TEMPERATURE SENSOR TESTING
If Control has gone into lockout due to excessive tank
temperature (four flash, three second pause) reset
control by rotating gas control knob to "OFF" position
and wait a minimum of (5) minutes. Then follow lighting
instructions and return gas control knob to desired
setpoint.
Observe Green LED indicator.
Does error code 4 (four flash, three
second pause) continue?
Y
Temperature Sensor Testing
Following "Gas Control
Disassembly/Reassembly"
instructions, disassemble Gas
Control to access temperature
sensor.
With the temperature sensor still
in the back plate, use a multi-
meter set to the Ohms setting,
determine the resistance of
temperature sensor
(see caution and photos above)
Once the temperature sensor resistance values are known, the
water temperature must also be known to determine if the
resistance values are correct. See next page to obtain water
temperature.
Are temperature sensor resistance values correct?
Replace Gas Control
14
N
Using a multi-meter set to the ohms setting, insert one meter probe (see caution)
into center wire position of thermal well connector, insert the second probe (see
caution) into either of the outside wire positions (see photo on left).
Alternate the probe on the outside position to the opposite outside wire position
(see photo on right).
Resume normal operation.
Y
SERVICE PROCEDURE V

Gas Control

Testing, Disassembly & Replacement
CAUTION
DO NOT use standard multimeter probes for this test.
Doing so will damage connector. Use special pin type
electronic probes or small diameter wire pins inserted
into connector.
N
Replace temperature
sensor
14