CHECKING GAS CONNECTIONS

WARNING
: Test all gas piping and connections for leaks after installing or servicing. Correct all leaks immediately.
Pressure Testing Gas Supply Piping System
Test Pressures In Excess Of 1/2 PSIG(3.5kPa)
1. Disconnect heater with its appliance main gas valve (control valve) and equipment shutoff valve from gas supply
piping system. Pressures in excess of 1/2 psig will damage heater regulator.
2. Cap off open end of gas pipe where equipment shutoff valve was connected.
3. Pressurize supply piping system by either using compressed air or opening gas supply tank valve.
4. Check all joints of gas supply piping system. Apply mixture of liquid soap and water to gas joints. Bubbles
forming show a leak.
5. Correct all leaks immediately.
6. Reconnect heater and equipment shutoff valve to gas supply. Check reconnected fittings for leaks.
WARNING:
Never use an open flame to check for a leak. Apply a
mixture of liquid soap and water to all joints. Bubbles forming show a
leak. Correct all leaks immediately.
Pressure Testing Heater Gas Connections
1.
Open equipment shutoff valve (see Figure 15).
2.
Open gas supply tank valve.
3.
Make sure control knob of heater is in the OFF position.
4.
Check all joints from equipment shutoff valve to control valve.
Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.
5.
Correct all leaks immediately.
6.
Light heater (see Operating, page 17).Check all other internal joints for leaks.
7.
Turn off heater (see To Turn Off Gas to Appliance, P18).
CAUTION:
Make sure external regulator has been installed between gas supply and heater. See guidelines
under "Connecting to Gas Supply" (page 12).
Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1.
Close equipment shutoff valve (see Figure 15, page 14).
2.
Pressure supply piping system by either using compressed air or opening gas supply tank valve.
3. Check all joints from gas meter to equipment shutoff valve (see Figure 15).
4. Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.
5. Correct all leaks immediately.
14
Figure 15 –Equipment Valve