Msx-A25Wv- Max. Refrigerant Piping Length & Max. Height Difference; Msx-A25Wv- Additional Refrigerant Charge (R410A:g); Msx-A25Wv- Piping Preparation - Mitsubishi Electric MSC-A07WV Service Manual

Split-type, air conditioners split-type, heat pump air conditioners
Hide thumbs Also See for MSC-A07WV:
Table of Contents

Advertisement

MSX-A25WV-
E1
MAX.REFRIGERANT PIPING LENGTH & MAX. HEIGHT DIFFERENCE
UNIT No.
Max.
limits
ADDITIONAL REFRIGERANT CHARGE (R410A:g)
A
unit
B
unit
PIPING PREPARATION
1Table below shows the specifications of pipes commercially available.
UNIT No.
For liquid
A
B
and
unit
For gas
2Ensure that the 2 refrigerant pipes are well insulated to prevent condensation.
3Refrigerant bending radius must be 10cm or more.
Indoor unit A
MSC-A12WV - E1
Outdoor unit
MUX-A25WV - E1
Pipe length
L
A
A
L
B
B
Outdoor unit
precharged
7m
950g
0
Outdoor unit
precharged
7m
950g
0
Outside diameter
Pipe
Indoor unit B
MSC-A12WV - E1
L
H
A
15m
15m
Refrigerant piping length (one way)
8m
9m
10m
20
40
60
Refrigerant piping length (one way)
8m
9m
10m
20
40
60
Insulation
thickness
mm
6.35
8mm
12.7
8mm
41
L
H
B
Height difference (H)
10m
10m
11m
12m
13m
80
100
120
11m
12m
13m
80
100
120
Insulation material
Heat resisting foam plastic
0.045 specific gravity
No. of bends
10
10
14m
15m
140
160
14m
15m
140
160