Hpflash Does Not Install Image.bin On A Pentium Iii; Initiate Battery Test Command Has Been Sent Message Not Displayed; Input Frequency Shows Zero; Installshield Error Code -6001 Appears During Setup - HP A1353A User Manual

Ups management module
Table of Contents

Advertisement

HPFlash does not install image.bin on a Pentium III

Symptom: The image.bin file is not installed on a Pentium III during a serial upgrade.
Possible Cause: The minimum hardware requirement for HPFlash is Pentium 4.
Action: Be sure that the hardware meets the minimum HPFlash requirements.
Initiate Battery Test Command Has Been Sent
message not displayed
Action: View the results of the battery test on the Application Log screen
56).

Input frequency shows zero

Symptom: During a battery test the input frequency shows zero, but the input frequency shows a regular
line voltage.
Possible Cause: When executing a battery test, the parameters might show incorrect information.
Action: Verify the parameters after the battery test is complete.

InstallShield error code -6001 appears during setup

Symptom: During installation or upgrade, the following error message appears:
Possible Cause: A previous installation of any product using InstallShield might have corrupted some of
the InstallShield runtime files.
Action: InstallShield installers copy DLL files to a local folder on your machine at C:\Program
Files\Common Files\InstallShield\Professional\RunTime\0701. Delete or rename the 0701 folder and
retry the installation. The installer recreates the 0701 folder and includes the necessary setup files.
For more information, search the InstallShield knowledge base (http://www.installshield.com/kb).
("Application Log
menu" on page
Troubleshooting 91