Pulse input/frequency input jumpers
The Pulse/Frequency Input Module with Digital Outputs (Module ID D) contain jumpers to set the de-
energized Input Filter Cutoff Frequency. All four inputs are factory set to 500 KHz as shown in Figure 23.
To change, use needle nose pliers and move the jumper(s) to the desired position. See the figure below for
the default positions and jumper settings for 100 KHz and 5 KHz.
Pulse/frequency card wiring
The pulse frequency card input is designed to accept a contact closure type transmitter. The typical wiring
circuit is shown below.
Pulse Transmitter
MOSFET, Open Collector, or
Contact Closure drive.
Release F
4/01
Pulse/Frequency Input Board

Figure 20 PI/FI module input filter cutoff frequency setting

R
+
-

Figure 21 Pulse/frequency input connections

UMC800 Controller Installation and User Guide
1
OFF
2
JX1 -
1
2
JX2 -
ON
1
2
V Supply (DC)
L
+
-
+
V Return (DC)
-
Pulse / Frequency Input Card
Input Connections
Mounting and Wiring
Signal Wiring
500KHz
100KHz
5KHz
JA1
JA2
JB1
JB2
JC2
JC1
JD2
JD1
R
1k
T=
Note: All pulse
frequency inputs
share a return
connection that is
common to all pulse /
frequency inputs on a
card.