Honeywell B Service Data page 7

Tp970 and tp9600 series pneumatic thermostats
Hide thumbs Also See for B:
Table of Contents

Advertisement

Table 5. TP974A, TP978A-E, TP979A-E Thermostat Specifications.
Old
New
Model No.
Model No.
TP974A 1000
TP974A 2000
TP978A 1006
No
Replacement
TP978B 1004
No
Replacement
TP978C 1002
No
Replacement
TP978D 1000
No
Replacement
TP978E 1007
TP978E 2007
TP979A 1005
TP979A 2005
TP979B 1003
TP979B 2003
TP979C 1001
TP979C 2001
TP979D 1009
TP979D 2009
TP979E 1006
TP979E 2006
TP970 AND TP9600 SERIES PNEUMATIC THERMOSTATS
Action
Setpoint
DA, 1- or
50-100 F
2-Pipe Sensor
(10-38 C)
Bleed Type
Range
DA Heating
60-73 F
DA Cooling
Heating
RA heating
77-90 F
DA Cooling
Cooling
DA Heating
RA Cooling
RA Heating
RA Cooling
RA (Right Side)
68-82 F
DA (Left Side)
DA Heating
60-90 F
DA Cooling
RA Heating
RA Cooling
DA Heating or
Cooling
RA Heating or
Cooling
DA Heating
DA Cooling
DA Heating
RA Cooling
7
Supply Air
Degrees
Pressure
Throttling
psi (kPa)
Range
18 (124)
3-15 (21-103)
Output
18 (124)
2-10 F
(1.1-5.6 C)
0.18 (1)
1-4 F
18 (124)
Adjustable
2-10 F
(1.1-5.6 C)
13 (90) Day
18 (124) Nite
Special Features
Sensor for use with
RP908 & RP920
Controller
ZEB Energy
Conservation, Setpoint
Stop 73 F (Heating),
77 F (Cooling)
Includes Cover
Special System-
Powered Thermostat
for Carrier
Day/Nite Heat with
night set down; Cool
with night set up.
75-7134—1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents