Haier AB092XCERA Service Manual page 11

X multi series
Hide thumbs Also See for AB092XCERA:
Table of Contents

Advertisement

Item
Function
Rating capacity
Power input (indoor + outdoor)
Current input (indoor + outdoor)
EER / COP
Minimum capacity
Power input
Maximum capacity
Power input (indoor + outdoor)
Power source
Max.Running current (indoor + outdoor)
Power facor(under rating power input)
Fuse size (recommended size)
Compressor
Fan
Heat exchanger
Dimension
(WxDxH)
Refrigerant control method
Defrosting method
Crankcase heater power
Noise level
Weight
Refrigerant
Pipe
Connecting method
Between I.D &O.D
1. The above performance data are from the combination of AU362XHERA+2*AD092XLERA+2*AD122XLERA.
2. Large drop and long piping installation will obviously reduce the total capacity.
Model / Manufacture
Oil charge and type
Type
Number
Type × Number
Speed
Motor output/input power
Air-flows (H/M/L)
Type / Diameter
Face area
External
Package
H/M/L
Net / Shipping
Type / Charge
No need to recharge
Recharge
Liquid
Gas
Drop between IU & OU
Piping length between IU & OU
Total liquid piping length
Max.Drop between IU &OU
Max.Drop between IU & IU
Max.Piping length between IU & OU
Max.Total length
-11-
Model
AU362XHERA
Cooling
——
W
10000
W
3200
A
14.3
3.13
W/W
W
1500
W
550
11000
W
4000
W
1PH, 220-230V~, 50Hz
——
A / A
18.1
——
99%
A
TNB220FLBM / MELCO
——
——
Twin Rotary (DC inverter)
——
——
——
r/min
W
m³/h
mm
1068x340x830
mm
1100x440x979
mm
——
Automatic by reversible cycle
——
W
dB(A)
kg / kg
kg
m
g/m
mm
mm
——
m
m
m
m
10(indoor unit lower than outdoor unit)
m
15 (indoor unit higher than outdoor unit)
m
m
Heating
11000
3200
14.3
3.44
1800
550
11500
4000
18.1
99%
30
870CC
1
Axial × 1
990/ 840/ 590
130/300
about 4300
TP2M / 7.0
about 0.75
PMVs
35
59/-/-
74 / 89
R410A / 3.0
40
20
5* Φ6.35
5* Φ9.52
Flared
≤5
≤10
≤40
25
60