Installing Your Cooker
Connecting to the gas supply
Means of isolation shall be provided at the shut off point by
either an approved quick connect device or a Type 1 man-
ual shut off valve. The outlet of t he quick conn ect device
shall be at, or below, the horizontal position.
Connection to t he g as suppl y should be made using th e
Aquaknect AS /NZS 18 69 cl ass B hose assembly with an
internal diameter of not less than 10mm and regulator (reg-
ulator for use with natural gas)
NOTE: Maximum length of hose 900mm.
The temperature rise of the areas at the rear of the cooker
that are likely to come into contact with the flexible hose do
not exceed 70˙C.

Ventilation requirements

Ventilation must be as specified by AS5601 Installation code.
The room containing the appliance should have an air sup -
ply.
An applia nce should be installed i n a locati on for complete
combustion of gas, proper flueing and to maintain ambient
temperature o f th e immediate sur rounding at safe limits,
under normal conditions.
LP Gas only - Do not install this appliance in a room below
ground level. This does not preclude installation into rooms
which are basements with respect to one side of the build -
ing, but open to ground level on the opposite side.
Failure to install appliances correctly is dangerous and could
lead to prosecution.
After installation make sure all connections are gas
sound.
Commissioning
Pressure settings:
Natural Gas - 1.0 kPa
Butane - 2.75 kPa
Propane - 2.75 kPa
Hob
Turn on gas supply and check for soundness at the hot-
plate injector. Light two burners and check that the pres-
sure is correct.