Residential Control Systems Inc. Model TU16 UPB Thermostat INSTALLATION AND OPERATION MANUAL Rev P HVAC Control Unit DCN: 141-01435 Rev 01 8/30/06 This revision of the document applies to the following part numbers and revisions or later. Product Part No...
Page 2
It supports 3 stages of heating and 2 stages of cooling for Heat Pump systems. The TU16 has a convenient setup mode from the Wall Display Unit. You can set the network Unit ID, F or C display mode and easily calibrate the internal and all attached remote sensors.
TS16 Wall Display Unit The TS16 Wall Display Unit has a LCD display and control buttons for changing the setpoint, system operating mode and manual fan mode. The WDU also has an internal temperature sensor. The display serves as a common display for many functions. It normally shows the current room temperature but switches to show setpoint, mode or other functions when buttons are pushed.
Control Buttons Setpoint UP and DOWN Buttons The UP and DOWN buttons control the heating or cooling setpoint temperature. To View The Current Setpoint: Push either the UP or DOWN buttons once will cause the LCD display to change to show the current setpoint temperature (but won’t change it). To Change The Setpoint: With the setpoint displayed as above, push the UP button to increase the setpoint temperature by one degree or push the DOWN button to decrease the setpoint by one degree.
Setting the Fahrenheit or Celsius mode In the setup mode, press the mode button to select “FC” mode. The TU16 is default set to F mode. To change the degree mode, press the UP/DOWN buttons to select F or C as desired. To exit press mode again to move another setup mode or wait for the screen to time out and return to the normal thermostat temperature display.
You can view the outside temperature by pressing both the UP/DOWN buttons simultaneously. Display Lock The TU16 WDU control buttons can be locked to prevent unauthorized changes in system operation from the WDU. The display lock/unlock state can only be set by the “DL” network command. See the Serial Protocol Manual for details on this command.
UPB powerline network. The TU16 Control Unit connects to the HVAC system the same as, and in place of, a standard thermostat. It is usually mounted near the HVAC system, although it can be mounted anywhere convenient. It is connected to the WDU by a 4 wire cable, either standard thermostat wiring or typically Cat 3/5 in new construction.
Page 8
G, W1, W2 HEAT PUMP HVAC SYSTEM OPERATION The TU16 has Heat Pump operating modes of Heating, Cooling, Auto changeover and Emergency Heat. The Heat Pump HVAC system operation is the same as for Standard systems for normal first and second stage operations.
CO relay will already be on and this avoids continuous on/off cycling the CO valve for each call. After the MOT period expires and another call is not active, the CO output will go OFF. TU16 Control Unit HVAC System Outputs for Heat Pump Systems Operating Mode...
Page 10
UPB Thermostat Setup Program can set the network address, either directly or via a device setup mode. Unit ID The TU16 UPB Unit ID address can be set directly from the Wall Display Unit and also by the network configuration tool.
Page 11
For the complete UPB thermostat protocol, please refer to the RCS UPB Thermostat Protocol Manual, document number 150-00205. The TU16 has two UPB operation Modes, Link and Message. Link mode is a simple table of UPB Link addresses mapped to thermostat modes or setpoints. Message Mode is a more robust protocol of commands and messages designed for thermostats.
TU16 Installation STOP Before proceeding with removing an existing thermostat and installing the TU16, Read the following important steps. 1. Record existing wiring information on the enclosed wiring form. 2. Perform the TU16 bench test 3. Check WDU wiring BEFORE applying power to control unit.
Page 13
TU16 Wall Display Unit Installation WDU Location Choose a location that best represents the temperature of the area to be controlled. Avoid locations that are subject to drafts, from doors and windows, or areas with direct sunlight exposure. WDU Mounting Route the wires to the WDU through the access hole in the back of the case. Mount the WDU to the wall with the screws and anchors provided.
TU16 Control Unit Installation Location and Mounting Install the TU16 Control Unit in a protected, convenient, INDOOR location near the HVAC system or in a service accessible area such as an equipment closet or garage. Mount the Control Unit in a vertical position on a wall or sturdy structural member. The unit may be mounted on the HVAC system but care should be taken to avoid the hot burner section or high vibration fan areas.
Diagram 1 - Standard Gas or Electric System Wiring IMPORTANT! For typical central heating/cooling systems, leave jumper JP1 installed. If you have separate Heating TU16 Control Unit and Cooling system transformers, CUT JUMPER JP1. Wire RC to the Cooling system transformer and RH to the Heating system transformer.
Page 16
HVAC System Wiring Diagram 2 - Heat Pump System Wiring TU16 Control Unit FUSE IMPORTANT! Do not cut JP1 for Heat Pump Systems. RC and RH are common for Heat Pumps. OFF ON Heat Pump HVAC System Note: Set SW1-S1 to HP RC&RH...
Page 17
In this case there is a separate heating 24VAC transformer and a cooling 24VAC transformer. This type of a system requires that the TU16 Control Unit be connected using a separate heating system power input R terminal (RH) and a separate cooling system power input R terminal (RC). When connecting to these systems you must “split”...
System Checkout It is strongly recommended that you hook-up and run a simple bench test before installing the TU16. Not only will this save you time in system checkout but will also familiarize you with the thermostat’s operation. THERMOSTAT BENCH TEST 1.
(O) outputs. You must know what your system CO type is (CO with Cool (typical) or CO with Heat). You should have configured the TU16 control unit for correct CO type, refer to this setting. Heat Pump systems have an additional O terminal.
Page 20
TU16 Wiring Diagram TU16 CONTROL UNIT Fuse Mini ATO S2 2 2 Amp TS16 OFF ON WALL DISPLAY UNIT RH=RC Cut Jumper to split HVAC SYSTEM +12VDC +V 24V COM Blue STATUS THERMOSTAT CONNECTOR CLOCK 24V RH C - 24VAC Common...