Connection of piping

1. Move the indoor tubing and drain hose to the hole
• Remove tubing holder and pull the tubing out of the chassis.
2. Replace the tubing holder into original position
3. Route the tubing and the drain hose staight backwards.
4. Insert the connecting cable into the indoor unit through the hole.
• Do not connect the cable to the indoor unit
• Make a small loop with the cable for easy connection later.
5. Tape the tubing and the connecting cable.
6. Indoor unit installation.
7. Connecting the pipings to the indoor unit.
PIPE SIZE
1/4"
3/8"
1/2"
5/8"
3/4"
• Align the center of the pipings and suffciently
tighten the flare nut with fingers.
• Finally, tighten the flare nut with troque
wrench until the wrench clicks.
When tightening the flare nut with troque
wrench, ensure the direction for tightening
follows the arrow on the wrench.

Precautions in bending

1. If it is necessary to bend or stretch the
tubing, use the spring which is attached to
the tubing in stead of pipe bender.
• Please make a careful notice to make a
smooth line.
• Hold the tubing with your two hands closely
and then bend or stretch it slowly not to
make any crack.
• Remember that the radius (R) should not
exceed 70mm (Refer to Fig. 1)
2. Do not repeat the bending process to prevent
the tubing from cracking or crushing.
3. Keep in mind that the bending part should
not be cracked and make the radius (R) as
long as possible (Refer to Fig. 2)
TORQUE
1.8~2.5 kgf·m
3.4~4.2 kgf·m
5.5~6.6 kgf·m
6.3~8.2 kgf·m
9.9~12.1 kgf·m
Indoor unit tubing
Spanner
Spring
(Fig. 1)
(Fig. 2)
Installation of Unit
Flare nut
Pipings
Torque wrench
R70mm
Installation Manual 13