CONTROLLER
1
L1
(HOT)
24 VAC
L2
GREEN (CLOSED)
ORANGE (OPEN)
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
2
TIME-OUT FUNCTION AVAILABLE WITH ML6294D,F MODELS.
3
500 OHM POTENTIOMETER.
Fig. 9. ML6294D,F typical wiring diagram.
The ML6194/ML6294 has a plastic housing with two tapped
holes for 1/2 in. (13 mm) conduit fittings.
ML6194 and ML6294 Models with Factory-
mounted Auxiliary Switches (see Fig. 10)
ML6194C,F and ML6294C,F models have two nonadjustable
low voltage rated spdt auxiliary switches that are factory set to
make common to normally open at 12° and 82° rotation from
closed (counterclockwise). See Fig. 10.
COMMON
12
NO
INTERNAL
NC
AUXILIARY
COMMON
SWITCH
82
3A, 24 VAC
NO
NC
SWITCHES SHOWN AT ACTUATOR (CCW)
CLOSED POSITION.
Fig. 10. ML6194C,F and ML6294 Actuator wiring for
auxiliary switches.
ML6194 and ML6294 Wiring for Common
Transformer
Fig. 11 through 13 show typical wiring for ML6194 and
ML6294 Non-Spring Return DCA using a common
transformer.
ML6194, ML6294 NON-SPRING RETURN DIRECT COUPLED ACTUATORS
ML6294
B
BLUE
MOTOR
W
YELLOW
2
TIME OUT
T2
RED
T1
BLACK
TAN
3
M11280A
WHITE/RED
WHITE/BLUE
WHITE/YELLOW
BLACK/RED
BLACK/BLUE
BLACK/YELLOW
M7877A
1
L1
(HOT)
L2
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
Fig. 11. Common transformer with two controller outputs
and two ML6194A,C or ML6294A,C Actuators.
1
L1
(HOT)
L2
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
Fig. 12. Common transformer with two controller outputs
and two ML6194D,F or ML6294D,F Actuators.

OPERATION

The ML6194 and ML6294 Non-Spring Return DCA are
designed to be used in ventilating and air conditioning
installations to operate dampers, ventilation flaps, and louvers
requiring up to 300 lb-in. torque.
The ML6194 and ML6294 Non-Spring Return DCA are
operated by an spdt floating controller. When using an spdt
floating controller, actuator is driven toward fully open
(clockwise) position when controller makes B contact and
toward fully closed (counterclockwise) position when
controller makes W contact. It stops when neither contact is
made.
7
ML6194A,C
ML6294A,C
CONTROLLER
BLUE
YELLOW
BLACK
ML6194A,C
ML6294A,C
CONTROLLER
BLUE
YELLOW
BLACK
M11277A
ML6194D,F
ML6294D,F
CONTROLLER
BLUE
YELLOW
RED
BLACK
ML6194D,F
ML6294D,F
CONTROLLER
BLUE
YELLOW
RED
BLACK
M11278A
63-2511—1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ml6294