state).
The indoor heat exchanger sensor tests the temperature of the indoor heat exchanger. If the
temperature is higher than 55 , decrease the rotate speed of the compressor and do the high
temperature-preventing protection of the indoor heat exchanger; if the temperature of the indoor heat
exchanger is lower than 47 , recover to the normal control.
TC
Fgh_t1 2
Fgh_t2 2
Fgh_t3 2
Fgh_t4—2
Fgh_t5—2
Normal
N Decreasing at the speed of 1HZ/1 second
P Decreasing at the speed of 1Hz/10 seconds
Q Continue to keep the last-time instruction cycle
R Increasing at the speed of 1Hz/10seconds
Remarks: the outdoor unit
5.2.6.3 The control of preventing the overcurrent of the compressor
●During the starting process of the compressor, if the curren of the compressor is greater than 12A for
3 seconds, stop the compressor and alarm, after 3 minutes, start it again, if such state appears 3
times in 20 minutes, stop the compressor and alarm, and confirm the malfunction. Then continue to
run it only after the the power is off.
●During the starting process of the compressor, if the AC current is greater than 11A, the frequency of
the compressor decreases at the speed of 1HZ/second.
●During the starting process of the compressor, if the AC current is greater than 10A, the frequency of
the compressor decreases at the speed of 0.1HZ/second.
●During the starting process of the compressor, if the AC current is greater than 9.5A, the frequency
of the compressor increases at the prohibited speed.
●During the starting process of the compressor, if the AC current is greater than 9A, the frequency of
the compressor increases at the speed of no faster than 0.1HZ/second.
5.2.6.4 The protection function of AC current:
During the starting process of the compressor, if the AC current is greater than 10.5A, the frequency
of the compressor decreases at the speed of 1HZ/second.
During the starting process of the compressor, if the AC current is greater than 9.5A, the frequency of
the compressor decreases at the speed of 0.1HZ/second.
During the starting process of the compressor, if the AC current is greater than 9.0A, the frequency of
the compressor increases at the prohibited speed.
During the starting process of the compressor, if the AC current is greater than 8A, the frequency of
the compressor increases at the speed of no faster than 0.1HZ/second.
HSM18HEKC/HRAC03/R2(DB)HUM18HC03/R2(DB)-SM
The compressor stops
Fgh_t1 65
N Decreasing the frequency rapidly Fgh_t2 63
P Decreasing the frequency slowly
Fgh_t3
Q Prohibiting increasing the frequency
Fgh_t4
R Increasing slowly
26
Function and control
55
52
Fgh_t5
48
Domestic Air Conditioner