7.3.1 Thermistor or Related Abnormality

Indoor Display
E1: Room temperature sensor failure
E2: Heat-exchange sensor failure
outdoor display
LED1 flash 10 times Frost-removing temperature sensor failure
LED1 flash 11 times Suction temperature sensor failure
LED1 flash 12 times Ambient temperature sensor failure
LED1 flash 13 times Exhaust temperature sensor failure
Method of
The temperatures detected by the thermistors are used to determine thermistor errors
Malfunction
Detection
Malfunction
when the thermistor input is more than 4.92V or less than 0.08V during compressor
Decision
operation.
Conditions
Note: The values vary slightly in some models
Supposed
Faulty connector connection
Causes
Faulty thermistor
Faulty PCB
Troubleshooting
* Caution Be sure to turn off power switch before connect or disconnect connector,
Check the connector onnection.
Thermistor resistance check
Thermistor resistance check method:
Remove the connector of the thermistor on the PCB, and measure the resistance of thermistor using tester.The relationship
between normal temperature and resistance is shown in the value of indoor thermistor.
2HUM18HC03/R2(DB)-SM
damage may be occurred.
Is it normal?
Yes
Is it normal?
Yes
50
NO
Correct the connection
NO
Replace the thermistor
Replace the indoor unit PCB