Table 10
Fault Symptom Codes (continued)
FSC
Message
307A
Diag get drive 2 status failed
(Failed to get drive status, communication
error.)
307B
Diag get drive 3 status failed
(Failed to get drive status, communication
error.)
3082
Drive Stow Failed, Media Returned to
Source
3083
Drive Stow Failed, Media Remains in
Drive
ERP
Press the Enter button to reboot.
Ensure the drive shows good status
through the drive status window.
Deactivate the drive using the GUI control
panel maintenance menu.
Reseat drive.
Check cabling.
Load/unload a cartridge to the drive to
verify.
Check the tape cartridge used in the last
operation for damage.
Run the cartridge cycle diagnostic to
verify.
Press the Enter button to reboot.
Ensure the drive shows good status
through the drive status window.
Deactivate the drive using the GUI control
panel maintenance menu.
Reseat drive.
Check cabling.
Load/unload a cartridge to the drive to
verify.
Check the tape cartridge used in the last
operation for damage.
Run the cartridge cycle diagnostic to
verify.
Press the Enter button to clear the
message.
Use only media approved for the drive
type.
Invalid user initiated operation. Set
parameters correctly and try again.
Press the Enter button to clear the
message.
Invalid user initiated operation. Set
parameters correctly and try again.
Ensure cartridges are in magazines.