page 16), and add it to the chiller rated or running amperage.
Multiply 460/3/60 amperage by 2.0 for 208-230/3/60 amperages.
10 hp and 15 hp water-cooled chillers come standard with 4" (101 mm) swivel casters.
Com-
Process connections, in. NPT
pressor
1
2
hp
Pump pumps no tank
10.0
1.5"/3.0 2.0"/3.0
15.0
2.0"/3.0 2.5"/3.0
To convert to cm, multiply by 2.54. Add to height dimension based on mounting options.
Weight is for standard chiller. Some optional features will increase weight. Multiply by 0.454 to calculate Kg.
Operating weight is with a full 40-gallon (151 liter) reservoir tank of water.
2-40 HP Portable Chillers
Nominal Com-
tons
water pres- Nom. Water
2
flow
sor pump conn. Tower
pump gpm
hp
10.2
25.7
10.0
15.3
38.1
15.0
no pump, 1 pump, no
tank,
height
to/from
1.5"
1.5" / 2.0"
2.0"
2.0" / 3.0"
Chapter 7: Appendix
Condenser water
flow in gpm
City
hp in. NPT water
water
2.0
1.5"
32.2
16.1
2.0
2.0"
47.6
23.8
Dimensions
in inches
width
Depth
44.0"
34.0"
74.7"
44.0"
34.0"
74.7"
Power in amps
460/3/60
1 pump
2 pumps
rated running rated running
22.5
16.7
24.2
29.7
21.6
31.4
Weights
Dry
Ship.
Oper.
lbs.
lbs.
lbs.
950
1,175
1,282
1,024 1,249
1,365
51 of 78