Planning The Installation - Honeywell enviracaire Elite F300E Product Data

Electronic air cleaner
Hide thumbs Also See for enviracaire Elite F300E:
Table of Contents

Advertisement

F300E ELECTRONIC AIR CLEANER
3
6
8 (162)
SYSTEM
3
6
4
(172)
F300
IN.
MM
406 X 635
16 X 25
16 X 20
406 X 508
508 X 635
20 X 25
20 X 20
508 X 508
Fig. 2. Installation dimensions of Electronic Air Cleaner in in. (mm).

PLANNING THE INSTALLATION

Application
The F300E Electronic Air Cleaner is used in a forced air
heating, cooling, or ventilating system. It removes airborne
particles from the air circulated through it. All models have
an internal air flow switch that operates the air cleaner when
the system blower is on.
Review Installation Requirements
The air cleaner should be installed where all the air passing
through the system circulates through it. The best location is
in the return air duct next to the blower compartment so the
air cleaner can help keep the blower motor and evaporator
coils clean.
IMPORTANT
Do not mount in the discharge air duct.
68-0240-1
DIM. E
(SEE TABLE)
DIM. A
(SEE
TABLE)
5
8
(16)
2-1/2
(63)
DIM. A
DIM. B
IN.
MM
IN.
14 7/16
367
16 3/16
14 7/16
367
16 3/16
18 7/16
468
20 3/16
18 7/16
468
20 3/16
DIM. C (SEE TABLE)
DIM. D (SEE TABLE)
DIM. D
DIM. C
MM
IN.
MM
IN.
411
23 1/4
591
25
411
18 1/4
457
20
513
23 1/4
591
25
513
18 1/4
457
20
For most efficient air cleaning, airflow must be spread evenly
across the face of the air cleaner. If the duct is a different
size than the air cleaner cabinet, gradual transitions are
recommended. If the duct turns sharply just before the air
cleaner, turning vanes are recommended.
Applications with Air Conditioning
The air cleaner should be installed upstream from the
evaporator coil. The air cleaner will help keep the coil clean,
reducing maintenance.
Applications with a Humidifier
An evaporative humidifier can be mounted upstream from
the air cleaner. An atomizing humidifier should be mounted
downstream from the air cleaner, even though hard water
salts will be blown into the living space and deposited as
dust. If an atomizing humidifier must be mounted upstream
from the air cleaner:
4
(SEE TABLE)
DIM. E
MM
IN.
MM
626
2 3/4
70
2 3/4
509
70
2 3/4
626
70
2 3/4
509
70
M14731
DIM. B
7
8
(22)

Hide quick links: